5 Operation

Operation manual

16

EBSH/X(B)11+16P30+50DF

Daikin Altherma 3 R ECH

O

4P663485-1 – 2021.07

▪ Main zone - Cooling

▪ Additional zone - Heating

▪ Additional zone - Cooling

▪ Tank (only available to installers)

INFORMATION

To  operate  weather  dependent,  correctly  configure  the
setpoint  of  the  main  zone,  additional  zone  or  tank.  See

"5.9.4 Using weather-dependent curves"

 [

4

 17].

5.9.2

2-points curve

Define the weather-dependent curve with these two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Example

Y1

Y2

X1

X2

a

Item

Description

a

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Storage tank

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

5.9.3

Slope-offset curve

Slope and offset

Define the weather-dependent curve by its slope and offset:

▪ Change  the 

slope

  to  differently  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures.  For  example,  if  leaving  water  temperature  is  in
general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

e

Item

Description

a

WD curve before changes.

b

WD curve after changes (as example):

▪ When  slope  is  changed,  the  new  preferred

temperature  at  X1  is  unequally  higher  than  the
preferred temperature at X2.

▪ When  offset  is  changed,  the  new  preferred

temperature  at  X1  is  equally  higher  as  the  preferred
temperature at X2.

c

Slope

d

Offset

e

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2,

Y3, Y4

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Storage tank

Summary of Contents for Altherma 3 R ECH2O

Page 1: ...ish Operation manual Daikin Altherma 3 R ECH O EBSH11P30DF EBSHB11P30DF EBSH11P50DF EBSHB11P50DF EBSH16P30DF EBSHB16P30DF EBSH16P50DF EBSHB16P50DF EBSX11P30DF EBSXB11P30DF EBSX11P50DF EBSXB11P50DF EBS...

Page 2: ...20 11 1 Configuration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure...

Page 3: ...Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do NOT place...

Page 4: ...Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the room where you w...

Page 5: ...external room thermostat control the protection is NOT guaranteed 1 Go to C 2 Operation Space heating cooling Operation Space heating cooling Tank Off On C 2 2 Set operation to On or Off To change the...

Page 6: ...e temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information see also 5 4 Turning operation ON or OFF 411 5 6 Space heating coolin...

Page 7: ...rect config file on the USB memory stick Export the current settings i e field settings MMI EEPROM settings schedule timers from the user interface MMI to the USB memory stick LCD screen The LCD scree...

Page 8: ...ylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Activation Schedule Level 7 5 Electricity price High Medium Low Schedule 5 Tank Powerful operation Schedule 1 9 Room comfort setpo...

Page 9: ...mp failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy is curren...

Page 10: ...ure 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving wa...

Page 11: ...ting cooling operation OFF Tank heating operation 55 21 35 45 c 55 21 35 45 d c Tank heating operation ON d Tank heating operation OFF 5 4 2 To turn ON or OFF Space heating cooling operation NOTICE Ro...

Page 12: ...lowing options Heating Only heating mode Cooling Only cooling mode Automatic The operation mode changes automatically between heating and cooling based on the outdoor temperature Restricted per month...

Page 13: ...day With the higher set temperature in the afternoon and evening more hot water is available During the morning you consume hot water and the storage tank temperature decreases When the tank temperat...

Page 14: ...the name of the current schedule Mon Sat Wed Fri Thu Tue Sun User defined 1 2 Select Delete Delete Rename Select 3 Select OK to confirm To clear the content of a day schedule 1 Select the day of whic...

Page 15: ...Weather dependent curve 5 9 1 What is a weather dependent curve Weather dependent operation The unit operates weather dependent if the desired leaving water or tank temperature is determined automati...

Page 16: ...ambient temperatures For example if leaving water temperature is in general fine but at low ambient temperatures too cold raise the slope so that leaving water temperature is heated increasingly more...

Page 17: ...e tank When the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dep...

Page 18: ...es example open flames an operating gas appliance or an operating electric heater WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrost...

Page 19: ...o the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not Alternatively when Emergency is set to auto SH reduced DHW on space heating is reduced bu...

Page 20: ...tings Tables to be filled in by installer 11 1 Configuration wizard Setting Fill in System Indoor unit type read only Backup heater type 9 3 1 Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P663485 1 2021 07 Copyright 2021 Daikin 4P663485 1 0000000U Verantwortung f r Energie und Umwelt...

Reviews: