Daikin ACZ Installation And Maintenance Manual Download Page 5

Introduction

www.DaikinApplied.com 

IM 743-7 • MICROTECH II CHILLER UNIT CONTROLLER

Component Data

The Modbus communication module is a printed circuit board 

that inserts directly into the serial card slot of the MicroTech II 

chiller unit controller as shown in 

Figure 1

Figure 1: Modbus Communication Module Attached to Unit Controller 

Figure 2

 shows the two important features of the 

communication module circuit board (the Modbus network 

connector and 8-pin header), which are described in the 

following section. 

Figure 2: Communication Module Main Features  

Modbus Network Connector

An RS-485 connector port connects the communication 

module to the Modbus network. See 

Figure 2 

for connector 

location and the table below for additional details.

Pin

Function

1

Reference (GND)

2

Data B (+)

3

Data A (-)

8-Pin Header

The 8-pin header connects the MicroTech II chiller unit 

controller to the communication module. See 

Figure 2

 for 

header location.

Network  

Connector

8-Pin Header

GND   +     - 

Summary of Contents for ACZ

Page 1: ...fugal Heat Recovery HSC Water Cooled Single Compressor Centrifugal Heat Recovery TGZ Templifier Water Heater TSC Water Cooled Single Compressor Centrifugal Templifier WCC Water Cooled Centrifugal Dual...

Page 2: ...ion Module 8 Network Configuration 9 Set up the Unit for Network Control 9 Network Setup for Centrifugal Chillers 9 Network Setup for all other Chillers 9 Modbus Network Addressing 9 Modbus Network Co...

Page 3: ...uent versions until otherwise indicated However if your software is of a later version some of the information in this document may not completely describe your application Limited Warranty Consult yo...

Page 4: ...s been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interfere...

Page 5: ...he communication module circuit board the Modbus network connector and 8 pin header which are described in the following section Figure 2 Communication Module Main Features Modbus Network Connector An...

Page 6: ...le with RS 485 network connector attached to module This manual IM 743 Tools Required A small flathead screwdriver or similar tool as shown in Figure 4 Needle nose pliers or similar tool as shown in F...

Page 7: ...you feel the connectors align press the communication module into the plug Verify that the module is firmly connected Figure 8 Step 3 8 Mount the plastic cover on the serial card slot Slip the cover o...

Page 8: ...card slot with the 8 pin plug that mates to the header on the communication module NOTE This operation relies more on fitting the communication module into the connector than seeing the connectors ma...

Page 9: ...ler is operational from the BAS interface Once the BAS protocol has been set proceed to the next section to set network addressing parameters Table 1 Password Menu Screen Model Menu Screen Password AG...

Page 10: ...he baud rate must match the other slave devices on the network Table 2 Network Parameters Parameter Default Range Description Network Address 0 247 Default 1 The Modbus Address i e ID or Ident Number...