background image

5 Configuration

Installation manual

14

EABH/X16DA+9W

Daikin Altherma – Low temperature split

4P556066-1 – 2018.10

All settings can be done using the menu structure. If for any reason it
is required to change a setting using the overview settings, then the
overview settings can be accessed as follows:

1

Set the user permission level to Installer. See 

"To

change the user permission level" on page 13

.

2

Go to [9.I]: Installer settings > Overview field
settings.

3

Turn the left dial to select the first part of the setting
and confirm by pressing the dial.

00
01
02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

0

1

2
3

4

Turn the left dial to select the second part of the
setting

00
01

15

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

5

Turn the right dial to modify the value from 15 to 20.

00
01

20

02
03
04

05
06
07
08
09

0A
0B
0C
0D
0E

1

6

Press the left dial to confirm the new setting.

7

Press the center button to go back to the home
screen.

INFORMATION

When  you  change  the  overview  settings  and  you  go  back
to  the  home  screen,  the  user  interface  will  show  a  popup
screen and request to restart the system.

When  confirmed,  the  system  will  restart  and  recent
changes will be applied.

5.2

Configuration wizard

After first power ON of the system, the user interface will guide you
using  the  configuration  wizard.  This  way  you  can  set  the  most
important  initial  settings.  This  way  the  unit  will  be  able  to  run
properly.  Afterwards,  more  detailed  settings  can  be  done  via  the
menu structure if required.

5.2.1

Configuration wizard: Language

#

Code

Description

[7.1]

N/A

Language

5.2.2

Configuration wizard: Time and date

#

Code

Description

[7.2]

N/A

Set the local time and date

INFORMATION

By  default,  daylight  savings  time  is  enabled  and  clock
format  is  set  to  24  hours.  If  you  want  to  change  these
settings,  you  can  do  this  in  the  menu  structure  (User
settings > Time/date) once the unit is initialised.

5.2.3

Configuration wizard: System

Indoor unit type

The indoor unit type is displayed, but cannot be adjusted.

Backup heater type

The  backup  heater  is  adapted  to  be  connected  to  most  common
European electricity grids. The type of backup heater must be set on
the user interface. For units with a built-in backup heater, the type of
heater can be viewed but not changed.

#

Code

Description

[9.3.1]

[E‑03]

▪ 3: 6V

▪ 4: 9W

Domestic hot water

The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. Set this setting according to
the actual installation.

#

Code

Description

[9.2.1]

[E‑05]

(*)

[E‑06]

(*)

[E‑07]

(*)

▪ No DHW

No tank installed.

▪ EKHWS/E

Tank  with  booster  heater  installed  at
the side of the tank.

▪ EKHWP/HYC

Tank  with  optional  booster  heater
installed at the top of the tank.

(*)

Use the menu structure instead of the overview settings.
Menu structure setting [9.2.1] replaces the following 3
overview settings:

[E-05]

Can the system prepare domestic hot water?

[E-06]

Is a domestic hot water tank installed in the system?

[E-07]

What kind of domestic hot water tank is installed?

In  case  of  a  third-party  tank,  we  recommend  to  use  the  setting  for
EKHWS.

In  case  of  EKHWP/HYC,  we  recommend  to  set  the  temperature  of
the booster heater NOT higher than 70°C.

Emergency

When  the  heat  pump  fails  to  operate,  the  backup  heater  and/or
booster  heater  can  serve  as  an  emergency  heater  and  either
automatically or non-automatically take over the heat load.

▪ When auto emergency is set to Automatic and a heat pump failure

occurs,  the  backup  heater  will  automatically  take  over  the  heat
load, and the booster heater in the optional tank will automatically
take over the domestic hot water production.

▪ When  auto  emergency  is  set  to  Manual  and  a  heat  pump  failure

occurs,  the  domestic  hot  water  and  space  heating  operation  will
stop and need to be recovered manually via the user interface. To
recover  operation  manually,  go  to  the  Malfunctioning  main  menu
screen,  where  the  user  interface  will  then  ask  you  to  confirm
whether  the  backup  heater  and/or  booster  heater  can  take  over
the heat load or not.

We  recommend  to  set  Emergency  to  Automatic  if  the  house  is
unattended for longer periods.

#

Code

Description

[9.5]

N/A

▪ 0: Manual

▪ 1: Automatic

INFORMATION

The  auto  emergency  setting  can  be  set  in  the  menu
structure of the user interface only.

Summary of Contents for Altherma EABH16DA6V

Page 1: ...Installation manual Daikin Altherma Low temperature split English Installation manual Daikin Altherma Low temperature split EABH16DA6V EABH16DA9W EABX16DA6V EABX16DA9W ...

Page 2: ...ou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi następujących ...

Page 3: ...e 14 5 2 3 Configuration wizard System 14 5 2 4 Configuration wizard Backup heater 15 5 2 5 Configuration wizard Main zone 16 5 2 6 Configuration wizard Additional zone 16 5 2 7 Detailed screen with weather dependent curve 17 5 2 8 Configuration wizard Tank 17 5 3 Settings menu 18 5 3 1 Main zone 18 5 3 2 Additional zone 18 5 3 3 Information 18 5 4 Menu structure Overview installer settings 19 6 C...

Page 4: ... corrosion Valve towards expansion vessel The valve towards the expansion vessel if equipped MUST be open 3 2 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the outdoor unit NOT included NOTICE When circulation in each space heating cooling loop is controlled by remotely controll...

Page 5: ... 9 Domestic hot water tank thermistor 2 d 10 User interface used as room thermostat 2 f 11 Room thermostat 3 or 4 100 mA b 12 Outdoor ambient temperature sensor 2 b 13 Indoor ambient temperature sensor 2 b 14 Heat pump convector 2 100 mA b Field supplied components 15 Shut off valve 2 100 mA b Item Description Wires Maximum running current 16 Electricity meter 2 per meter b 17 Domestic hot water p...

Page 6: ...move the user interface panel also disconnect the cables from the back of the panel to prevent damage 3 1 2 4 2 Mounting the indoor unit 4 2 1 To install the indoor unit 1 Fix the wall bracket accessory to the wall level with 2 Ø8 mm bolts 2 a a Optional If you want to fix the unit to the wall from inside the unit provide an additional screw plug 2 Lift the unit 42kg 3 Attach the unit to the wall ...

Page 7: ...piping Deformation of the piping can cause malfunctioning of the unit 1 Connect the O rings and shut off valves to the indoor unit water connections 2 Connect the outdoor unit field piping on the water IN connection a of the indoor unit 3 Connect the space heating cooling field piping on the space heating water OUT connection b of the indoor unit a b a b a Water IN connection b Space heating water...

Page 8: ...ided by the glycol manufacturer If necessary meet the requirements set by the glycol manufacturer The added concentration of glycol should NEVER exceed 35 If the liquid in the system is frozen the pump will NOT be able to start Mind that if you only prevent the system from bursting the liquid inside might still freeze When water is at standstill inside the system the system is very likely to freez...

Page 9: ...installer reference guide or the installation manual of the outdoor unit 4 4 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables 4 4 1 About electrical compliance Only for the backup heater of the indoor unit See 4 4 4 To connect the backup heater power supply on page 10 4 4 2 To connect the electrical wiring on the indoor unit 1...

Page 10: ...ices according to the applicable legislation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make sure that the power supply is in accordance with the backup heater capacity as listed in the table below Backup heater type Backup heater capacity Power supply M...

Page 11: ...Do NOT cut or remove the backup heater power supply cable 4 4 5 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Wiring is different for a NC normal closed valve and a NO normal open valve X2M X1M X2M X1M NO NC M2S M2S 21 29 21 28 2 Fix the cable with cable ties to the cable tie mountings 4 4 6 To connect the ele...

Page 12: ...ountings 4 4 10 To connect the changeover to external heat source 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below X5M A4P X1M YC Y1 Y2 Y3 Y4 X2M X1M X3 X4 X2M X1 X2 L N a a Installation of EKRP1HB is required 2 Fix the cable with cable ties to the cable tie mountings 4 4 11 To connect the power consumption digital inputs 1 Conn...

Page 13: ...wizard When you turn ON the user interface for the first time via the indoor unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to Installer settings Configuration wizard To access Installer settings see 5 1 1 To access the most use...

Page 14: ...he backup heater is adapted to be connected to most common European electricity grids The type of backup heater must be set on the user interface For units with a built in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic hot water or not and which tank is used ...

Page 15: ...c valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter 5 2 4 Configuration wizard Backup heater The backup heater is adapted to be connected to most common European electricity grids If the backup heater is available the voltage configuratio...

Page 16: ... To compensate you can Increase the weather dependent curve desired temperatures 2 5 Enable leaving water temperature modulation and increase the maximum modulation 2 C Control For the control of the unit there are 3 possibilities Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling d...

Page 17: ...her dependent zones Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X X1 X2 Outdoor ambient temperature Y Y1 Y2 Desired tank temperature or leaving water temperature The symbol shown here corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank 5 2 8 Configuration wizard Tank This part only applies ...

Page 18: ...settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if the leaving water temperature control on the uni...

Page 19: ... Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 2 Domestic hot water Domestic hot water DHW pump DHW pump schedule Solar 9 9 Power consumption control Power consumption control Type Limit Limit 1 Limit 2 Limit 3 Limit 4 Priority heater Electricity meter 2 Electricity meter 1 9 A Energy metering 9 Installer settings Configuration wizard Domestic hot water Backup heater Boo...

Page 20: ...There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON Only for tanks with built in booster heater Booster heater circuit breaker F2B field supply is turned ON The correct pipe size is installed and the pipes are prop...

Page 21: ...es in the water circuit during the test run Shut off valve test Diverter valve test Bivalent signal test Alarm output test C H signal test DHW pump test 6 2 5 To perform an underfloor heating screed dryout Conditions Make sure all operation is disabled Go to the Operation menu and turn off Room Space heating cooling and Tank operation 1 Set the user permission level to Installer See To change the ...

Page 22: ... 8 1 Piping diagram Indoor unit 3D120613 R2T R1T B1PW B1L A B e e B f i g c a b h j d h S1L i A Water side B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e Shut off valve for service f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Backup heater B1L Flow sensor B1PW Space heating water pressure sensor R1T Thermistor heat excha...

Page 23: ...ess Ext thermistor External thermistor Heat pump convector Heat pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch b...

Page 24: ...us Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For safety thermostat For safety thermostat Inrush Inrush current English Translation Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat contact ...

Page 25: ...ternal room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core signal 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core 2 core Only for KRP1HB Changeover to ext heat source output Alarm output Solar input Cooli...

Page 26: ......

Page 27: ......

Page 28: ...4P556066 1 2018 10 Copyright 2018 Daikin 4P556066 1 0000000Q ...

Reviews: