5 Piping installation

Installation manual

14

2MXM-A9, 3MXM-A9, 4MXM-A9, 5MXM-A9

R32 Split series

3P600450-9T – 2022.09

It  is  recommended  to  provide  at  least  150  mm  of  free  space  below
the unit (300 mm for heavy snowfall areas). Additionally, make sure
the unit is positioned at least 100 mm above the maximum expected
level of snow. If necessary, construct a pedestal. See 

"4.2 Mounting

the outdoor unit"

 [

4

 14] for more details.

In  heavy  snowfall  areas  it  is  very  important  to  select  an  installation
site  where  the  snow  will  NOT  affect  the  unit.  If  lateral  snowfall  is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.

4.2

Mounting the outdoor unit

4.2.1

To provide the installation structure

Use a vibration-proof rubber (field supply) in cases where vibrations
may be transmitted to the building.

The unit may be installed directly on a concrete veranda or another
solid surface as long as it provides proper drainage.

Prepare  4  sets  of  M8  or  M10  anchor  bolts,  nuts  and  washers  (field
supply).

20 mm

(mm)

353

600

240

240

a

a

100 mm above expected level of snow

4.2.2

To install the outdoor unit

4× M8/M10

4.2.3

To provide drainage

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(large,  small)  with  the  outdoor  unit.  Take  adequate
measures  so  that  the  evacuated  condensate  CANNOT
freeze.

NOTICE

If  the  drain  holes  of  the  outdoor  unit  are  blocked  up  by  a
mounting base or floor surface, place additional foot bases
≤30 mm under the outdoor unit's feet.

▪ Use a drain socket for drainage if necessary.

a

a

Drain hole

To close the drain holes and attach the drain
socket

1

Install  drain  caps  (accessory  f)  and  (accessory  g).  Make  sure
the edges of the drain caps close off the holes completely.

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (large).

b

Drain hole. Install a drain cap (small).

c

Drain hole for drain socket

5

Piping installation

5.1

Preparing refrigerant piping

5.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

2MXM68

Liquid piping

2× Ø6.4 mm (1/4")

Gas piping

1× Ø9.5 mm (3/8")

1× Ø12.7 mm (1/2")

Summary of Contents for 2MXM68A2V1B9

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series 2MXM68A2V1B9 3MXM40A2V1B9 3MXM52A2V1B9 3MXM68A2V1B9 4MXM68A2V1B9 4MXM80A2V1B9 5MXM90A2V1B9...

Page 2: ...i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt n uetele vadovaujantis io dokume...

Page 3: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 4: ...a f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastavalt...

Page 5: ...a TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi...

Page 6: ...ctrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11 2022 D DAIKIN TCF PED 014...

Page 7: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 8: ...ons 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the provisions of BS EN 60335 2 40 A B C DAIKIN TCF 032E23 11...

Page 9: ...urated temperature corresponding with the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate Q...

Page 10: ...5 About cool mode lock 21 9 5 1 To turn ON cool mode lock 21 10 Commissioning 21 10 1 Checklist before commissioning 22 10 2 Checklist during commissioning 22 10 3 Trial operation and testing 22 10 3...

Page 11: ...oor units shall be of non permanent type CAUTION Do NOT connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add an...

Page 12: ...NOT ONLY the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous CAUTION Do NOT insert fingers rods or other objec...

Page 13: ...50 b a 100 b a b a 350 350 50 b a 1200 100 350 a b a Air outlet b Air inlet Allow 300 mm of work space below the ceiling surface and 250 mm for piping and electrical servicing NOTICE The height of the...

Page 14: ...unit 4 M8 M10 4 2 3 To provide drainage NOTICE In cold areas do NOT use a drain socket hose and caps large small with the outdoor unit Take adequate measures so that the evacuated condensate CANNOT fr...

Page 15: ...ation materials should be at least 20 mm to prevent condensation on the surface of the insulation Use separate thermal insulation pipes for the gas and liquid refrigerant piping 5 1 3 Refrigerant pipi...

Page 16: ...ut for 12 7 mm e Inter unit piping Coat the threaded connection port of the outdoor unit where the flare nut comes in with refrigeration oil Flare nut for mm Tightening torque N m 9 5 33 39 12 7 50 60...

Page 17: ...applicable legislation Contact your installer for more information WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING The refrigerant inside the unit is mil...

Page 18: ...lculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Use the GWP value mentioned on the refrigerant charge label 2 Fix the label on the inside...

Page 19: ...the conductor Details are described in Guidelines when connecting the electrical wiring in the installer reference guide Component Power supply cable Voltage 220 240 V Current See table below A Phase...

Page 20: ...tion works with following units 3MXM40 3MXM52 FTXM FTXP FTXJ FVXM CTXA CTXM CVXM If another indoor unit is used the connector for standby electric saving MUST be plugged in The standby electricity sav...

Page 21: ...unit to heat operation 9 4 1 To turn ON heat mode lock 1 Remove the switch cover on the service PCB 2 Set the heat mode lock switch SW5 1 to ON 1 1 4 3 2 1 A 1 2 3 4 5 SW5 4 3 2 1 2 OFF ON 9 5 About c...

Page 22: ...on For more information see the indoor unit installation manual and or the indoor installer reference guide Before starting the test run measure the voltage at the primary side of the safety breaker T...

Page 23: ...ng of the system 11 Maintenance and service NOTICE General maintenance inspection checklist Next to the maintenance instructions in this chapter a general maintenance inspection checklist is also avai...

Page 24: ...Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board Symbol Meaning PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar tra...

Page 25: ...r A r B s s t t u u d p o o n l l m l w x v A v B v A v B q h 2MXM68 a Heat exchanger k 4 way valve u Thermistor gas b Outdoor air temperature thermistor l Muffler v Room c Heat exchanger thermistor...

Page 26: ...12 7CuT 12 7CuT 12 7CuT 12 7CuT 15 9CuT 15 9CuT 15 9CuT 7 9CuT 9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT S1PH d e...

Page 27: ...9 5CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT MV MV MV A B C 6 4CuT 6 4CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT S1PH SV 9 5CuT 9 5CuT 6 4CuT 12 7CuT 7 9CuT MVD 6 4CuT 15 9CuT 12 7CuT 7 9CuT 7 9CuT 7 9CuT 7 9CuT 7...

Page 28: ...T 12 7CuT 15 9CuT 9 5CuT 9 5CuT 9 5CuT d e f k a a b c g i j d r A r B r C r D r E s t s t s t s t s t v A v A v B v C v D v E v B v C v D v E u u u u u d p o o n l m l l w x q h y y 5MXM90 a Heat exc...

Page 29: ......

Page 30: ......

Page 31: ......

Page 32: ...3P600450 9T 2022 09 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: