6. Control way of Errors (if any)
1) “F-sensor” error
[ F1 ]
Cause : F-sensor open or short
Control : Condition of ambient temperature
How to reset : If F-sensor is normal, the error is terminal temperature.
2) “R-sensor” error
[ r1 ]
Cause : R-sensor open or short
Control : Condition of ambient temperature
How to reset : If R-sensor is normal, the error is terminal temperature.
3) “RT-sensor” error
[ rt ]
Cause : RT-sensor open or short (full down)
Control : Normal operation, deletion of control by RT-sensor
If RT-sensor is normal, the error is terminated automatically.
4) “D-sensor” error
[d1]
Cause : D-sensor open or short (full down)
Control : Time limit (30 min) of defrosting return
If D-sensor is normal, the error is terminated automatically.
5) “Door” error
[dr]
or
[dF]
or
[dH]
Cause : in case it senses that door is open for more than 1 hour.
Control : Deletion of function related door switch sensing
If door switch (open & close) is sensed, the error is terminated automatically.
6) “Cycle” error
[C1]
Cause : in case comp. works for over 3 hours when D-sensor temp. is over -5
℃
Control : normal operation
When D-sensor temp. is below -5
℃
in comp. off it is terminated.
7) “Return after defrosting” error
[F3]
Cause : in case defrosting return is done by time limit of 80 min
Control : Deletion of Pre-cool mode in defrosting mode
If defrosting return is done by D-sensor, it is terminated.
8) A/S forced defrosting mode
[d2]
Push “REFRIGERATOR SET” button 5 times while pushing “FREEZER SET” button
Simultaneously.
Control : A/S forced defrosting control (Pre-cool is deleted)
If D-sensor temp. is over 10
℃
, the mode is terminated automatically.
35 / 20
26 / 22
27 / 45
16 / 41
14 / 50
ON/OFF (min)
Over 29C
~ 29C
~ 19C
~ 13C
~ 7C
RT-S
6 / 4
4 / 6
3 / 7
2 / 10
3 / 50
OFF
ON/OFF (min)
Over 39C
~ 39C
~ 29C
~ 19C
~ 13C
~ 7C
RT-S
Summary of Contents for FRS-20BD
Page 4: ......
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 33: ...32 5 1 Wiring Diagram 5 DIAGRAM FRS 20BD 24BD Basic Model...
Page 34: ...33 FRS 20DD FD 24DD FD Dispenser Model...
Page 66: ......
Page 67: ......
Page 69: ...68 9 5 Dispenser Water Flow Dispenser Models Only...
Page 70: ...CABINET 69 10 EXPLODED VIEW 10 1 FRS 20BD 24BD Basic Model...
Page 71: ...EXPLODED VIEW MECH ROOM 70...
Page 72: ...EXPLODED VIEW R Room 71...
Page 73: ...72 EXPLODED VIEW F ROOM...
Page 74: ...73 EXPLODED VIEW F DOOR...
Page 75: ...74 EXPLODED VIEW R DOOR...
Page 81: ...EXPLODED VIEW 10 3 FRS 20DD FRS 24DD Dispenser Only CABINET 80...
Page 82: ...EXPLODED VIEW MECH ROOM 81...
Page 83: ...EXPLODED VIEW R Room 82...
Page 84: ...83 EXPLODED VIEW F ROOM...
Page 85: ...EXPLODED VIEW F Door 84...
Page 86: ...85 EXPLODED VIEW R Door...
Page 92: ...EXPLODED VIEW 10 5 FRS 20FD FRS 24FD Dispenser Homebar CABINET 91...
Page 93: ...EXPLODED VIEW MECH ROOM 92...
Page 94: ...EXPLODED VIEW R Room 93...
Page 95: ...94 EXPLODED VIEW F ROOM...
Page 96: ...EXPLODED VIEW F Door 95...
Page 97: ...96 EXPLODED VIEW R Door...