ENGLISH
58
Page 11.0
On page 11.0 you can set the system status in ON, OFF or controlled by a remote
signal EXT (digital input I1).
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
If EXT is selected, reading of the status of digital input I1 is enabled. When input I1
is energised the system goes ON and the pump is started (on the Home Page the
messages “EXT” and “ON” appear alternately at bottom right); when input I1 is not
energised the system goes OFF and the pump goes off (on the Home Page the
messages “EXT” and “OFF” appear alternately at bottom right).
For the connection of the inputs see par.
5.5.1
10. FACTORY
SETTINGS
Parameter
Value
Regulating mode
= Regulation with constant differential pressure
Hs (Differential Pressure Set-point)
50% of the max. pump head (see inverter sensitive
parameters set in factory)
Fs (Frequency Set-point)
90% of the pump rated frequency
Tmax 50
ºC
Operating mode
auto
Set-point reduction percentage
50 %
Twin operating mode
= Alternate every 24h
Pump start control
EXT (from remote signal on input I1).
11.
TYPES OF ALARM
Alarm Code
Alarm Symbol
Alarm Description
e0 - e16; e21
Internal Error
e17 - e19
Short Circuit
e20
Voltage Error
e22 - e30
Voltage Error
e31
Protocol Error
e32 - e35
Excess temperature
e37
Low voltage
e38
High voltage
e39 - e40
Excess current
e42
Dry operation
e43; e44; e45; e54
Pressure Sensor
e46
Pump Disconnected
Table 6: List of Alarms
Summary of Contents for MCE/C Series
Page 20: ...ITALIANO 19 Figura 8 Men MCE C...
Page 38: ...FRAN AIS 37 Figure 8 Menu MCE C...
Page 56: ...ENGLISH 55 Figure 8 MCE C Menu...
Page 66: ...DEUTSCH 65 Abbildung 3 Anschl sse...
Page 74: ...DEUTSCH 73 Abbildung 8 MCE C Men...
Page 93: ...NEDERLANDS 92 Afbeelding 8 Menu MCE C...
Page 111: ...ESPA OL 110 Figura 8 Men del MCE C...
Page 128: ...SVENSKA 127 Fig 8 Meny MCE C...
Page 133: ...132 1 Vn x n y V3 0 3 y 2 2 1 CEI 64 2 2 2 2 3 IEC 536 1 NEC...
Page 135: ...134 4 1 C EN 61800 3 2 5 IEC 536 1 NEC 22 C 5 1 22 C 3 1 LINE LN 1 1...
Page 136: ...135 4 2 2 3 22 C 22 C 22 C 5 2 22 C 4 3 1 PUMP UVW 1 22 C 22 C 1 3 4 3 A AS...
Page 141: ...140 6 L1 L2 6 5 6 2 22 C 2 Link 3 2 22 C 17 22 C 1 17 22 C 2 1 5 2 ET 3 ET 9 7 0 6 22 C...
Page 143: ...142 8 22 C 22 C 7 3 7 7 8 1 8 2 7 3 3 1 3 8 3 ON OFF...
Page 144: ...143 9 8 Home Page 60 Home Page 3...
Page 145: ...144 8 C...
Page 162: ...T RK E 161 Resim 8 MCE C Men s...
Page 167: ...166 1 Vn x n y V3 0 Sw 3 y 2 2 1 CEI 64 2 2 2 2 3 5 IEC 536 1 NEC...
Page 169: ...168 5 5 IEC 536 1 NEC MCE 22 C 5 1 MCE 22 C 3 1 LINE LN 1 1 4 mm2 inverter 2 inverter 3 PVC...
Page 173: ...172 4 11 18 J5 18 19 Vdc 50 mA V GND 4 I1 I2 I3 I4...
Page 175: ...174 5 5 5 5 3 3 J3 J4 OUT1 OUT2 V 250 A 5 2 5 mm 3 80 5 OUT1 OUT2 6 L1 L2...
Page 178: ...177 8 MCE 22 C 7 3 LED 7 7 8 1 8 2 7 3 3 1 3 8 3 ON OFF...
Page 179: ...178 9 8 60 3 OK...
Page 180: ...179 8 MCE C...
Page 197: ...ROM N 196 Figura 8 Meniu MCE C...
Page 214: ...SLOVEN INA 213 Slika 8 Menijske strani inverterja MCE C...
Page 218: ......
Page 219: ......