2/12
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Room
└─
Antifrost
1.4.1
[2-06]
R/W
0: No
1: Yes
1.4.2
[2-05]
R/W
4~16°C, step: 1°C
8°C
└─
Setpoint range
1.5.1
[3-07]
R/W
12~18°C, step: 1°C
12°C
1.5.2
[3-06]
R/W
18~30°C, step: 1°C
30°C
1.5.3
[3-09]
R/W
15~25°C, step: 1°C
15°C
1.5.4
[3-08]
R/W
25~35°C, step: 1°C
35°C
Room
1.6
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
1.7
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Room comfort setpoint
1.9.1
[9-0A]
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
1.9.2
[9-0B]
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
Main zone
2.4
0: Fixed
1: WD heating, fixed cooling (*3)
2: Weather dependent
└─
Heating WD curve
2.5
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
2.5
[1-01]
R/W
10~25°C, step: 1°C
15°C
2.5
[1-02]
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
40°C
[2-0C]=1
45°C
[2-0C]=2
55°C
2.5
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
25°C
└─
Cooling WD curve
2.6
[1-06]
R/W
10~25°C, step: 1°C
20°C (*3)
2.6
[1-07]
R/W
25~43°C, step: 1°C
35°C (*3)
2.6
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C (*3)
2.6
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0:
18°C (*3)
[2-0C]=1:
7°C (*3)
[2-0C]=2:
18°C (*3)
Main zone
2.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─
Setpoint range
2.8.1
[9-01]
R/W
15~37°C, step: 1°C
25°C
2.8.2
[9-00]
R/W
37~65, step: 1°C
[2-0C]=2:
65°C
[2-0C]
≠
2:
55°C
2.8.3
[9-03]
R/W
5~18°C, step: 1°C
7°C (*3)
2.8.4
[9-02]
R/W
18~22°C, step: 1°C
22°C (*3)
Main zone
2.9
[C-07]
R/W
0: Leaving water
1: External room thermostat
2: Room thermostat
2.A
[C-05]
R/W
1: 1 contact
2: 2 contacts
└─
Delta T
2.B.1
[1-0B]
R/W
3~12°C, step: 1°C
[2-0C]
≠
2 (Radiator)
5°C
[2-0C] = 2 (Radiator)
10°C
2.B.2
[1-0D]
R/W
3~10°C, step: 1°C
5°C (*3)
└─
Modulation
2.C.1
[8-05]
R/W
0: No
1: Yes
2.C.2
[8-06]
R/W
0~10°C, step: 1°C
5°C
└─
Shut off valve
Modulation
Max modulation
Cooling minimum
Cooling maximum
Control
Ext Thermostat type
Delta T heating
Delta T cooling
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Emitter type
Heating minimum
Heating maximum
Setpoint mode
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Cooling minimum
Cooling maximum
Room sensor offset
Room sensor offset
Heating comfort setpoint
Cooling comfort setpoint
Field settings table
Installer setting at variance with
default value
Activation
Room setpoint
Heating minimum
Heating maximum
4P717810
‐
1
‐
2022.11
(*1)
*6V*_(*2)
*9W*_
(*3)
Only
applicable
for
models
where
cooling
is
possible