IM 743-7 • MICROTECH II CHILLER UNIT CONTROLLER 10 www.DaikinApplied.com

Network Configuration

Follow these steps to configure the required parameters for the 

communication module. Refer to 

Table 2

 for default values and 

acceptable ranges.

NOTE: 

The Network Address (ID or Ident Number), 

along with the baud rate, must be set before you 

can communicate on the Modbus network. Both 

parameters are only available in the unit controller 

keypad/display after the BAS protocol is set to 

Modbus. 

From the unit controller Set/Unit Setpoint menu screen:

1.  Set the Network Address (ID Number) to match the 

Network Address of the unit controller.  The Network 

Address of the communication module (slave) must be 

unique in the network. Contact the system integrator for 

the desired Network Address.

2.  Set the baud rate to the desired network data 

transmission speed. The baud rate must match the other 

slave devices on the network.

Table 2: Network Parameters

Parameter

Default/Range

Description

Network Address

0-247

Default: 1

The Modbus Address (i.e. 

ID or Ident Number) of the 

communication module. This 

must be unique throughout the 

entire network

Baud Rate

1200, 2400, 4800, 9600, 

19200

Default: 19200

Data transfer speed (bps) of the 

Modbus network.

Additional Modbus Configuration 

Parameters

The communication module and unit controller support a 

number of Modbus setpoints.  After the unit controller has 

been set up for Modbus communication, the default values of 

these setpoints can be modified to enable control or monitoring 

of chiller operation via the network.  The setpoints may be 

changed from the BAS or the unit controller.  
Refer to the MicroTech II Chiller Unit Controller Operation 

Manual (

Reference Documents

) for menu options 

and instructions.  The MicroTech II Chiller Modbus 

Protocol Information Document, ED 15063, provides 

descriptions of all network parameters for BAS integration 

(www.DaikinApplied.com)

.

Summary of Contents for ACZ

Page 1: ...fugal Heat Recovery HSC Water Cooled Single Compressor Centrifugal Heat Recovery TGZ Templifier Water Heater TSC Water Cooled Single Compressor Centrifugal Templifier WCC Water Cooled Centrifugal Dual...

Page 2: ...ion Module 8 Network Configuration 9 Set up the Unit for Network Control 9 Network Setup for Centrifugal Chillers 9 Network Setup for all other Chillers 9 Modbus Network Addressing 9 Modbus Network Co...

Page 3: ...uent versions until otherwise indicated However if your software is of a later version some of the information in this document may not completely describe your application Limited Warranty Consult yo...

Page 4: ...s been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interfere...

Page 5: ...he communication module circuit board the Modbus network connector and 8 pin header which are described in the following section Figure 2 Communication Module Main Features Modbus Network Connector An...

Page 6: ...le with RS 485 network connector attached to module This manual IM 743 Tools Required A small flathead screwdriver or similar tool as shown in Figure 4 Needle nose pliers or similar tool as shown in F...

Page 7: ...you feel the connectors align press the communication module into the plug Verify that the module is firmly connected Figure 8 Step 3 8 Mount the plastic cover on the serial card slot Slip the cover o...

Page 8: ...card slot with the 8 pin plug that mates to the header on the communication module NOTE This operation relies more on fitting the communication module into the connector than seeing the connectors ma...

Page 9: ...ler is operational from the BAS interface Once the BAS protocol has been set proceed to the next section to set network addressing parameters Table 1 Password Menu Screen Model Menu Screen Password AG...

Page 10: ...he baud rate must match the other slave devices on the network Table 2 Network Parameters Parameter Default Range Description Network Address 0 247 Default 1 The Modbus Address i e ID or Ident Number...

Page 11: ...n no T Taps or ring layout Verify that network wiring does not exceed 4000 ft total distance limit without repeaters at 19200 bps baud Verify that polarity is maintained Check that there are end of li...

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representati...

Reviews: