3 About the box

Installation manual

12

2MXM-A9, 3MXM-A9, 4MXM-A9, 5MXM-A9

R32 Split series

3P600450-9T – 2022.09

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing the outdoor unit installation (see 

"8 Finishing the

outdoor unit installation"

 [

4

 20])

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn OFF the power supply before servicing.

▪ Install  the  switch  box  cover  before  turning  ON  the

power supply.

Commissioning (see 

"10 Commissioning"

 [

4

 21])

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When  performing  the  test  operation,  NOT  ONLY  the
outdoor unit, but the connected indoor unit will operate as
well.  Working  on  an  indoor  unit  while  performing  a  test
operation is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

Maintenance and service (see 

"11 Maintenance and

service"

 [

4

 23])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

WARNING

▪ Before  carrying  out  any  maintenance  or  repair  activity,

ALWAYS  switch  off  the  circuit  breaker  on  the  supply
panel, remove the fuses or open the protection devices
of the unit.

▪ Do NOT touch live parts for 10 minutes after the power

supply is turned off because of high voltage risk.

▪ Please  note  that  some  sections  of  the  electric

component box are hot.

▪ Make sure you do NOT touch a conductive section.

▪ Do NOT rinse the unit. This may cause electric shocks

or fire.

DANGER: RISK OF ELECTROCUTION

▪ Use this compressor on a grounded system only.

▪ Turn the power off before servicing the compressor.

▪ Reattach  the  switch  box  cover  and  service  lid  after

servicing.

CAUTION

ALWAYS wear safety glasses and protective gloves.

DANGER: RISK OF EXPLOSION

▪ Use a pipe cutter to remove the compressor.

▪ Do NOT use the brazing torch.

▪ Use approved refrigerants and lubricants only.

DANGER: RISK OF BURNING/SCALDING

Do NOT touch the compressor with bare hands.

3

About the box

Keep the following in mind:

▪ At  delivery,  the  unit  MUST  be  checked  for  damage  and

completeness.  Any  damage  or  missing  parts  MUST  be  reported
immediately to the claims agent of the carrier.

▪ Bring  the  packed  unit  as  close  as  possible  to  its  final  installation

position to prevent damage during transport.

▪ Prepare  in  advance  the  path  along  which  you  want  to  bring  the

unit to its final installation position.

3.1

Outdoor unit

3.1.1

To remove the accessories from the
outdoor unit

Make sure you have all following accessories delivered with the unit:

a

b

c

d

e

i

j

g

h

f

a

Outdoor unit installation manual

Summary of Contents for 2MXM68A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2MXM68A2V1B9 3MXM40A2V1B9 3MXM52A2V1B9 3MXM68A2V1B9 4MXM68A2V1B9 4MXM80A2V1B9 5MXM90A2V1B9...

Page 2: ...i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vadovaujantis io dokume...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 5: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 6: ...ctrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11 2022 D DAIKIN TCF PED 014...

Page 7: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 8: ...ons 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11...

Page 9: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 10: ...5 About cool mode lock 21 9 5 1 To turn ON cool mode lock 21 10 Commissioning 21 10 1 Checklist before commissioning 22 10 2 Checklist during commissioning 22 10 3 Trial operation and testing 22 10 3...

Page 11: ...oor units shall be of non permanent type CAUTION Do NOT connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add an...

Page 12: ...NOT ONLY the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous CAUTION Do NOT insert fingers rods or other objec...

Page 13: ...50 b a 100 b a b a 350 350 50 b a 1200 100 350 a b a Air outlet b Air inlet Allow 300 mm of work space below the ceiling surface and 250 mm for piping and electrical servicing NOTICE The height of the...

Page 14: ...unit 4 M8 M10 4 2 3 To provide drainage NOTICE In cold areas do NOT use a drain socket hose and caps large small with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT fr...

Page 15: ...ation materials should be at least 20 mm to prevent condensation on the surface of the insulation Use separate thermal insulation pipes for the gas and liquid refrigerant piping 5 1 3 Refrigerant pipi...

Page 16: ...ut for 12 7 mm e Inter unit piping Coat the threaded connection port of the outdoor unit where the flare nut comes in with refrigeration oil Flare nut for mm Tightening torque N m 9 5 33 39 12 7 50 60...

Page 17: ...applicable legislation Contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The refrigerant inside the unit is mil...

Page 18: ...lculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label 2 Fix the label on the inside...

Page 19: ...the conductor Details are described in Guidelines when connecting the electrical wiring in the installer reference guide Component Power supply cable Voltage 220 240 V Current See table below A Phase...

Page 20: ...tion works with following units 3MXM40 3MXM52 FTXM FTXP FTXJ FVXM CTXA CTXM CVXM If another indoor unit is used the connector for standby electric saving MUST be plugged in The standby electricity sav...

Page 21: ...unit to heat operation 9 4 1 To turn ON heat mode lock 1 Remove the switch cover on the service PCB 2 Set the heat mode lock switch SW5 1 to ON 1 1 4 3 2 1 A 1 2 3 4 5 SW5 4 3 2 1 2 OFF ON 9 5 About c...

Page 22: ...on For more information see the indoor unit installation manual and or the indoor installer reference guide Before starting the test run measure the voltage at the primary side of the safety breaker T...

Page 23: ...ng of the system 11 Maintenance and service NOTICE General maintenance inspection checklist Next to the maintenance instructions in this chapter a general maintenance inspection checklist is also avai...

Page 24: ...Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board Symbol Meaning PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar tra...

Page 25: ...r A r B s s t t u u d p o o n l l m l w x v A v B v A v B q h 2MXM68 a Heat exchanger k 4 way valve u Thermistor gas b Outdoor air temperature thermistor l Muffler v Room c Heat exchanger thermistor...

Page 26: ...12 7CuT 12 7CuT 12 7CuT 12 7CuT 15 9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e...

Page 27: ...9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7...

Page 28: ...T 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r A r B r C r D r E s t s t s t s t s t v A v A v B v C v D v E v B v C v D v E u u u u u d p o o n l m l l w x q h y y 5MXM90 a Heat exc...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...3P600450 9T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: