7
|
Unit installation
Installer reference guide
62
ERRA08~12E + EL23E
Daikin Altherma 3 R MT F
4P708478-1 – 2023.05
Table 3: Maximum chimney length
When installing a chimney, the chimney length must be less than the maximum chimney length.
•
Use the columns with the correct refrigerant charge. For intermediate refrigerant charges, use the columns with
the higher value.
Example:
If the refrigerant charge is 3.5 kg, use the columns of 4.05 kg.
•
For intermediate diameters, use the column with the lower value.
Example:
If the diameter is 23 mm, use the
column of 22 mm.
•
X: Not allowed
Maximum chimney length (m) – In case of Refrigerant charge=3.25 kg (and T=60°C)
In case of Refrigerant charge=4.05 kg (and T=60°C)
Chimney
Inside diameter of chimney (mm)
Inside diameter of chimney (mm)
20 mm
22 mm
24 mm
26 mm
28 mm
20 mm
22 mm
24 mm
26 mm
28 mm
Straight pipe
24.41 m
42.18 m
67.50 m
102.40 m
149.26 m
13.28 m
24.78 m
41.27 m
64.11 m
94.87 m
1× 90° elbow
22.61 m
40.20 m
65.34 m
100.06 m
146.74 m
11.48 m
22.80 m
39.11 m
61.77 m
92.35 m
2× 90° elbow
20.81 m
38.22 m
63.18 m
97.72 m
144.22 m
9.68 m
20.82 m
36.95 m
59.43 m
89.83 m
3× 90° elbow
19.01 m
36.24 m
61.02 m
95.38 m
141.70 m
7.88 m
18.84 m
34.79 m
57.09 m
87.31 m
Table 4: Minimum bottom opening area for natural ventilation
Take the following into account:
•
Use the correct table. For intermediate refrigerant charges, use the table with the higher value.
Example:
If the
refrigerant charge is 3.5 kg, use the table of 3.65 kg.
•
For intermediate floor areas, use the column with the lower value.
Example:
If the floor area is 7.25 m², use the
column of 6.00 m².
•
For intermediate release height values, use the row with the lower value.
Example:
If the release height is
1.90 m, use the row of 1.86 m.
•
A
nv
: Bottom opening area for natural ventilation.
•
A
nv-min
: Minimum bottom opening area for natural ventilation.
•
(*): Already OK (no ventilation openings needed).
A
nv-min
(dm²) – In case of Refrigerant charge=3.25 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
4.00 m²
6.00 m²
8.00 m²
10.00 m²
12.00 m²
14.00 m²
16.00 m²
1.66 m
4.186 dm²
2.327 dm²
1.474 dm²
0.689 dm²
(*)
(*)
(*)
1.86 m
3.531 dm²
1.563 dm²
0.600 dm²
(*)
(*)
(*)
(*)
2.06 m
2.953 dm²
0.882 dm²
(*)
(*)
(*)
(*)
(*)
2.26 m
2.436 dm²
0.266 dm²
(*)
(*)
(*)
(*)
(*)
2.46 m
1.967 dm²
(*)
(*)
(*)
(*)
(*)
(*)
2.66 m
1.537 dm²
(*)
(*)
(*)
(*)
(*)
(*)
2.86 m
1.141 dm²
(*)
(*)
(*)
(*)
(*)
(*)
3.06 m
0.773 dm²
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=3.65 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
4.00 m²
6.00 m²
8.00 m²
10.00 m²
12.00 m²
14.00 m²
16.00 m²
1.66 m
5.159 dm²
3.300 dm²
2.513 dm²
1.788 dm²
1.048 dm²
0.303 dm²
(*)
1.86 m
4.450 dm²
2.482 dm²
1.581 dm²
0.751 dm²
(*)
(*)
(*)
2.06 m
3.827 dm²
1.756 dm²
0.749 dm²
(*)
(*)
(*)
(*)
2.26 m
3.269 dm²
1.100 dm²
(*)
(*)
(*)
(*)
(*)
2.46 m
2.766 dm²
0.502 dm²
(*)
(*)
(*)
(*)
(*)
2.66 m
2.306 dm²
(*)
(*)
(*)
(*)
(*)
(*)
2.86 m
1.882 dm²
(*)
(*)
(*)
(*)
(*)
(*)
3.06 m
1.490 dm²
(*)
(*)
(*)
(*)
(*)
(*)
A
nv-min
(dm²) – In case of Refrigerant charge=4.05 kg
Release height (m)
Floor area of room A (m²) [! NOT room A + room B !]
4.00 m²
6.00 m²
8.00 m²
10.00 m²
12.00 m²
14.00 m²
16.00 m²
1.66 m
6.132 dm²
4.272 dm²
3.551 dm²
2.886 dm²
2.198 dm²
1.498 dm²
0.792 dm²
1.86 m
5.369 dm²
3.401 dm²
2.562 dm²
1.789 dm²
1.002 dm²
0.209 dm²
(*)
2.06 m
4.700 dm²
2.629 dm²
1.681 dm²
0.809 dm²
(*)
(*)
(*)
2.26 m
4.103 dm²
1.934 dm²
0.886 dm²
(*)
(*)
(*)
(*)
2.46 m
3.565 dm²
1.302 dm²
0.160 dm²
(*)
(*)
(*)
(*)
2.66 m
3.074 dm²
0.721 dm²
(*)
(*)
(*)
(*)
(*)