Daikin ACZ Installation And Maintenance Manual Download Page 4

IM 743-7 • MICROTECH II CHILLER UNIT CONTROLLER 4 

www.DaikinApplied.com

Introduction

Hazardous Information Messages

Recognize Safety Symbols, Words and Labels

The following symbols and labels are used throughout this 

manual to indicate immediate or potential hazards.  It is the 

owner and installer’s responsibility to read and comply with 

all safety information and instructions accompanying these 

symbols.  Failure to heed safety information increases the 

risk of property damage and/or product damage, serious 

personal injury or death.  Improper installation, operation and 

maintenance can void the warranty.

 CAUTION

Cautions indicate potentially hazardous situations, which can result in 

personal injury or equipment damage if not avoided. 
Static sensitive components. Can cause equipment damage.
Discharge any static electrical charge by touching the bare metal inside the 

control panel before performing any service work. Never unplug cables, 

circuit board terminal blocks, or power plugs while power is applied to the 

panel

 WARNING

Warnings indicate potentially hazardous situations, which can result in 

property damage, severe personal injury, or death if not avoided.

 

DANGER

Dangers indicate a hazardous situation which will result in death or 

serious injury if not avoided. Electric shock hazard. Can cause personal 

injury or equipment damage. This equipment must be properly grounded. 

Connections and service to the MicroTech II Unit Controller must be 

performed only by personnel knowledgeable in the operation of the 

equipment being controlled.

 NOTICE

This equipment generates, uses and can radiate radio frequency energy 

and, if not installed and used in accordance with this instruction manual, 

may cause interference to radio communications. It has been tested and 

found to comply with the limits for a Class A digital device, pursuant to 

part 15 of the FCC rules. These limits are designed to provide reasonable 

protection against harmful interference when the equipment is operated in a 

commercial environment. Operation of this equipment in a residential area 

is likely to cause harmful interference in which case the user will be required 

to correct the interference at his or her own expense. Daikin disclaims any 

liability resulting from any interference or for the correction thereof.

The Modbus communication module connects the 

MicroTech II chiller unit controller to a building automation 

system (BAS). This interface enables the exchange of Modbus 

data points between the unit controller and the network. 
The Modbus communication module, together with the unit 

controller, support the Modbus RTU standard protocol. 

Features

•  Integration into a building automation and control system 

once inserted into the unit controller

•  LEDs that indicate communication status and network 

activity

•  Network addressing and baud rate set directly from the 

unit controller

•  Modbus application pre-installed and ready for custom 

configuration

Specifications

The following section provides a summary of technical data 

and conformance to agency listings.

General

Dimensions

3/8

” x 1 

3/16

” (60 x 30 mm)

Operating

Temperature

14 - 140°F (-10 - 60°C)

Humidity

90% RH

Storage and Transportation

Temperature

-4 - 158°F (-20 - 70°C)

Humidity

90% RH

Electrical

Power

8-38 VDC (+5% / –5%) bus connector, max. 1W

Network cable

RS-485 (EIA-485)
two-wire twisted pair, shielded AWG 20-22, max 

3281 ft 888(1000 m)

Bus connection/

Transceiver

Opto-isolated
A-, B+, GND  (2 wires)

Bus termination

120 

Ω

  end of line resistor for units at start or end 

of trunk 

Data transmission 

(baud rate)

1200, 2400, 4800, 9600, 19200, (default) bps 

Additional Components

Modbus network 

connector

RS-485 connection plug

Agency Listings - Unit Controller

US

UL 873

Canada

CSA C22.2 No. 24-93

Summary of Contents for ACZ

Page 1: ...fugal Heat Recovery HSC Water Cooled Single Compressor Centrifugal Heat Recovery TGZ Templifier Water Heater TSC Water Cooled Single Compressor Centrifugal Templifier WCC Water Cooled Centrifugal Dual...

Page 2: ...ion Module 8 Network Configuration 9 Set up the Unit for Network Control 9 Network Setup for Centrifugal Chillers 9 Network Setup for all other Chillers 9 Modbus Network Addressing 9 Modbus Network Co...

Page 3: ...uent versions until otherwise indicated However if your software is of a later version some of the information in this document may not completely describe your application Limited Warranty Consult yo...

Page 4: ...s been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interfere...

Page 5: ...he communication module circuit board the Modbus network connector and 8 pin header which are described in the following section Figure 2 Communication Module Main Features Modbus Network Connector An...

Page 6: ...le with RS 485 network connector attached to module This manual IM 743 Tools Required A small flathead screwdriver or similar tool as shown in Figure 4 Needle nose pliers or similar tool as shown in F...

Page 7: ...you feel the connectors align press the communication module into the plug Verify that the module is firmly connected Figure 8 Step 3 8 Mount the plastic cover on the serial card slot Slip the cover o...

Page 8: ...card slot with the 8 pin plug that mates to the header on the communication module NOTE This operation relies more on fitting the communication module into the connector than seeing the connectors ma...

Page 9: ...ler is operational from the BAS interface Once the BAS protocol has been set proceed to the next section to set network addressing parameters Table 1 Password Menu Screen Model Menu Screen Password AG...

Page 10: ...he baud rate must match the other slave devices on the network Table 2 Network Parameters Parameter Default Range Description Network Address 0 247 Default 1 The Modbus Address i e ID or Ident Number...

Page 11: ...n no T Taps or ring layout Verify that network wiring does not exceed 4000 ft total distance limit without repeaters at 19200 bps baud Verify that polarity is maintained Check that there are end of li...

Page 12: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representati...

Reviews: