5 Operation

Operation manual

13

EBBH/X11+16DF + EBVH/X11+16S(U)18+23DJ
Daikin Altherma 3 R F+W
4P643605-2 – 2021.09

2

Adjust the desired leaving water temperature.

+

35

°C

2

a

b

Main zone

+

45

°C

3

a

b

Additional zone

a

 Actual leaving water temperature

b

 Desired leaving water temperature

5.7

Domestic hot water control

5.7.1

Reheat mode

In  reheat  mode  the  DHW  tank  continuously  heats  up  to  the
temperature  shown  on  the  home  screen  (example:  50°C)  when  the
temperature drops below a certain value.

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

Tt

T

t

DHW tank temperature

t

Time

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank

 > 

Heat up mode

 > 

Reheat only

.

INFORMATION

When  the  DHW  tank  mode  is  reheat,  the  risk  for  capacity
shortage  and  comfort  problem  is  significant.  In  case  of
frequent  reheat  operation,  space  heating/cooling  function
is regularly interrupted.

5.7.2

Scheduled mode

In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.

Example: 

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

▪ Initially,  the  DHW  tank  temperature  is  the  same  as  the

temperature  of  the  domestic  water  entering  the  DHW  tank
(example: 

15°C

).

▪ At 00:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Comfort

 

= 60°C

).

▪ During  the  morning,  you  consume  hot  water  and  the  DHW  tank

temperature decreases.

▪ At 14:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Eco

 = 

50°C

). Hot water is available again.

▪ During  the  afternoon  and  evening,  you  consume  hot  water  again

and the DHW tank temperature decreases again.

▪ At 00:00 the next day, the cycle repeats.

5.7.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

Domestic hot water tank temperature

t

Time

5.7.4

Using DHW powerful operation

About powerful operation

Powerful operation

 allows the domestic hot water to be heated by

the  backup  heater  or  booster  heater.  Use  this  mode  on  days  when
there is more hot water usage than usual.

To check if powerful operation is active

If 

 is displayed on the home screen, powerful operation is active.

Activate or deactivate 

Powerful operation

 as follows:

1

Go to [5.1]: 

Tank

 > 

Powerful operation

2

Turn powerful operation 

Off

 or 

On

.

Usage example: You immediately need more hot water

You are in the following situation:

▪ You already consumed most of your domestic hot water.

Summary of Contents for Altherma EBBH11DF6V

Page 1: ...al Daikin Altherma 3 R F W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W EBVH11S18 23DJ6V EBVH11S18 23DJ9W EBVH16S18 23DJ6V EBVH16S18 23DJ9W EBVH16SU23DJ6V EBVX11S18 23DJ6V EBVX11S18 23DJ9W EBVX16S18 23DJ6V EBVX16S18 23DJ9W ...

Page 2: ...figuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure the best possible performance Request the installer to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If NOT request him to do so Keep...

Page 3: ...pliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are marked with the following symbol This m...

Page 4: ...NG Air purging heat emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you want to purge air is sufficiently ventilated Reason Refrigerant might leak into the water circuit and subsequently into the room when you purge air from the he...

Page 5: ...on C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However for leaving water temperature control and external room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the desired room temperature During room temperature...

Page 6: ...g water temperature Possible actions on this screen Go through the temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating cooling control 412 5 8 Schedule screen Example 414 5 9 Weather dependent curve 415 User reference guide 4 3 Domestic hot water To turn tank ...

Page 7: ...ng any button or rotating any dial awakens the display Dials and buttons You use the dials and buttons To navigate through the screens menus and settings of the LCD screen To set values a b c d e Item Description a Left dial The LCD shows an arc on the left side of the display when you can use the left dial Turn then press the left dial Navigate through the menu structure Turn the left dial Choose...

Page 8: ...etpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 7 5 Electricity price High Medium Low Schedule 8 1 Energy data Electricity input Produced heat 5 Tank Powerful operation Comfort setpoint Eco setpoint Reheat setpoint Schedule WD cu...

Page 9: ...Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is currently being used for space heating e3 Smart energy is currently being used for domestic hot water f Space operation mode Cooling Heating g Outdoor quiet mode g1 6 Measured outdoor temperature a g...

Page 10: ...ture 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temperature zones Shows the applicable symbol for your additional zone emitter type Set the leaving water temperature for the additional zone if present Submenu Description 4 Space heating coolin...

Page 11: ...ation ON b Space heating cooling operation OFF Tank heating operation 55 21 35 45 c 55 21 35 45 d c Tank heating operation ON d Tank heating operation OFF 5 4 2 To turn ON or OFF Space heating cooling operation NOTICE Room frost protection Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling room frost protection operation if enabled can still activate However f...

Page 12: ...ing based on the outdoor temperature Restricted per month according to the Operation mode schedule 4 2 To restrict automatic changeover according to a schedule Conditions You set the space operation mode to Automatic 1 Go to 4 2 Space heating cooling Operation mode schedule 2 Select a month 3 For each month select an option Reversible Not restricted Heating only Restricted Cooling only Restricted ...

Page 13: ... the temperature of the domestic water entering the DHW tank example 15 C At 00 00 the DHW tank is programmed to heat up the water to a preset value example Comfort 60 C During the morning you consume hot water and the DHW tank temperature decreases At 14 00 the DHW tank is programmed to heat up the water to a preset value example Eco 50 C Hot water is available again During the afternoon and even...

Page 14: ...the schedule to the other weekdays 5 Program the schedule for Saturday and copy it to Sunday 6 Give the schedule a name To go to the schedule 1 Go to 1 1 Room Schedule 2 Set scheduling to Yes 3 Go to 1 2 Room Heating schedule To clear the content of the week schedule 1 Select the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Delete Delete Rename Select 3 Select O...

Page 15: ...ter list and confirm the selected character The schedule name can contain up to 15 characters 5 Confirm the new name INFORMATION Not all schedules can be renamed 5 9 Weather dependent curve 5 9 1 What is a weather dependent curve Weather dependent operation The unit operates weather dependent if the desired leaving water or tank temperature is determined automatically by the outdoor temperature It...

Page 16: ... changes and proceed 5 9 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently increase or decrease the temperature of the leaving water for different ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is...

Page 17: ... 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Zone Go to Tank Restriction Only available to installers 5 C Tank WD curve INFORMATION Maximum and minimum setpoints You cannot configure the curve with temperatures that are higher or lower than the set maximum and minimum setpoints for that zone ...

Page 18: ...ed both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Please contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The appliance shall be stored in a room without continuously operating ignition sources examp...

Page 19: ...r the domestic hot water production and space heating For EBBH X The backup heater automatically takes over the heat load and the booster heater in the optional tank takes over the domestic hot water production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioning ...

Page 20: ...er used in any type of building for domestic purposes LWT Leaving water temperature Water temperature at the water outlet of the unit 11 Installer settings Tables to be filled in by installer 11 1 Configuration wizard Setting Fill in System Indoor unit type read only Backup heater type 9 3 1 read only Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 Booster heater capacity 9 4 1 if appli...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P643605 2 2021 09 Copyright 2021 Daikin 4P643605 2 0000000N Verantwortung für Energie und Umwelt ...

Reviews: