6 Energy saving tips

Operation manual

17

EBBH/X11+16DF + EBVH/X11+16S(U)18+23DJ
Daikin Altherma 3 R F+W
4P643605-2 – 2021.09

Item

Description

Y1, Y2,

Y3, Y4

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Domestic hot water tank

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

5.9.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Main zone – Heating

[2.4] 

Main zone

 > 

Setpoint

mode

WD heating, fixed cooling

OR 

Weather dependent

Main zone – Cooling

[2.4] 

Main zone

 > 

Setpoint

mode

Weather dependent

Additional zone – Heating

[3.4] 

Additional zone

 >

Setpoint mode

WD heating, fixed cooling

OR 

Weather dependent

Additional zone – Cooling

[3.4] 

Additional zone

 >

Setpoint mode

Weather dependent

Tank

[5.B] 

Tank

 > 

Setpoint mode

Restriction: 

Only available to

installers.

Weather dependent

To change the type of weather-dependent curve

To change the type for all zones (main + additional) and for the tank,
go to [2.E] 

Main zone

 > 

WD curve type

.

Viewing which type is selected is also possible via:

▪ [3.C] 

Additional zone

 > 

WD curve type

▪ [5.E] 

Tank

 > 

WD curve type

Restriction: 

Only available to installers.

To change the weather-dependent curve

Zone

Go to …

Main zone – Heating

[2.5] 

Main zone

 > 

Heating WD

curve

Main zone – Cooling

[2.6] 

Main zone

 > 

Cooling WD

curve

Additional zone – Heating

[3.5] 

Additional zone

 >

Heating WD curve

Additional zone – Cooling

[3.6] 

Additional zone

 >

Cooling WD curve

Zone

Go to …

Tank

Restriction: 

Only available to

installers.

[5.C] 

Tank

 > 

WD curve

INFORMATION

Maximum and minimum setpoints

You cannot configure the curve with temperatures that are
higher  or  lower  than  the  set  maximum  and  minimum
setpoints for that zone or for the tank. When the maximum
or minimum setpoint is reached, the curve flattens out.

To fine-tune the weather-dependent curve: slope-offset curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

To fine-tune the weather-dependent curve: 2-points curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone or tank:

You feel …

Fine-tune with

setpoints:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Y2

(a)

Y1

(a)

X1

(a)

X2

(a)

OK

Cold

OK

Hot

Cold

OK

Cold

Cold

Cold

Hot

Hot

OK

Hot

Cold

Hot

Hot

(a)

See 

"5.9.2 2-points curve"

 [

4

 16].

6

Energy saving tips

Tips about room temperature

▪ Make  sure  the  desired  room  temperature  is  NEVER  too  high  (in

heating  mode)  or  too  low  (in  cooling  mode),  but  ALWAYS
according  to  your  actual  needs.  Each  saved  degree  can  save  up
to 6% of heating/cooling costs.

▪ Do  NOT  increase/decrease  the  desired  room  temperature  to

speed up space heating/cooling. The space will NOT heat up/cool
down faster.

▪ When  your  system  layout  contains  slow  heat  emitters  (example:

underfloor  heating),  avoid  large  fluctuation  of  the  desired  room
temperature  and  do  NOT  let  the  room  temperature  drop  too  low/
rise  too  high.  It  will  take  more  time  and  energy  to  heat  up/cool
down the room again.

Summary of Contents for Altherma EBBH11DF6V

Page 1: ...al Daikin Altherma 3 R F W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W EBVH11S18 23DJ6V EBVH11S18 23DJ9W EBVH16S18 23DJ6V EBVH16S18 23DJ9W EBVH16SU23DJ6V EBVX11S18 23DJ6V EBVX11S18 23DJ9W EBVX16S18 23DJ6V EBVX16S18 23DJ9W ...

Page 2: ...figuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure the best possible performance Request the installer to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If NOT request him to do so Keep...

Page 3: ...pliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are marked with the following symbol This m...

Page 4: ...NG Air purging heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into the room when you purge air from the he...

Page 5: ...on C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However for leaving water temperature control and external room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the desired room temperature During room temperature...

Page 6: ...g water temperature Possible actions on this screen Go through the temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating cooling control 412 5 8 Schedule screen Example 414 5 9 Weather dependent curve 415 User reference guide 4 3 Domestic hot water To turn tank ...

Page 7: ...ng any button or rotating any dial awakens the display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc on the left side of the display when you can use the left dial Turn then press the left dial Navigate through the menu structure Turn the left dial Choose...

Page 8: ...etpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 7 5 Electricity price High Medium Low Schedule 8 1 Energy data Electricity input Produced heat 5 Tank Powerful operation Comfort setpoint Eco setpoint Reheat setpoint Schedule WD cu...

Page 9: ...Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is currently being used for space heating e3 Smart energy is currently being used for domestic hot water f Space operation mode Cooling Heating g Outdoor quiet mode g1 6 Measured outdoor temperature a g...

Page 10: ...ture 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the applicable symbol for your additional zone emitter type Set the leaving water temperature for the additional zone if present Submenu Description 4 Space heating coolin...

Page 11: ...ation ON b Space heating cooling operation OFF Tank heating operation 55 21 35 45 c 55 21 35 45 d c Tank heating operation ON d Tank heating operation OFF 5 4 2 To turn ON or OFF Space heating cooling operation NOTICE Room frost protection Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However f...

Page 12: ...ing based on the outdoor temperature Restricted per month according to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You set the space operation mode to Automatic 1 Go to 4 2 Space heating cooling Operation mode schedule 2 Select a month 3 For each month select an option Reversible Not restricted Heating only Restricted Cooling only Restricted ...

Page 13: ... the temperature of the domestic water entering the DHW tank example 15 C At 00 00 the DHW tank is programmed to heat up the water to a preset value example Comfort 60 C During the morning you consume hot water and the DHW tank temperature decreases At 14 00 the DHW tank is programmed to heat up the water to a preset value example Eco 50 C Hot water is available again During the afternoon and even...

Page 14: ...the schedule to the other weekdays 5 Program the schedule for Saturday and copy it to Sunday 6 Give the schedule a name To go to the schedule 1 Go to 1 1 Room Schedule 2 Set scheduling to Yes 3 Go to 1 2 Room Heating schedule To clear the content of the week schedule 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Delete Delete Rename Select 3 Select O...

Page 15: ...ter list and confirm the selected character The schedule name can contain up to 15 characters 5 Confirm the new name INFORMATION Not all schedules can be renamed 5 9 Weather dependent curve 5 9 1 What is a weather dependent curve Weather dependent operation The unit operates weather dependent if the desired leaving water or tank temperature is determined automatically by the outdoor temperature It...

Page 16: ... changes and proceed 5 9 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is...

Page 17: ... 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Zone Go to Tank Restriction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for that zone ...

Page 18: ...ed both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Please contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuously operating ignition sources examp...

Page 19: ...r the domestic hot water production and space heating For EBBH X The backup heater automatically takes over the heat load and the booster heater in the optional tank takes over the domestic hot water production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioning ...

Page 20: ...er used in any type of building for domestic purposes LWT Leaving water temperature Water temperature at the water outlet of the unit 11 Installer settings Tables to be filled in by installer 11 1 Configuration wizard Setting Fill in System Indoor unit type read only Backup heater type 9 3 1 read only Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 Booster heater capacity 9 4 1 if appli...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P643605 2 2021 09 Copyright 2021 Daikin 4P643605 2 0000000N Verantwortung für Energie und Umwelt ...

Reviews: