![background image](http://html.mh-extra.com/html/daikin/altherma-3-r-w/altherma-3-r-w_installers-reference-manual_501226252.webp)
13
|
Maintenance and service
Installer reference guide
252
ERGA04~08EA + EHBH/X04+08EF
Daikin Altherma 3 R W
4P629085-1B – 2021.11
a
b
a
Bottom part to be unscrewed
b
Water filter housing
3
Remove the strainer and the rolled‑up filter from the water filter housing and
clean with water.
4
Install the cleaned rolled‑up filter and strainer in the water filter housing.
INFORMATION
Correctly install the strainer in the magnetic filter/dirt separator housing using the
protrusions.
a
b
c
c
a
Rolled‑up filter
b
Strainer
c
Protrusion
5
Install and properly tighten the bottom of the water filter housing.
13.3.3 To install the water filter
NOTICE
Check the condition of the O-rings and replace if needed. Apply water or silicon
grease to the O-rings before installation.
1
Install the water filter in the correct location.
a
c
b
a