8
|
Configuration
Installer reference guide
141
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
Prerequisite:
Flashing LED above the button and an error code on the main
display.
Prerequisite:
Check the meaning of the error code (see
186]) and resolve the cause.
1
Press to restart the gas boiler.
Maximum space heating supply temperature
See the user reference guide of the indoor unit for more details.
Domestic hot water temperature
See the user reference guide of the indoor unit for more details.
Keep hot function
This function must be deactivated through the parameter settings of the gas boiler.
Frost protection function
The boiler is equipped with an internal frost protection function that automatically
operates when necessary, even if the boiler is turned off. If the heat exchanger
temperature drops too low, the burner will switch on until the temperature is
sufficiently high again. When frost protection is active, is displayed on the service
display.
To set the parameters via the service code
The gas boiler is factory set in accordance with the default settings. Take into
account the remarks in the table below when changing the parameters.
1
Press simultaneously on and until appears on the main and the service
display.
2
Use the and buttons to set (service code) on the main display.
3
Press the button to set the parameter on the service display.
4
Use the and buttons to set the parameter to the desired value on the
service display.
5
When all settings are done, press until appears on the service display.
Result:
The gas boiler has now been reprogrammed.
INFORMATION
▪
Press the button to exit the menu without storing the parameter changes.
▪
Press the button to load the default settings of the gas boiler.
Parameters on the gas boiler
Parameter
Setting
Range
Default
settings
Description
Service code
—
—
To access the installer settings,
enter the service code (=15)