4 Unit installation
Installation manual
11
EBBH/X11+16DF
Daikin Altherma 3 R W
4P643600-1B – 2021.10
PATTERN 3
No
Yes
START PATTERN 3
A
You can install the unit in room A if you lead the chimney outside
the building.
3a
You CANNOT install the unit in the room. Place the unit in a larger
room.
3b
See table 3:
Is it possible to lead a chimney
outside the building respecting the maximum
chimney length?
Tables for PATTERN 1, 2 and 3
Table 1: Minimum floor area
For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
Minimum floor area (m²)
Charge (kg)
Release height without chimney (m)
1.95
2.05
2.15
2.25
2.35
2.45
2.55
2.65
2.75
2.85
2.95
3.8
11.64
10.53
9.57
8.74
8.01
7.37
6.80
6.30
6.00
5.79
5.59
4
12.89
11.67
10.61
9.68
8.88
8.17
7.54
6.98
6.48
6.10
5.89
4.5
16.32
14.76
13.42
12.26
11.23
10.34
9.54
8.84
8.20
7.64
7.13
5
20.14
18.23
16.57
15.13
13.87
12.76
11.78
10.91
10.13
9.43
8.80
5.5
24.37
22.05
20.05
18.31
16.78
15.44
14.25
13.20
12.26
11.41
10.65
5.8
27.11
24.53
22.30
20.36
18.66
17.17
15.85
14.68
13.63
12.69
11.84
Table 2: Minimum release height
Take the following into account:
• For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 22.50 m², use the column of 20.00 m².
• For intermediate refrigerant charges, use the row with the higher value.
Example:
If the refrigerant charge is 4.3 kg, use the row of 4.5 kg.
• (*): The release height of the unit without chimney (minimum 1.95 m) is already higher than the minimum required release height. => OK (no
chimney needed).
Minimum release height (m)
Charge (kg)
Floor area (m²)
5.00
10.00
15.00
20.00
25.00
30.00
3.8
3.30
2.10
(*)
(*)
(*)
(*)
4
3.47
2.21
(*)
(*)
(*)
(*)
4.5
3.91
2.49
2.03
(*)
(*)
(*)
5
4.34
2.77
2.26
1.96
(*)
(*)
5.5
4.78
3.04
2.49
2.15
(*)
(*)
5.8
5.04
3.21
2.62
2.27
2.03
(*)