background image

4 Installation

Installation manual

8

EABH/X16DA+9W

Daikin Altherma – Low temperature split

4P556066-1 – 2018.10

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  must  be  installed  on  the
domestic  cold  water  inlet  connection  in  accordance  with
the applicable legislation.

4.3.2

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

INFORMATION

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

4.3.3

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see installer reference guide) that include the activation of pump in
case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water from the system before it can freeze.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

Adding glycol to the water lowers the freezing point of the water.

The required concentration depends on the lowest expected outdoor
temperature,  and  on  whether  you  want  to  protect  the  system  from
bursting or from freezing. To prevent the system from freezing, more
glycol is required. Add glycol according to the table below.

INFORMATION

▪ Protection  against  bursting:  the  glycol  will  prevent  the

piping  from  bursting,  but  NOT  the  liquid  inside  the
piping from freezing.

▪ Protection  against  freezing:  the  glycol  will  prevent  the

liquid inside the piping from freezing.

Lowest expected
outdoor
temperature

Prevent from
bursting

Prevent from
freezing

–5°C

10%

15%

–10°C

15%

25%

–15°C

20%

35%

–20°C

25%

–25°C

30%

NOTICE

▪ The  required  concentration  might  differ  depending  on

the type of glycol. ALWAYS compare the requirements
from the table above with the specifications provided by
the  glycol  manufacturer.  If  necessary,  meet  the
requirements set by the glycol manufacturer.

▪ The  added  concentration  of  glycol  should  NEVER

exceed 35%.

▪ If the liquid in the system is frozen, the pump will NOT

be  able  to  start.  Mind  that  if  you  only  prevent  the
system from bursting, the liquid inside might still freeze.

▪ When  water  is  at  standstill  inside  the  system,  the

system is very likely to freeze and get damaged.

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

If…

Then…

The system contains a domestic
hot water tank

Only use propylene glycol

(a)

The system does NOT contain a
domestic hot water tank

You can use either propylene
glycol

(a)

 or ethylene glycol

(a)

Propylene glycol, including the necessary inhibitors,
classified as Category III according to EN1717.

WARNING

Ethylene glycol is toxic.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

WARNING

Due  to  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

Adding  glycol  to  the  water  circuit  reduces  the  maximum  allowed
water  volume  of  the  system.  For  more  information,  refer  to  the
chapter  "To  check  the  water  volume  and  flow  rate"  in  the  installer
reference guide.

NOTICE

If  glycol  is  present  in  the  system,  setting  [E-0D]  must  be
set to 1. If the glycol setting is NOT set correctly, the liquid
inside the piping can freeze.

Freeze protection by freeze protection valves

Summary of Contents for Altherma EABH16DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W ...

Page 2: ...ou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących ...

Page 3: ...e 14 5 2 3 Configuration wizard System 14 5 2 4 Configuration wizard Backup heater 15 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 16 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone 18 5 3 3 Information 18 5 4 Menu structure Overview installer settings 19 6 C...

Page 4: ... corrosion Valve towards expansion vessel The valve towards the expansion vessel if equipped MUST be open 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulation in each space heating cooling loop is controlled by remotely controll...

Page 5: ... 9 Domestic hot water tank thermistor 2 d 10 User interface used as room thermostat 2 f 11 Room thermostat 3 or 4 100 mA b 12 Outdoor ambient temperature sensor 2 b 13 Indoor ambient temperature sensor 2 b 14 Heat pump convector 2 100 mA b Field supplied components 15 Shut off valve 2 100 mA b Item Description Wires Maximum running current 16 Electricity meter 2 per meter b 17 Domestic hot water p...

Page 6: ...move the user interface panel also disconnect the cables from the back of the panel to prevent damage 3 1 2 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Fix the wall bracket accessory to the wall level with 2 Ø8 mm bolts 2 a a Optional If you want to fix the unit to the wall from inside the unit provide an additional screw plug 2 Lift the unit 42kg 3 Attach the unit to the wall ...

Page 7: ...piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the indoor unit water connections 2 Connect the outdoor unit field piping on the water IN connection a of the indoor unit 3 Connect the space heating cooling field piping on the space heating water OUT connection b of the indoor unit a b a b a Water IN connection b Space heating water...

Page 8: ...ided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liquid in the system is frozen the pump will NOT be able to start Mind that if you only prevent the system from bursting the liquid inside might still freeze When water is at standstill inside the system the system is very likely to freez...

Page 9: ...installer reference guide or the installation manual of the outdoor unit 4 4 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 4 4 1 About electrical compliance Only for the backup heater of the indoor unit See 4 4 4 To connect the backup heater power supply on page 10 4 4 2 To connect the electrical wiring on the indoor unit 1...

Page 10: ...ices according to the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply M...

Page 11: ...Do NOT cut or remove the backup heater power supply cable 4 4 5 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normal closed valve and a NO normal open valve X2M X1M X2M X1M NO NC M2S M2S 21 29 21 28 2 Fix the cable with cable ties to the cable tie mountings 4 4 6 To connect the ele...

Page 12: ...ountings 4 4 10 To connect the changeover to external heat source 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below X5M A4P X1M YC Y1 Y2 Y3 Y4 X2M X1M X3 X4 X2M X1 X2 L N a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 4 11 To connect the power consumption digital inputs 1 Conn...

Page 13: ...wizard When you turn ON the user interface for the first time via the indoor unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 5 1 1 To access the most use...

Page 14: ...he backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic hot water or not and which tank is used ...

Page 15: ...c valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter 5 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuratio...

Page 16: ... To compensate you can Increase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control For the control of the unit there are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling d...

Page 17: ...her dependent zones Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X X1 X2 Outdoor ambient temperature Y Y1 Y2 Desired tank temperature or leaving water temperature The symbol shown here corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies ...

Page 18: ...settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the uni...

Page 19: ... Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Boo...

Page 20: ...There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON Only for tanks with built in booster heater Booster heater circuit breaker F2B field supply is turned ON The correct pipe size is installed and the pipes are prop...

Page 21: ...es in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the ...

Page 22: ... 8 1 Piping diagram Indoor unit 3D120613 R2T R1T B1PW B1L A B e e B f i g c a b h j d h S1L i A Water side B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut off valve for service f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Backup heater B1L Flow sensor B1PW Space heating water pressure sensor R1T Thermistor heat excha...

Page 23: ...ess Ext thermistor External thermistor Heat pump convector Heat pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch b...

Page 24: ...us Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current English Translation Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact ...

Page 25: ...ternal room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core signal 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core 2 core Only for KRP1HB Changeover to ext heat source output Alarm output Solar input Cooli...

Page 26: ......

Page 27: ......

Page 28: ...4P556066 1 2018 10 Copyright 2018 Daikin 4P556066 1 0000000Q ...

Reviews: