background image

7 Configuration

Installation manual

32

EBBH/X11+16DF

Daikin Altherma 3 R W

4P643600-1B – 2021.10

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–8/2=

36°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 31].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 31].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 31].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent curves. Also see 

"7.3 Weather-dependent curve"

 [

4

 33].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 31].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.7

Configuration wizard: Tank

This part only applies to systems with an optional domestic hot water
tank installed.

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

All manuals and user guides at all-guides.com

Summary of Contents for Altherma 3 R W Series

Page 1: ...eu Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EBBH11DF6V EBBH11DF9W EBBH16DF6V EBBH16DF9W EBBX11DF6V EBBX11DF9W EBBX16DF6V EBBX16DF9W All manuals and u...

Page 2: ...om o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en ustanoven p edpisu prema odredbam...

Page 3: ...tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln tepl...

Page 4: ...uration wizard Time and date 29 7 2 3 Configuration wizard System 29 7 2 4 Configuration wizard Backup heater 31 7 2 5 Configuration wizard Main zone 31 7 2 6 Configuration wizard Additional zone 32 7...

Page 5: ...ns in this manual for correct installation of the unit See 4 1 1 Installation site requirements of the indoor unit 46 Special requirements for R32 see 4 1 2 Special requirements for R32 units 47 WARNI...

Page 6: ...from the heat emitters or collectors 3 About the box 3 1 Indoor unit At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring t...

Page 7: ...stallation patterns 48 WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those recommended by the manufacturer Be aware that R32...

Page 8: ...t b Chimney c1 Bottom opening for natural ventilation c2 Top opening for natural ventilation Hrelease Actual release height 1a 2a Without chimney From floor to top of the unit minimum 1 95 m 1b 2b Wit...

Page 9: ...release height without chimney START PATTERN 1 PATTERN 2 PATTERN 2 Conditions ventilation openings If you want to take advantage of the floor area of the adjacent room you must provide 2 openings one...

Page 10: ...nditions ventilation openings on previous page See table 3 For H1 Can the maximum chimney length be respected and is the chimney practically feasible See table 2 Do you need a chimney or not i e does...

Page 11: ...6 98 6 48 6 10 5 89 4 5 16 32 14 76 13 42 12 26 11 23 10 34 9 54 8 84 8 20 7 64 7 13 5 20 14 18 23 16 57 15 13 13 87 12 76 11 78 10 91 10 13 9 43 8 80 5 5 24 37 22 05 20 05 18 31 16 78 15 44 14 25 13...

Page 12: ...rrect table For intermediate refrigerant charges use the table with the higher value Example If the refrigerant charge is 4 3 kg use the table of 4 8 kg For intermediate floor areas use the column wit...

Page 13: ...the unoccupied room If the opening starts from the floor the height of the opening must be 20 mm a2 Top opening for natural ventilation between room A and the outside Must be a permanent opening that...

Page 14: ...all the front panel NOTICE When closing the indoor unit cover make sure that the tightening torque does NOT exceed 4 1 N m 4 3 Mounting the indoor unit 4 3 1 To install the indoor unit 1 Fix the wall...

Page 15: ...Piping diameter Liquid piping 9 5 mm 3 8 Gas piping 15 9 mm 5 8 Piping temper grade and thickness Outer diameter Temper grade Thickness t a 9 5 mm 3 8 Annealed O 0 8 mm t 15 9 mm 5 8 Annealed O 1 0 m...

Page 16: ...rate in the installation is guaranteed in all conditions For this purpose use the overpressure bypass valve delivered with the unit and respect the minimum water volume If operation is Then the minimu...

Page 17: ...agnetic filter and one on the backup heater are open 5 4 3 To fill the domestic hot water tank See the installation manual of the domestic hot water tank 5 4 4 To insulate the water piping The piping...

Page 18: ...e outdoor sensor Addendum book for optional equipment Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Install...

Page 19: ...anual of the wireless room thermostat Addendum book for optional equipment Wired room thermostat without multi zoning base unit Installation manual of the wired room thermostat Addendum book for optio...

Page 20: ...Wh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indoor unit is required if preferential kWh rate power supply is inte...

Page 21: ...he user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipme...

Page 22: ...rent for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to the cable tie mountings...

Page 23: ...413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4P 1 2 Wires connected to...

Page 24: ...ivalent 1 Open the following see 4 2 1 To open the indoor unit 413 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate termina...

Page 25: ...with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safe...

Page 26: ...follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cable ties to the cable tie mountings In case of high voltage Smart Grid con...

Page 27: ...e mountings If necessary bundle excessive cable length with a cable tie 7 Configuration INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHBCONV...

Page 28: ...he most used commands To change the user permission level You can change the user permission level as follows 1 Go to B User profile User profile B 2 Enter the applicable pin code for the user permiss...

Page 29: ...g according to the actual installation Code Description 9 2 1 E 05 a E 06 a E 07 a No DHW No tank installed EKHWS E small volume Tank with booster heater installed at the side of the tank with a volum...

Page 30: ...t function will remain active even if the user does NOT confirm emergency operation Number of zones The system can supply leaving water to up to 2 water temperature zones During configuration the numb...

Page 31: ...0A 0 Relay 1 1 Relay 1 Relay 1 2 2 Relay 1 Relay 2 3 Relay 1 Relay 2 Emergency Relay 1 2 INFORMATION Settings 9 3 3 and 9 3 5 are linked Changing one setting influences the other If you change one che...

Page 32: ...er can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT setpoint mode 2 4 is as f...

Page 33: ...during storage comfort to prioritize the domestic hot water preparation When the tank temperature rises above this value domestic hot water preparation and space heating cooling are executed sequentia...

Page 34: ...l ambient temperatures Examples Weather dependent curve when slope is selected X1 X2 c d e Y1 Y2 Y3 Y4 a b Weather dependent curve when offset is selected Y1 Y2 Y3 Y4 X1 X2 a b c d e Item Description...

Page 35: ...mperatures At cold outdoor temperatures Slope Offset OK Cold OK Hot Cold OK Cold Cold Cold Hot Hot OK Hot Cold Hot Hot To fine tune the weather dependent curve 2 points curve The following table descr...

Page 36: ...tpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor Ext amb sensor offset Ave...

Page 37: ...r unit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel...

Page 38: ...orm an operation test run Conditions Make sure all operation is disabled Go to C Operation and turn off Space heating cooling and Tank operation 1 Set the user permission level to Installer See To cha...

Page 39: ...r on site mode see Commissioning room frost protection will be automatically disabled for 12 hours after the first power on If the screed dryout still needs to be performed after the first 12 hours of...

Page 40: ...r C Field installed a1 Space heating cooling Water IN screw connection 1 Thermistors a2 Space heating cooling Water OUT screw connection 1 R1T Heat exchanger Water OUT b1 Gas refrigerant IN heating mo...

Page 41: ...OFF thermostat wireless ON OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired ON O...

Page 42: ...xing kit Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid...

Page 43: ...ace Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for...

Page 44: ...4P643600 1B 2021 10 Copyright 2021 Daikin 4P643600 1 B 0000000X Verantwortung f r Energie und Umwelt All manuals and user guides at all guides com...

Reviews: