5 Configuration

Installation manual

18

EBLQ+EDLQ011~W1

Daikin Altherma low temperature monobloc

4P522031-1 – 2018.01

#

Code

Description

[7.7.2.1]

[0-00]

[0-01]

[0-02]

[0-03]

Weather-dependent curve (heating):

[0-00]

[0-01]

Ta

Tt

[0-03]

[0-02]

▪ T

t

:  Target  leaving  water  temperature

(additional)

▪ T

a

: Outdoor temperature

[7.7.2.2]

[0-04]

[0-05]

[0-06]

[0-07]

Weather-dependent curve (cooling):

[0-04]

[0-05]

Ta

Tt

[0-07]

[0-06]

▪ T

t

:  Target  leaving  water  temperature

(additional)

▪ T

a

: Outdoor temperature

Leaving water temperature: Delta T source

#

Code

Description

[A.3.1.3.1]

[9-09]

Heating: required temperature
difference between entering and
leaving water.

In case a minimum temperature
difference is required for the good
operation of the heat emitters in heating
mode.

[A.3.1.3.2]

[9-0A]

Cooling: required temperature
difference between entering and
leaving water.

In case a minimum temperature
difference is required for the good
operation of the heat emitters in cooling
mode.

Leaving water temperature: Modulation

#

Code

Description

[A.3.1.1.5]

[8-05]

Leaving water temperature modulation:

▪ 0 (No): Disabled

▪ 1  (Yes):  Enabled.  The  leaving  water

temperature  is  calculated  according
to  the  difference  between  desired
and actual room temperature.
This  allows  better  matching  of  the
heat 

pump 

capacity 

to 

actual

required  capacity  and  results  in  less
start/stop  cycles  of  the  heat  pump
and more economic operation.

#

Code

Description

N/A

[8-06]

Leaving water temperature maximum
modulation:

0°C~10°C (default: 3°C)

Requires modulation to be enabled.

This is the value by which the desired
leaving water temperature is increased
or lowered.

INFORMATION

When  leaving  water  temperature  modulation  is  enabled,
the  weather‑dependent  curve  needs  to  be  set  to  a  higher
position  than  [8-06]  plus  the  minimum  leaving  water
temperature  setpoint  required  to  reach  a  stable  condition
on  the  comfort  setpoint  for  the  room.  To  increase
efficiency, modulation can lower the leaving water setpoint.
By  setting  the  weather‑dependent  curve  to  a  higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.

a

+[8-06]

−[8-06]

b

Ta

Tt

a

Weather-dependent curve

b

Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.

Leaving water temperature: Emitter type

#

Code

Description

[A.3.1.1.7]

[9-0B]

Reaction time of the system:

▪ 0: Quick (default)

Example: 

Small  water  volume  and

fan coils.

▪ 1: Slow

Example: 

Large  water  volume,  floor

heating loops.

Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.

5.2.6

Domestic hot water control

#

Code

Description

[A.4.1]

[6-0D]

Domestic hot water Type:

▪ 0 (Reheat only): Only reheat operation

is allowed.

▪ 1 ( sched.)(default): Same as

2,  but  between  the  scheduled  heatup
cycles, reheat operation is allowed.

▪ 2  (Scheduled  only):  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

Summary of Contents for Altherma EBLQ014CAV3

Page 1: ...ow temperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ011CAV3 EBLQ014CAV3 EBLQ016CAV3 EBLQ011CAW1 EBLQ014CAW1 EBLQ016CAW1 EDLQ011CAV3 EDLQ014CAV3 EDLQ016CAV3...

Page 2: ...B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU...

Page 3: ...sti za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uv...

Page 4: ...py the system settings from the first to the second user interface 14 5 1 4 To copy the language set from the first to the second user interface 15 5 1 5 Quick wizard Set the system layout after first...

Page 5: ...5 C in domestic hot water operation mode 3 2 Preparing water piping NOTICE In case of plastic pipes make sure they are fully oxygen diffusion tight according to DIN 4726 The diffusion of oxygen into t...

Page 6: ...m flow rate can be checked by way of the pump test check that the user interface does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely cont...

Page 7: ...nd washers field supply as follows 150 6 2 0 350 3 4 5 3 5 5 a mm 2 6 1 5 6 M12 a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is...

Page 8: ...n places where strong wind can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rub...

Page 9: ...ng Prevent from freezing 5 C 10 15 10 C 15 25 15 C 20 35 20 C 25 25 C 30 NOTICE The required concentration might differ depending on the type of glycol ALWAYS compare the requirements from the table a...

Page 10: ...ter field supply indicates a pressure of 2 0 bar 5 Purge as much air as possible from the water circuit For instructions see 6 Commissioning on page 21 6 Refill the circuit until the pressure is 2 0 b...

Page 11: ...emove reposition the switch box and gain access to other components during service CAUTION Do NOT push or place redundant cable length in the unit 4 4 2 To connect the main power supply 1 Connect the...

Page 12: ...4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring re...

Page 13: ...er NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in...

Page 14: ...other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result...

Page 15: ...tion select Confirm layout and press Confirm layout Please confirm the system layout The system will restart and will be ready for first startup OK Cancel Confirm Adjust 5 The user interface re initia...

Page 16: ...d backup heater Backup heater EKMBUHCA3V3 can only be configured to be a 3V3 backup heater Unified backup heater EKMBUHCA9W1 can be configured in 4 ways 3V3 1 230 V 1 step of 3 kW 6V3 1 230 V 1st step...

Page 17: ...sensor connected to option box EK2CB07CAV3 INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor Code Description A 2 2 F 6 D 04 PCC by digital inputs 0 No 1 Y...

Page 18: ...aximum modulation 0 C 10 C default 3 C Requires modulation to be enabled This is the value by which the desired leaving water temperature is increased or lowered INFORMATION When leaving water tempera...

Page 19: ...ature at the hot water taps INFORMATION There is a risk of space heating cooling capacity shortage comfort problem in case of frequent domestic hot water operation frequent and long space heating cool...

Page 20: ...thod Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room the...

Page 21: ...it The shut off valves are properly installed and fully open The pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume i...

Page 22: ...sure the room temperature control the leaving water temperature control and the domestic hot water control are turned OFF via the user interface 3 Go to A 7 4 Installer settings Commissioning Actuato...

Page 23: ...es 2 Press for more than 5 seconds 8 Technical data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is avail...

Page 24: ...actory setting of all switches OFF 4 Legend A1P Printed circuit board main A2P V3 only Printed circuit board service A2P W1 only Printed circuit board inverter A3P Printed circuit board noise filter A...

Page 25: ...hydro switch box Use normal kWh rate power supply for hydro switch box A1P Main PCB A2P Current loop PCB English Translation B1L Flow sensor E11H Flextube heater 15 6 W E12H Expansion vessel heater 50...

Page 26: ...ckup heater F1T F2T Thermal fuse backup heater F1U Fuse T 5 A 500 V backup heater option K1M Contactor backup heater step 1 English Translation K1R Relay backup heater step 1 K2M Contactor backup heat...

Page 27: ...om thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity...

Page 28: ...4P522031 1 2018 01 Copyright 2018 Daikin 4P522031 1 0000000B...

Reviews: