background image

6 Commissioning

Installation manual

20

EABH/X16DA+9W

Daikin Altherma – Low temperature split

4P556066-1 – 2018.10

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

INFORMATION

The  software  is  equipped  with  an  "installer-on-site"  mode
([9.G]:  Disable  protections),  that  disables  automatic
operation  by  the  unit.  At  first  installation,  setting  Disable
protections  is  by  default  set  to  Yes,  meaning  automatic
operation  is  disabled.  All  protective  functions  are  then
disabled. If the user interface home pages are off, the unit
will  NOT  operate  automatically.  To  enable  automatic
operation  and  the  protective  functions,  set  Disable
protections to No.

36 hours after the first power-on, the unit will automatically
set  Disable  protections  to  No,  ending  "installer-on-site"
mode  and  enabling  the  protective  functions.  If  –  after  first
installation  –  the  installer  returns  to  the  site,  the  installer
has to set Disable protections to Yes manually.

6.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor unit

 is properly mounted.

The 

outdoor unit

 is properly mounted.

The following 

field wiring

 has been carried out according

to this document and the applicable legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between indoor unit and outdoor unit

▪ Between the local supply panel and the indoor unit

▪ Between the indoor unit and the valves (if applicable)

▪ Between  the  indoor  unit  and  the  room  thermostat  (if

applicable)

▪ Between  the  indoor  unit  and  the  domestic  hot  water

tank (if applicable)

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

Only for tanks with built-in booster heater:

Booster  heater  circuit  breaker

  F2B  (field  supply)  is

turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There is NO 

water leak

 inside the indoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

air purge

 valve is open (at least 2 turns).

The 

pressure relief valve

 purges water when opened.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"3.2 Preparing water piping" on page 4

.

The 

domestic hot water tank

 is filled completely.

6.2

Checklist during commissioning

The 

minimum  flow  rate

  during  backup  heater/defrost

operation  is  guaranteed  in  all  conditions.  See  "To  check
the  water  volume  and  flow  rate"  in 

"3.2  Preparing  water

piping" on page 4

.

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

6.2.1

To check the minimum flow rate

1

Confirm according to the hydraulic configuration
which space heating loops can be closed due to
mechanical, electronic, or other valves.

2

Close all space heating loops that can be closed
(see previous step).

3

Start the pump test run operation (see 

"6.2.4 To

perform an actuator test run" on page 21

).

4

During pump test run operation, go to Sensors.

5

Select the flow rate information. During test run
operation, the unit can operate below the minimum
required flow rate.

6

Modify the bypass valve setting to reach the
minimum required flow rate + 2 l/min.

Minimum required flow rate

20 l/min

6.2.2

To perform an air purge

Conditions: 

Make  sure  all  operation  is  disabled.  Go  to  the

Operation menu and turn off Room, Space heating/cooling and Tank
operation.

1

Set the user permission level to Installer. See 

"To

change the user permission level" on page 13

.

2

Go to [A.3]: Commissioning > Air purge.

3

Select OK to confirm.

Result: 

The air purge starts. It stops automatically

when air purge cycle is finished.

To stop the air purge manually:

1

Go to Stop air purge.

2

Select OK to confirm.

Summary of Contents for Altherma EABH16DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W ...

Page 2: ...ou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących ...

Page 3: ...e 14 5 2 3 Configuration wizard System 14 5 2 4 Configuration wizard Backup heater 15 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 16 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone 18 5 3 3 Information 18 5 4 Menu structure Overview installer settings 19 6 C...

Page 4: ... corrosion Valve towards expansion vessel The valve towards the expansion vessel if equipped MUST be open 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulation in each space heating cooling loop is controlled by remotely controll...

Page 5: ... 9 Domestic hot water tank thermistor 2 d 10 User interface used as room thermostat 2 f 11 Room thermostat 3 or 4 100 mA b 12 Outdoor ambient temperature sensor 2 b 13 Indoor ambient temperature sensor 2 b 14 Heat pump convector 2 100 mA b Field supplied components 15 Shut off valve 2 100 mA b Item Description Wires Maximum running current 16 Electricity meter 2 per meter b 17 Domestic hot water p...

Page 6: ...move the user interface panel also disconnect the cables from the back of the panel to prevent damage 3 1 2 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Fix the wall bracket accessory to the wall level with 2 Ø8 mm bolts 2 a a Optional If you want to fix the unit to the wall from inside the unit provide an additional screw plug 2 Lift the unit 42kg 3 Attach the unit to the wall ...

Page 7: ...piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the indoor unit water connections 2 Connect the outdoor unit field piping on the water IN connection a of the indoor unit 3 Connect the space heating cooling field piping on the space heating water OUT connection b of the indoor unit a b a b a Water IN connection b Space heating water...

Page 8: ...ided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liquid in the system is frozen the pump will NOT be able to start Mind that if you only prevent the system from bursting the liquid inside might still freeze When water is at standstill inside the system the system is very likely to freez...

Page 9: ...installer reference guide or the installation manual of the outdoor unit 4 4 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 4 4 1 About electrical compliance Only for the backup heater of the indoor unit See 4 4 4 To connect the backup heater power supply on page 10 4 4 2 To connect the electrical wiring on the indoor unit 1...

Page 10: ...ices according to the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply M...

Page 11: ...Do NOT cut or remove the backup heater power supply cable 4 4 5 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normal closed valve and a NO normal open valve X2M X1M X2M X1M NO NC M2S M2S 21 29 21 28 2 Fix the cable with cable ties to the cable tie mountings 4 4 6 To connect the ele...

Page 12: ...ountings 4 4 10 To connect the changeover to external heat source 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below X5M A4P X1M YC Y1 Y2 Y3 Y4 X2M X1M X3 X4 X2M X1 X2 L N a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 4 11 To connect the power consumption digital inputs 1 Conn...

Page 13: ...wizard When you turn ON the user interface for the first time via the indoor unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 5 1 1 To access the most use...

Page 14: ...he backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic hot water or not and which tank is used ...

Page 15: ...c valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter 5 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuratio...

Page 16: ... To compensate you can Increase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control For the control of the unit there are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling d...

Page 17: ...her dependent zones Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X X1 X2 Outdoor ambient temperature Y Y1 Y2 Desired tank temperature or leaving water temperature The symbol shown here corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies ...

Page 18: ...settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the uni...

Page 19: ... Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Boo...

Page 20: ...There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON Only for tanks with built in booster heater Booster heater circuit breaker F2B field supply is turned ON The correct pipe size is installed and the pipes are prop...

Page 21: ...es in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the ...

Page 22: ... 8 1 Piping diagram Indoor unit 3D120613 R2T R1T B1PW B1L A B e e B f i g c a b h j d h S1L i A Water side B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut off valve for service f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Backup heater B1L Flow sensor B1PW Space heating water pressure sensor R1T Thermistor heat excha...

Page 23: ...ess Ext thermistor External thermistor Heat pump convector Heat pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch b...

Page 24: ...us Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current English Translation Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact ...

Page 25: ...ternal room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core signal 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core 2 core Only for KRP1HB Changeover to ext heat source output Alarm output Solar input Cooli...

Page 26: ......

Page 27: ......

Page 28: ...4P556066 1 2018 10 Copyright 2018 Daikin 4P556066 1 0000000Q ...

Reviews: