background image

11 Maintenance and service

Installation manual

23

2MXM-A9, 3MXM-A9, 4MXM-A9, 5MXM-A9
R32 Split series
3P600450-9T – 2022.09

▪ One or more LEDs are permanently on: abnormal stop (follow the

diagnosis procedure on the back of the right side plate and refer to
service manual).

10.3.2

To perform a test run

INFORMATION

If the unit runs into an error during commissioning, see the
service manual for the detailed troubleshooting guidelines.

Prerequisite: 

Power supply MUST be in the specified range.

Prerequisite: 

Test run operation may be done in cooling or heating

mode.

Prerequisite: 

Test  run  should  be  done  in  accordance  with  the

operation  manual  of  the  indoor  unit  to  make  sure  that  all  functions
and parts are working properly.

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.

2

Measure the temperature at the indoor unit inlet and outlet after
running the unit for about 20 minutes. The difference should be
more than 8°C (cooling) or 20°C (heating).

3

First  check  operation  of  each  unit  individually,  then  check
simultaneous  operation  of  all  indoor  units.  Check  both  heating
and cooling operation.

4

When test run is finished, set the temperature to a normal level.
In cooling mode: 26~28°C, in heating mode: 20~24°C.

INFORMATION

▪ Test run can be disabled if necessary.

▪ After the unit is turned OFF, it cannot be started again

for 3 minutes.

▪ When the test run is started in the heat mode right after

turning the safety breaker on, in some cases no air will
be  output  for  about  15  minutes  in  order  to  protect  the
unit.

▪ Operate  only  air  conditioner  during  test  run.  Do  NOT

operate  the  Hybrid  for  Multi  or  the  DHW  generator
during test run.

▪ During  cooling  operation,  frost  may  form  on  the  gas

stop valve or other parts. This is normal.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

10.4

Starting up the outdoor unit

See  the  indoor  unit  installation  manual  for  configuration  and
commissioning of the system.

11

Maintenance and service

NOTICE

General  maintenance/inspection  checklist.

  Next  to  the

maintenance  instructions  in  this  chapter,  a  general
maintenance/inspection  checklist  is  also  available  on  the
Daikin Business Portal (authentication required).

The 

general 

maintenance/inspection 

checklist 

is

complementary  to  the  instructions  in  this  chapter  and  can
be  used  as  a  guideline  and  reporting  template  during
maintenance.

NOTICE

Maintenance  MUST  be  done  by  an  authorised  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

12

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

INFORMATION

To  protect  the  environment,  make  sure  to  perform  an
automatic  pump  down  operation  when  relocating  or
dismantling  the  unit.  For  the  pump  down  procedure,  refer
to the service manual or the installer reference guide.

13

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

Business Portal (authentication required).

13.1

Wiring diagram

The wiring diagram is delivered with the unit, located inside of
the outdoor unit (bottom side of the top plate).

13.1.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit.  Part  numbering  is  by  Arabic  numbers  in  ascending  order  for
each part and is represented in the overview below by "*" in the part
code.

Symbol

Meaning

Symbol Meaning

Circuit breaker

Protective earth

Connection

Protective earth (screw)

,

Connector

A

Rectifier

Earth

Relay connector

Field wiring

Short-circuit connector

Fuse

Terminal

INDOOR

Indoor unit

Terminal strip

Summary of Contents for 2MXM68A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2MXM68A2V1B9 3MXM40A2V1B9 3MXM52A2V1B9 3MXM68A2V1B9 4MXM68A2V1B9 4MXM80A2V1B9 5MXM90A2V1B9...

Page 2: ...i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vadovaujantis io dokume...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 5: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 6: ...ctrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11 2022 D DAIKIN TCF PED 014...

Page 7: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 8: ...ons 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11...

Page 9: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 10: ...5 About cool mode lock 21 9 5 1 To turn ON cool mode lock 21 10 Commissioning 21 10 1 Checklist before commissioning 22 10 2 Checklist during commissioning 22 10 3 Trial operation and testing 22 10 3...

Page 11: ...oor units shall be of non permanent type CAUTION Do NOT connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add an...

Page 12: ...NOT ONLY the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous CAUTION Do NOT insert fingers rods or other objec...

Page 13: ...50 b a 100 b a b a 350 350 50 b a 1200 100 350 a b a Air outlet b Air inlet Allow 300 mm of work space below the ceiling surface and 250 mm for piping and electrical servicing NOTICE The height of the...

Page 14: ...unit 4 M8 M10 4 2 3 To provide drainage NOTICE In cold areas do NOT use a drain socket hose and caps large small with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT fr...

Page 15: ...ation materials should be at least 20 mm to prevent condensation on the surface of the insulation Use separate thermal insulation pipes for the gas and liquid refrigerant piping 5 1 3 Refrigerant pipi...

Page 16: ...ut for 12 7 mm e Inter unit piping Coat the threaded connection port of the outdoor unit where the flare nut comes in with refrigeration oil Flare nut for mm Tightening torque N m 9 5 33 39 12 7 50 60...

Page 17: ...applicable legislation Contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The refrigerant inside the unit is mil...

Page 18: ...lculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label 2 Fix the label on the inside...

Page 19: ...the conductor Details are described in Guidelines when connecting the electrical wiring in the installer reference guide Component Power supply cable Voltage 220 240 V Current See table below A Phase...

Page 20: ...tion works with following units 3MXM40 3MXM52 FTXM FTXP FTXJ FVXM CTXA CTXM CVXM If another indoor unit is used the connector for standby electric saving MUST be plugged in The standby electricity sav...

Page 21: ...unit to heat operation 9 4 1 To turn ON heat mode lock 1 Remove the switch cover on the service PCB 2 Set the heat mode lock switch SW5 1 to ON 1 1 4 3 2 1 A 1 2 3 4 5 SW5 4 3 2 1 2 OFF ON 9 5 About c...

Page 22: ...on For more information see the indoor unit installation manual and or the indoor installer reference guide Before starting the test run measure the voltage at the primary side of the safety breaker T...

Page 23: ...ng of the system 11 Maintenance and service NOTICE General maintenance inspection checklist Next to the maintenance instructions in this chapter a general maintenance inspection checklist is also avai...

Page 24: ...Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board Symbol Meaning PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar tra...

Page 25: ...r A r B s s t t u u d p o o n l l m l w x v A v B v A v B q h 2MXM68 a Heat exchanger k 4 way valve u Thermistor gas b Outdoor air temperature thermistor l Muffler v Room c Heat exchanger thermistor...

Page 26: ...12 7CuT 12 7CuT 12 7CuT 12 7CuT 15 9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e...

Page 27: ...9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7...

Page 28: ...T 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r A r B r C r D r E s t s t s t s t s t v A v A v B v C v D v E v B v C v D v E u u u u u d p o o n l m l l w x q h y y 5MXM90 a Heat exc...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...3P600450 9T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: