Daikin ACZ Installation And Maintenance Manual Download Page 11

Parts and Service

www.DaikinApplied.com 11 

IM 743-7 • MICROTECH II CHILLER UNIT CONTROLLER

Parts and Service

Troubleshooting

Follow these general procedures if you can control the 

MicroTech II chiller unit controller from the keypad/display, but 

are not able to communicate with the unit from the network:

General

→  

Confirm that the communication module is inserted 

properly (see 

Installation

 section).

→  Verify the unit controller is set up to communicate 

Modbus using the keypad/display.  Refer to the 

Network 

Configuration

 section or the MicroTech II Chiller Unit 

Controller OM (

Reference Documents

) for details.

Network Parameters

→  

Verify that the Network Address of the communication 

module (slave) is unique in the network. In contrast, the 

Baud Rate must match the other slave devices on the 

network.

→  

Make sure there are no duplicate devices on the 

network and that Network Address and Baud Rate are 

set correctly as shown in 

Table 2.

Network wiring

If performance is unsatisfactory or network is experiencing 

issues such as noise or slow transmission:

→  

Confirm that the shield is landed at only one point in 

the trunk.

→  

Be aware that the recommended network topology is 

daisy-chain (no T-Taps or ring layout).

→  

Verify that network wiring does not exceed 4000 

ft total distance limit (without repeaters) at 19200 bps 

baud.

→  

Verify that polarity is maintained.

→  

Check that there are end-of-line termination resistors 

(120 Ω) at the first and last device on the trunk. This is 

required by the EIA-485 specification.

→  

Verify that the network trunk avoids strong sources of 

electromagnetic interference (EMI).

→  

Note that the two-wire bus is

 not

 interchangeable and 

must be connected correctly.

→  

Verify that the network trunk is not located near a DC 

load switch (relay).

Network Performance

→  

If network traffic is slow, communication is 

intermittent, or the trunk is experiencing “noise,” it 

may be necessary to use a network protocol analyzer 

or oscilloscope to determine the source of poor 

performance. 

→  

Confirm power is applied to the unit controller.

Contact the Daikin Applied Controls Customer Support group 

at 866-462-7829 for additional assistance, if necessary.

Parts

Table 3: Replacement Parts List

Description

Part Number

 

MicroTech II Modbus Communication Module kit
Kit includes: Modbus communication module (RS-485 

serial network board), network connector, and IM 743

350147402

Network connector

Wago

330803003

Phoenix (shown in 

Figure 12

)

910108485

Figure 12: Phoenix Network Connector

To find your local parts office, visit 

www.DaikinApplied.com

 or 

call 800-37PARTS (800-377-2787

Summary of Contents for ACZ

Page 1: ...fugal Heat Recovery HSC Water Cooled Single Compressor Centrifugal Heat Recovery TGZ Templifier Water Heater TSC Water Cooled Single Compressor Centrifugal Templifier WCC Water Cooled Centrifugal Dual...

Page 2: ...ion Module 8 Network Configuration 9 Set up the Unit for Network Control 9 Network Setup for Centrifugal Chillers 9 Network Setup for all other Chillers 9 Modbus Network Addressing 9 Modbus Network Co...

Page 3: ...uent versions until otherwise indicated However if your software is of a later version some of the information in this document may not completely describe your application Limited Warranty Consult yo...

Page 4: ...s been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interfere...

Page 5: ...he communication module circuit board the Modbus network connector and 8 pin header which are described in the following section Figure 2 Communication Module Main Features Modbus Network Connector An...

Page 6: ...le with RS 485 network connector attached to module This manual IM 743 Tools Required A small flathead screwdriver or similar tool as shown in Figure 4 Needle nose pliers or similar tool as shown in F...

Page 7: ...you feel the connectors align press the communication module into the plug Verify that the module is firmly connected Figure 8 Step 3 8 Mount the plastic cover on the serial card slot Slip the cover o...

Page 8: ...card slot with the 8 pin plug that mates to the header on the communication module NOTE This operation relies more on fitting the communication module into the connector than seeing the connectors ma...

Page 9: ...ler is operational from the BAS interface Once the BAS protocol has been set proceed to the next section to set network addressing parameters Table 1 Password Menu Screen Model Menu Screen Password AG...

Page 10: ...he baud rate must match the other slave devices on the network Table 2 Network Parameters Parameter Default Range Description Network Address 0 247 Default 1 The Modbus Address i e ID or Ident Number...

Page 11: ...n no T Taps or ring layout Verify that network wiring does not exceed 4000 ft total distance limit without repeaters at 19200 bps baud Verify that polarity is maintained Check that there are end of li...

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representati...

Reviews: