See
Figure 5
for an example of connection.
Figure 5: Example of Connection of Analogue Input
5.5.3 Outputs
The connections of the outputs listed below refer to the two 3-pole terminal boards J3 and J4 indicated with
the screen-printing
OUT1
and
OUT2
below which is also indicated the type of contact for the terminal (
NC
=
Normally Closed,
C
= Common,
NO
= Normally Open).
Characteristics of the output contacts
Type of contact
NO, NC, COM
Max. bearable voltage [V]
250
Max. bearable current [A]
5
If resistive load
2,5
If inductive load
Max. accepted cable section [mm²]
3,80
Table 4: Characteristics of the output contacts
Functions associated with the outputs
OUT1
Presence/Absence of alarms in the system
OUT2
Pump running/Pump stopped
In the example shown in
Figure 6
the light
L1
is lit when there is an alarm in the system and it goes off when
no kind of malfunction is found, whereas the light
L2
is lit when the pump is running and goes off when the
pump is stopped (NC logic).
Summary of Contents for MCE-150/C
Page 20: ...ITALIANO 15 Figura 8 Menù MCE C ...
Page 37: ...FRANÇAIS 31 Figure 8 Menu MCE C ...
Page 54: ...ENGLISH 48 Figure 8 MCE C Menu ...
Page 72: ...DEUTSCH 66 Abbildung 8 MCE C Menü ...
Page 89: ...NEDERLANDS 82 Afbeelding 8 Menu MCE C ...
Page 106: ...ESPAÑOL 99 Figura 8 Menú del MCE C ...
Page 123: ...SVENSKA 116 Fig 8 Meny MCE C ...
Page 140: ...РУССКИЙ 133 Схема 8 Меню МСЕ C ...
Page 157: ...TÜRKÇE 150 Resim 8 MCE C Menüsü ...
Page 174: ...ΕΛΛΗΝΙΚΑ 167 Σχήμα 8 Μενού MCE C ...
Page 191: ...ROMÂNĂ 184 Figura 8 Meniu MCE C ...
Page 208: ...SLOVENŠČINA 201 Slika 8 Menijske strani inverterja MCE C ...