15
|
Technical data
Installer reference guide
205
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
15.8 Technical specifications: Gas boiler
15.8.1 General
EHYKOMB33AA*
Condensing boiler
Yes
Low-temperature boiler
No
B1 boiler
No
Cogeneration space heater
No
Combination heater
Yes
Related heat pump model
CHYHBH05/CHYHBH08
Function
Heating – Domestic hot water
Heat pump module
CHYHBH05
CHYHBH08
Device category
(a)
B
23
, B
33
, C
13(x)
, C
33(x)
, C
43(x)
, C
53(x)
,
C
63(x)
, C
83(x)
, C
93(x)
Gas
Gas consumption (G20, Natural gas E/H)
0.79~3.39 m
3
/h
Gas consumption (G25, Natural gas LL/L)
0.89~3.92 m³/h
Gas consumption (G31, Liquefied Propane gas)
0.30~1.29 m
3
/h
Maximum flue gas temperature domestic hot
water
70°C
Massive flow glue gas (maximum)
15.1 g/s
Available fan pressure
75 Pa
NOx class
6
NOx
36 mg/kWh
P
1
at 30% of rated input (30/37)
8.8 kW
P
4
rated output (80/60)
26.6 kW
η
1
efficiency at P
1
97.5%
η
4
efficiency at P
4
88.8%
Standby heat loss (P
stby
)
0.038 kW
Daily fuel consumption, Q
fuel
22.514 kWh
Daily electricity consumption, Q
elec
0.070 kWh
Central heating
Maximum pressure space heating circuit
3 bar
Maximum space heating water temperature
90°C
Nominal load (upper value) Q
n
(H
s
)
8.2~30.0 kW
Nominal load (lower value) Q
n
(H
i
)
7.6~27.0 kW
Output at 80/60°C (P
n
)
7.5~26.6 kW
Nominal output
8.2~26.6 kW