6
|
Application guidelines
Installer reference guide
57
ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
6.5.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/5 and X5M/6. See
125].
Power meter type
In case of…
Use a… power meter
▪
Single-phase outdoor unit
▪
Backup heater supplied from a single-
phase grid, i.e. the backup heater
model is:
-
*6V (6V3: 1N~ 230 V).
Single-phase
▪
Three-phase outdoor unit
▪
Backup heater supplied from a three-
phase grid, i.e. the backup heater
model is:
-
*6V (6T1: 3~ 230 V)
-
*9W (3N~ 400 V)
Three-phase
Example
Single-phase power meter
Three-phase power meter
b
580
1 50
0
0
c
c
f
e
d
g
A
B
C
a
c
X5M/5+6
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
1
/N)
b
Power meter (L
1
/N)
c
Fuse (L
1
/N)
d
Outdoor unit (L
1
/N)
e
Indoor unit (L
1
/N)
f
Backup heater (L
1
/N)
g
Booster heater (L
1
/N)
b
580
1 50
0
0
c
c
g
f
e
h
A
B
C
a
X5M/5+6
d
450896.005
A
Outdoor unit
B
Indoor unit
C
DHW tank
a
Electrical cabinet (L
1
/L
2
/L
3
/N)
b
Power meter (L
1
/L
2
/L
3
/N)
c
Fuse (L
1
/L
2
/L
3
/N)
d
Fuse (L
1
/N)
e
Outdoor unit (L
1
/L
2
/L
3
/N)
f
Indoor unit (L
1
/N)
g
Backup heater (L
1
/L
2
/L
3
/N)
h
Booster heater (L
1
/N)