8
|
Configuration
Installer reference guide
121
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
INFORMATION
During disinfection of the domestic hot water tank, the DHW temperature can
exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the applicable legislation.
#
Code
Description
[A.4.5]
[6‑0E]
Maximum setpoint
The maximum temperature that users can select
for the domestic hot water. You can use this
setting to limit the temperature at the hot water
taps.
The maximum temperature is NOT applicable
during disinfection function. See disinfection
function.
In case of [E‑06]=1 (tank installed):
▪
[E‑07]≠6: 40~75°C (default: 75°C)
▪
[E‑07]=6: 40~60°C (default: 60°C)
In case of [E‑06]=0 (no tank installed):
▪
40~65°C (default: 65°C)
Contact/helpdesk number
#
Code
Description
[6.3.2]
N/A
Number that users can call in case of problems.
8.1.3 Advanced configuration/optimisation
Space heating operation: advanced
Preset leaving water temperature
You can define preset leaving water temperatures:
▪
economic (denotes the desired leaving water temperature which results in the
lowest energy consumption)
▪
comfort (denotes the desired leaving water temperature which results in the
highest energy consumption).
Preset values make it easy to use the same value in the schedule or to adjust the
desired leaving water temperature according to the room temperature (see
modulation). If you later want to change the value, you ONLY have to do it in one
place. Depending on whether the desired leaving water temperature is weather
dependent or NOT, the desired shift values or the absolute desired leaving water
temperature should be specified.
NOTICE
The preset leaving water temperatures are ONLY applicable for the main zone, as the
schedule for the additional zone consists of On/OFF actions.