Introduction

This manual contains information regarding the network 

integration system used with MicroTech

®

 II unit controllers on 

Daikin Applied chillers. It describes how to install or replace 

a Modbus

®

 communication module on a MicroTech

 

II chiller 

unit controller. It also explains how to set network parameters 

and establish communication between the chiller and Modbus 

network.

Revision History

IM 743-0

Apr 2003

Initial release.

IM 743-1

May 2005

Removed references to RS 232 serial 

connection. Added WGS, WMC, HSC, TSC, and 

HDC models to Reference Documents section 

and cover page. Corrected pin connections on 

Figure 6.  Added notes under Unit Setup for 

Network Control and Network Address and Baud 

Rate sections.

IM 743-2

Nov 2005

Added setup for screw and scroll chillers.

IM 743-3

Apr 2007

Removed RS-485 part number from replacement 

parts list.

IM 743-4

Apr 2009

Added TGZ model.  Corrected Figure 2 and 

corresponding table with proper network pin 

connections.  Changed Unit Setup for Modbus 

Network Control section to refer to unit keypad.

IM 743-5

Dec2010

Updated chiller models on cover page and 

password menu screens.

IM 743-6

Mar 2017

Updated Daikin Applied branding and 

associated reference, document part numbers, 

major formatting revisions, added specs, 

troubleshooting, figures and revised Setup Unit 

for Network Control and Configuration sections.

IM 743-7

Jun 2022

Corrected Software Revision section. Updated 

Reference documents.

Software Revision

  

This document supports all versions of the standard 

MicroTech II Chiller Unit Controller application and all 

subsequent versions until otherwise indicated. However, if your 

software is of a later version, some of the information in this 

document may not completely describe your application.

Limited Warranty

Consult your local Daikin Applied representative for warranty 

details. To find your local Daikin Applied representative, go to 

www.DaikinApplied.com

.

Reference Documents

Company

Number

Title

Source

Modbus-IDA.

ORG

Modbus Application 

Protocol Specification 

V1.1b

www.Modbus.

org

Modbus-IDA.

ORG

Modbus over Serial 

Line Specification and 

Implementation Guide 

V1.02

www.Modbus.

org

Daikin Applied

ED 15063

MicroTech II Modbus 

Chiller Unit Controller 

Protocol Document

www.

DaikinApplied.

com

Daikin Applied

IOM 1210

WMC - Magnetic Bearing 

Compressor Chiller 

Installation, Operation, 

and Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1274

WSC - Single Centrifugal 

Compressor Installation, 

Operation, and 

Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1281

WDC/WCC - Dual 

Centrifugal Compressor 

Installation, Operation, 

and Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1319

Templifier TGZ Heat 

Recovery Water Heaters 

Operating Manual

www.

DaikinApplied.

com

Daikin Applied

IOM 1322

WGZ - Water-Cooled 

Scroll Chiller Operation 

and Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOMM ACZ/

AGZ

(Legacy)

Air-Cooled Condensing 

Unit Installation, 

Operation, and 

Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOMM AGZ

(Legacy)

Air-Cooled Scroll Chiller 

Installation, Operation, 

and Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

IOMM WPV

(Legacy)

Centrifugal Chiller 

Installation, Operation, 

and Maintenance Manual

www.

DaikinApplied.

com

Daikin Applied

OM 1127

(Legacy)

AGS - Air-Cooled Screw 

Chiller Operating Manual

www.

DaikinApplied.

com

Daikin Applied

OM WGS

(Legacy)

Water-Cooled Screw 

Chiller Operating Manual

www.

DaikinApplied.

com

Summary of Contents for ACZ

Page 1: ...fugal Heat Recovery HSC Water Cooled Single Compressor Centrifugal Heat Recovery TGZ Templifier Water Heater TSC Water Cooled Single Compressor Centrifugal Templifier WCC Water Cooled Centrifugal Dual...

Page 2: ...ion Module 8 Network Configuration 9 Set up the Unit for Network Control 9 Network Setup for Centrifugal Chillers 9 Network Setup for all other Chillers 9 Modbus Network Addressing 9 Modbus Network Co...

Page 3: ...uent versions until otherwise indicated However if your software is of a later version some of the information in this document may not completely describe your application Limited Warranty Consult yo...

Page 4: ...s been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interfere...

Page 5: ...he communication module circuit board the Modbus network connector and 8 pin header which are described in the following section Figure 2 Communication Module Main Features Modbus Network Connector An...

Page 6: ...le with RS 485 network connector attached to module This manual IM 743 Tools Required A small flathead screwdriver or similar tool as shown in Figure 4 Needle nose pliers or similar tool as shown in F...

Page 7: ...you feel the connectors align press the communication module into the plug Verify that the module is firmly connected Figure 8 Step 3 8 Mount the plastic cover on the serial card slot Slip the cover o...

Page 8: ...card slot with the 8 pin plug that mates to the header on the communication module NOTE This operation relies more on fitting the communication module into the connector than seeing the connectors ma...

Page 9: ...ler is operational from the BAS interface Once the BAS protocol has been set proceed to the next section to set network addressing parameters Table 1 Password Menu Screen Model Menu Screen Password AG...

Page 10: ...he baud rate must match the other slave devices on the network Table 2 Network Parameters Parameter Default Range Description Network Address 0 247 Default 1 The Modbus Address i e ID or Ident Number...

Page 11: ...n no T Taps or ring layout Verify that network wiring does not exceed 4000 ft total distance limit without repeaters at 19200 bps baud Verify that polarity is maintained Check that there are end of li...

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representati...

Reviews: