6 Electrical installation

Installation manual

17

EBBH/X11+16DF
Daikin Altherma 3 R W
4P643600-1B – 2021.10

a

b

a

Space heating/cooling – Water OUT (screw connection,
1")

b

Space heating/cooling – Water IN (screw connection, 1")

2

Screw the indoor unit nuts on the shut-off valves.

3

Connect the field piping on the shut-off valves.

4

In case of connection with the optional domestic hot water tank,
see the installation manual of the domestic hot water tank.

NOTICE

Install air purge valves at all local high points.

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"5.3.1  To

check the water volume and flow rate"

 [

4

 16].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"5.3.1  To

check  the  water  volume  and  flow  rate"

  [

4

  16]  and

"8.2.1 To check the minimum flow rate"

 [

4

 38].

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=  1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

5.4.2

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Pump.

 To prevent blocking of the pump rotor, commission

the unit as quickly as possible after filling the water circuit.

INFORMATION

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

5.4.3

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.

5.4.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

6

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

INFORMATION

When  installing  field  supply  or  option  cables,  foresee
sufficient  cable  length.  This  will  make  it  possible  to  open
the  switch  box  and  gain  access  to  other  components
during service.

6.1

About electrical compliance

Only for the backup heater of the indoor unit

See 

"6.3.2 To connect the backup heater power supply"

 [

4

 20].

6.2

Guidelines when connecting the
electrical wiring

Tightening torques

Indoor unit:

Item

Tightening torque (N•m)

X1M

2.45 ±10%

X2M

0.88 ±10%

X5M

0.88 ±10%

X6M

2.45 ±10%

X7M, X8M

2.45 ±10%

X10M

0.88 ±10%

M4 (earth)

1.47 ±10%

6.3

Connections to the indoor unit

Item

Description

Power supply (main)

See 

"6.3.1 To connect the main power

supply"

 [

4

 19].

Power supply (backup
heater)

See 

"6.3.2 To connect the backup heater

power supply"

 [

4

 20].

Shut-off valve

See 

"6.3.3 To connect the shut-off

valve"

 [

4

 22].

Electricity meters

See 

"6.3.4 To connect the electricity

meters"

 [

4

 22].

Domestic hot water
pump

See 

"6.3.5 To connect the domestic hot

water pump"

 [

4

 22].

Alarm output

See 

"6.3.6 To connect the alarm

output"

 [

4

 23].

Space cooling/heating
operation control

See 

"6.3.7 To connect the space cooling/

heating ON/OFF output"

 [

4

 23].

All manuals and user guides at all-guides.com

Summary of Contents for Altherma 3 R W Series

Page 1: ...eu Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W All manuals and u...

Page 2: ...om o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en ustanoven p edpisu prema odredbam...

Page 3: ...tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln tepl...

Page 4: ...uration wizard Time and date 29 7 2 3 Configuration wizard System 29 7 2 4 Configuration wizard Backup heater 31 7 2 5 Configuration wizard Main zone 31 7 2 6 Configuration wizard Additional zone 32 7...

Page 5: ...ns in this manual for correct installation of the unit See 4 1 1 Installation site requirements of the indoor unit 46 Special requirements for R32 see 4 1 2 Special requirements for R32 units 47 WARNI...

Page 6: ...from the heat emitters or collectors 3 About the box 3 1 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring t...

Page 7: ...stallation patterns 48 WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those recommended by the manufacturer Be aware that R32...

Page 8: ...t b Chimney c1 Bottom opening for natural ventilation c2 Top opening for natural ventilation Hrelease Actual release height 1a 2a Without chimney From floor to top of the unit minimum 1 95 m 1b 2b Wit...

Page 9: ...release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must provide 2 openings one...

Page 10: ...nditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a chimney or not i e does...

Page 11: ...6 98 6 48 6 10 5 89 4 5 16 32 14 76 13 42 12 26 11 23 10 34 9 54 8 84 8 20 7 64 7 13 5 20 14 18 23 16 57 15 13 13 87 12 76 11 78 10 91 10 13 9 43 8 80 5 5 24 37 22 05 20 05 18 31 16 78 15 44 14 25 13...

Page 12: ...rrect table For intermediate refrigerant charges use the table with the higher value Example If the refrigerant charge is 4 3 kg use the table of 4 8 kg For intermediate floor areas use the column wit...

Page 13: ...the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a permanent opening that...

Page 14: ...all the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Fix the wall...

Page 15: ...Piping diameter Liquid piping 9 5 mm 3 8 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 9 5 mm 3 8 Annealed O 0 8 mm t 15 9 mm 5 8 Annealed O 1 0 m...

Page 16: ...rate in the installation is guaranteed in all conditions For this purpose use the overpressure bypass valve delivered with the unit and respect the minimum water volume If operation is Then the minimu...

Page 17: ...agnetic filter and one on the backup heater are open 5 4 3 To fill the domestic hot water tank See the installation manual of the domestic hot water tank 5 4 4 To insulate the water piping The piping...

Page 18: ...e outdoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Install...

Page 19: ...anual of the wireless room thermostat Addendum book for optional equipment Wired room thermostat without multi zoning base unit Installation manual of the wired room thermostat Addendum book for optio...

Page 20: ...Wh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rate power supply is inte...

Page 21: ...he user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipme...

Page 22: ...rent for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings...

Page 23: ...413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to...

Page 24: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate termina...

Page 25: ...with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safe...

Page 26: ...follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid con...

Page 27: ...e mountings If necessary bundle excessive cable length with a cable tie 7 Configuration INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV...

Page 28: ...he most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Enter the applicable pin code for the user permiss...

Page 29: ...g according to the actual installation Code Description 9 2 1 E 05 a E 06 a E 07 a No DHW No tank installed EKHWS E small volume Tank with booster heater installed at the side of the tank with a volum...

Page 30: ...t function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configuration the numb...

Page 31: ...0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one che...

Page 32: ...er can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT setpoint mode 2 4 is as f...

Page 33: ...during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Page 34: ...l ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c d e Item Description...

Page 35: ...mperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tune the weather dependent curve 2 points curve The following table descr...

Page 36: ...tpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Ave...

Page 37: ...r unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel...

Page 38: ...orm an operation test run Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To cha...

Page 39: ...r on site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of...

Page 40: ...r C Field installed a1 Space heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mo...

Page 41: ...OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON O...

Page 42: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Page 43: ...ace Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for...

Page 44: ...4P643600 1B 2021 10 Copyright 2021 Daikin 4P643600 1 B 0000000X Verantwortung f r Energie und Umwelt All manuals and user guides at all guides com...

Reviews: