background image

5 Configuration

Installation manual

13

EABH/X16DA+9W
Daikin Altherma – Low temperature split
4P556066-1 – 2018.10

NOTICE

Make  sure  to  select  and  install  the  safety  thermostat
according to the applicable legislation.

In  any  case,  to  prevent  unnecessary  tripping  of  the  safety
thermostat, it is recommended that …

▪ … the safety thermostat is automatically resettable.

▪ …  the  safety  thermostat  has  a  maximum  temperature

variation rate of 2°C/min.

▪ …  there  is  a  minimum  distance  of  2  m  between  the

safety  thermostat  and  the  motorised  3‑way  valve
delivered with the domestic hot water tank.

INFORMATION

After  it  is  installed,  do  NOT  forget  to  configure  the  safety
thermostat.  Without  configuration,  the  indoor  unit  will
ignore the safety thermostat contact.

INFORMATION

The  preferential  kWh  rate  power  supply  contact  is
connected to the same terminals (X5M/9+10) as the safety
thermostat.  It  is  only  possible  for  the  system  to  have
EITHER  preferential  kWh  rate  power  supply  OR  a  safety
thermostat.

4.5

Finishing the indoor unit
installation

4.5.1

To close the indoor unit

1

Reinstall the user interface panel.

2

Reinstall the switch box cover and close the switch box.

3

Reinstall the front panel.

NOTICE

When  closing  the  indoor  unit  cover,  make  sure  that  the
tightening torque does NOT exceed 4.1 N•m.

5

Configuration

5.1

Overview: Configuration

This  chapter  describes  what  you  have  to  do  and  know  to  configure
the system after it is installed.

NOTICE

The  explanation  about  the  configuration  in  this  chapter
gives  you  ONLY  basic  explanations.  For  more  detailed
explanation  and  background  information,  see  the  installer
reference guide.

Why

If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:

▪ The calculations of the software

▪ What you can see on and do with the user interface

How

You can configure the system via the user interface.

First  time  –  Configuration  wizard.

  When  you  turn  ON  the  user

interface  for  the  first  time  (via  the  indoor  unit),  the  configuration
wizard starts to help you configure the system.

Restart  the  configuration  wizard.

  If  the  system  is  already

configured, you can restart the configuration wizard. To restart the
configuration  wizard,  go  to  Installer  settings  >  Configuration
wizard.  To  access  Installer  settings,  see 

"5.1.1  To  access  the

most used commands" on page 13

.

Afterwards.

  If  necessary,  you  can  make  changes  to  the

configuration in the menu structure or the overview settings.

INFORMATION

When  the  configuration  wizard  is  finished,  the  user
interface  will  show  an  overview  screen  and  request  to
confirm.  When  confirmed,  the  system  will  restart  and  the
home screen will be displayed.

Accessing settings – Legend for tables

You  can  access  the  installer  settings  using  two  different  methods.
However,  NOT  all  settings  are  accessible  via  both  methods.  If  so,
the  corresponding  table  columns  in  this  chapter  are  set  to  N/A  (not
applicable).

Method

Column in tables

Accessing settings via the breadcrumb in the

menu structure

. To enable breadcrumbs,

press the   button in the home screen.

#

Accessing settings via the code in the

overview field settings

.

Code

See also:

"To access the installer settings" on page 13

"5.4 Menu structure: Overview installer settings" on page 19

5.1.1

To access the most used commands

To change the user permission level

You can change the user permission level as follows:

1

Go to [B]: User profile.

2

Enter the applicable code for the user permission.

▪ Move the cursor from left to right.

▪ Browse  through  the  list  of  digits  and  change  the

selected digit.

▪ Confirm the pincode and proceed.

Installer pin code

The  Installer  pin  code  is 

5678

.  Additional  menu  items  and  installer

settings are now available.

5678

Installer

Advanced user pin code

The Advanced user pin code is 

1234

. Additional menu items for the

user are now visible.

User pin code

The User pin code is 

0000

.

To access the installer settings

1

Set the user permission level to Installer.

2

Go to [9]: Installer settings.

To modify an overview setting

Example: 

Modify [1‑01] from 15 to 20.

Summary of Contents for Altherma EABH16DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W ...

Page 2: ...ou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących ...

Page 3: ...e 14 5 2 3 Configuration wizard System 14 5 2 4 Configuration wizard Backup heater 15 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 16 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone 18 5 3 3 Information 18 5 4 Menu structure Overview installer settings 19 6 C...

Page 4: ... corrosion Valve towards expansion vessel The valve towards the expansion vessel if equipped MUST be open 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulation in each space heating cooling loop is controlled by remotely controll...

Page 5: ... 9 Domestic hot water tank thermistor 2 d 10 User interface used as room thermostat 2 f 11 Room thermostat 3 or 4 100 mA b 12 Outdoor ambient temperature sensor 2 b 13 Indoor ambient temperature sensor 2 b 14 Heat pump convector 2 100 mA b Field supplied components 15 Shut off valve 2 100 mA b Item Description Wires Maximum running current 16 Electricity meter 2 per meter b 17 Domestic hot water p...

Page 6: ...move the user interface panel also disconnect the cables from the back of the panel to prevent damage 3 1 2 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Fix the wall bracket accessory to the wall level with 2 Ø8 mm bolts 2 a a Optional If you want to fix the unit to the wall from inside the unit provide an additional screw plug 2 Lift the unit 42kg 3 Attach the unit to the wall ...

Page 7: ...piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the indoor unit water connections 2 Connect the outdoor unit field piping on the water IN connection a of the indoor unit 3 Connect the space heating cooling field piping on the space heating water OUT connection b of the indoor unit a b a b a Water IN connection b Space heating water...

Page 8: ...ided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liquid in the system is frozen the pump will NOT be able to start Mind that if you only prevent the system from bursting the liquid inside might still freeze When water is at standstill inside the system the system is very likely to freez...

Page 9: ...installer reference guide or the installation manual of the outdoor unit 4 4 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 4 4 1 About electrical compliance Only for the backup heater of the indoor unit See 4 4 4 To connect the backup heater power supply on page 10 4 4 2 To connect the electrical wiring on the indoor unit 1...

Page 10: ...ices according to the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply M...

Page 11: ...Do NOT cut or remove the backup heater power supply cable 4 4 5 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normal closed valve and a NO normal open valve X2M X1M X2M X1M NO NC M2S M2S 21 29 21 28 2 Fix the cable with cable ties to the cable tie mountings 4 4 6 To connect the ele...

Page 12: ...ountings 4 4 10 To connect the changeover to external heat source 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below X5M A4P X1M YC Y1 Y2 Y3 Y4 X2M X1M X3 X4 X2M X1 X2 L N a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 4 11 To connect the power consumption digital inputs 1 Conn...

Page 13: ...wizard When you turn ON the user interface for the first time via the indoor unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 5 1 1 To access the most use...

Page 14: ...he backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic hot water or not and which tank is used ...

Page 15: ...c valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter 5 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuratio...

Page 16: ... To compensate you can Increase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control For the control of the unit there are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling d...

Page 17: ...her dependent zones Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X X1 X2 Outdoor ambient temperature Y Y1 Y2 Desired tank temperature or leaving water temperature The symbol shown here corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies ...

Page 18: ...settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the uni...

Page 19: ... Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Boo...

Page 20: ...There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON Only for tanks with built in booster heater Booster heater circuit breaker F2B field supply is turned ON The correct pipe size is installed and the pipes are prop...

Page 21: ...es in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the ...

Page 22: ... 8 1 Piping diagram Indoor unit 3D120613 R2T R1T B1PW B1L A B e e B f i g c a b h j d h S1L i A Water side B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut off valve for service f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Backup heater B1L Flow sensor B1PW Space heating water pressure sensor R1T Thermistor heat excha...

Page 23: ...ess Ext thermistor External thermistor Heat pump convector Heat pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch b...

Page 24: ...us Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current English Translation Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact ...

Page 25: ...ternal room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core signal 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core 2 core Only for KRP1HB Changeover to ext heat source output Alarm output Solar input Cooli...

Page 26: ......

Page 27: ......

Page 28: ...4P556066 1 2018 10 Copyright 2018 Daikin 4P556066 1 0000000Q ...

Reviews: