8
|
Configuration
Installer reference guide
128
C08AF + EHYKOMB33A
Daikin Altherma R Hybrid
4P471761-1E – 2020.10
#
Code
Description
[A.3.1.1.6.1]
[F-0B]
The shut-off valve:
▪
0 (
No
)(default): is NOT influenced by heating
demand.
▪
1 (
Yes
): closes when there is NO heating
demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
Operation range
Depending on the average outdoor temperature, the operation of the unit in space
heating is prohibited.
Space heating OFF temp
: When the averaged outdoor temperature raises
above this value, space heating is turned OFF to avoid overheating.
#
Code
Description
[A.3.3.1]
[4-02]
14°C~35°C (default: 25°C)
Depending on [1‑0A], the actual outdoor
temperature will be averaged over the selected
time period. Refer to
▪
[4‑02]>25°C: heat pump will be prohibited
when the outdoor temperature reaches [4‑02].
This temperature can be different from the
outdoor average temperature.
▪
[4‑02]<25°C and [1‑0A]≠0: heat pump will be
prohibited when the outdoor temperature
reaches [4‑02]. This temperature can be
different from the actual outdoor temperature.
▪
[4‑02]<25°C and [1‑0A]=0: heat pump will be
prohibited when the outdoor temperature
reaches [4‑02]. There will be no average of the
outdoor temperature.
When the above cases occur, then the outdoor
unit will still be able to operate for DX units.
Domestic hot water control: advanced
Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled or sch
reheat.
You can define preset tank temperatures:
▪
storage economic
▪
storage comfort
▪
reheat
▪
reheat hysteresis
Preset values make it easy to use the same value in the schedule. If you later want
to change the value, you only have to do it in 1 place (see also operation manual
and/or user reference guide).