PI-VLD

factory setting 

DIP switches by Software SCS deactivatable

DIP switch settings

4

1

2

OFF

use in conjunction with BSY+ drives 

OFF

ON

use as single drive 

ON

OFF

ON

---

n.c.

mode: 

"turn-before-tilt"

 

locking stroke 38 mm 
(1.49")

mode: 

"tilt-before-turn" 

locking stroke 19 mm
(0.75")

19mm 19mm

19mm 19mm

3

OFF
ON

1 2 3 4

English

English

2/12

99.824.37 2.1/10/15

3/12

99.824.37 2.1/10/15

! IMPORTANT ! Safety Notes

1.  Mounting  of  the  drive  should  be  carried  out  by  a  D+H  distributor,  whose  qualification  and    
experience is ensured by regular in-house training. 
2.  All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3.  For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4.  Observe enclosed red safety slip!
5.   Danger of violent pressure in handaccessible area.
6.  The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7.  A suitable field wiring means should be provided in the end use application.
8.  The mounting and routing of external wiring should be determined in the end product.
9.  The mounting of each unit shall be evaluated in the end use.
10.  The suitability of the leads for field wiring should be determined in the end-use application.
11.  Suitability of strain relief means in conjunction with the flexible cord shall be evaluated in the end-use,  
if applicable.
12.  The drive must be mounted a min of 8 feet above the floor or any access level.
13.  The  drives  were  not  evaluated  for  entrapment  protection  since  they  are  to  be  installed  at    
least  8  feet  above  the  floor.  Where  entrapment  is  a  consideration,  the  need  for  additional  tests  and   
evaluation should be determined during the end product investigation.
14.  The drive shall be connected to a Class 2 power supply.

For North America:
15.  The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.

The  VLD  51/038  can  be  integrated  in  almost  all 
common profiles. Please consult your D+H service 
and  sales  partner  about  precise  mounting 
specifications and CAD-data.

Attention:

  Screw  either  tappet  driver  (PI-VLD)  on 

the VLD 51/038 before mounting of the drive.

Mounting information

Drive unit with 2,5 m (98.4") silicone cable. 
Dependent on the type of window, different bracket 
sets are available separately.

Scope of supply

1 2 3 4 5 6

7 8 9 10 11 12

Mot. a

Mot. b

HS

Data a

Data b

Signal

(WH) Mot. a

(BN) Mot. b

(OG) HS

(YE) Data a

(GN) Data b

Signal

Clamping range :
28 -18 AWG
(solid or flexible)  

< optional >

Cable tie

 

Plug connection

Loop through terminals 
max. 60 V / 6 A

VLD 51/038-BSY+

1

2

3

4

5

6

7

8

9 10 11 12

Mot. a

Mot. b

HS

Data a

Data b

(WH) 

white

(BN) 

brown

(OG) 

orange

(YE) 

yellow

(GN) 

green

(PK) 

pink

(GY) 

grey

Ø max. 7 mm

(0.27")

VLD 51/038-BSY+

VLD 51/038-BSY+

-  Linear drive for locking and unlocking of         
  standard lock-sliding fittings
-  Either integrate in the window profile or
  mountable on the outer frame
-  Suitable for a complete remote control of     
  windows and flaps, in conjunction with D+H 
  window drives with BSY+ electronics.
  Integrated electronics will control the   
  connnected window drive
-  Up to 6 VLD drives synchronizable
-  Locking stroke at the drive adjustable
-  Input to move the drive into the service
  position (e. g. for window cleaning)
-  Individually programmable via software SCS

Intended use

Type  

 

 

VLD 51/038-BSY+

 

Rated voltage 

 

24 V DC ± 20 %

Nominal current 

 

1 A

 

Stroke 

 

 

19 or 38 mm * **

Runtime 

 

 

approx. 4,5 or 9 s *

Service life   

 

> 10.000 double strokes

Duty cycle 

 

 

30% (cycle time 10 min.)

Housing 

 

 

stainless steel (V2A)

Ingress protection    

IP 50

Temp. range  

 

-5 °C...+50 °C

   

 

 

 

(23 °F... 122 °F)

Connection   

 

2.5 m (97.5") silicone cable

 

Forces
- Locking direction   

max. 500 N* (112.4 lbf)

- Unlocking direction 

max. 600 N* (134.9 lbf)

- Breakaway force in
  unlocking direction  

max. 1000 N (224.8lbf)

 

  * Programmable with software SCS
** Adjustable via DIP switch

Technical data

Summary of Contents for VLD 51/038-BSY+

Page 1: ...824 37 2 1 10 15 E 222052 C US en Original instructions Page 2 es Manual original P gina 6 VLD 51 038 BSY PI VLD Please order bracket sets separately Rogamos que pidan los juegos de fijaci n por separ...

Page 2: ...connected to a Class 2 power supply For NorthAmerica 15 The Uniform Building Code Standard Vols 1 2 3 have to be observed The VLD 51 038 can be integrated in almost all common profiles Please consult...

Page 3: ...75 19mm 19mm 19mm 19mm 3 OFF ON 1 23 4 English 3 12 99 824 37 2 1 10 15 1 2 3 4 5 6 7 8 9 10 11 12 Mot a Mot b HS Data a Data b Signal WH Mot a BN Mot b OG HS YE Data a GN Data b Signal Clamping range...

Page 4: ...tch the window will be locked again For further information contact your D H service and sales partner Service position VLD 51 038 BSY 6 12 service position control plus Triggering of a single window...

Page 5: ...when mounting and starting has been carried out by an authorized D H distributor D H guarantee is expired with connection of D H components with external systems or with mixing of D H products with p...

Page 6: ...comprobaci nfinaldelproducto 14 Elactuadorhadeconectarseaunafuentedealimentaci ndeclase2 ParaEstadosUnidosdeAm rica 15 Sedeber ntenerencuentalosvol menes1 2y3delosEst ndaresUniformesdelC digoT cnicode...

Page 7: ...38 mm 1 49 Modo de servicio bascular antes de girar carrera de cierre 19 mm 0 75 19mm 19mm 19mm 19mm 3 Cable tie Sujetacables max 7 mm 0 28 rea de bornes 28 18 AWG unifilar o con hilos conductores fin...

Page 8: ...ci n de varias ventanas 1 Ventana 2 Ventana Con la entrada de posici n de servicio el WLC se desplaza hacia la posici n de giro de la ventana Para la alimentaci n de corriente el actuador debe activar...

Page 9: ...rios y embalajes sean sometidos a un proceso de recuperaci n que respete el medio ambiente No arroje las herramientas el ctricas a la basura S lo para los pa ses de la UE Conforme a la Directriz Europ...

Page 10: ...Connection Conexi n Connection via junction box Conexi n a trav s de caja de conexi n Further window drives can be parallel connected Se pueden conectar en paralelo varios motores Monitoring Supervisi...

Page 11: ...ive directly connected to WLC Actuador de ventana BSY directamente conectado al WLC Loop through terminals Bornes de enlazado max 60 V 6 A VP signal of connected BSY window drives has to be activated...

Page 12: ...7 4 9 3 All sizes in millimetre Todas las medidas en mil metros D H MechatronicAG Georg Sasse Str 28 32 Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www...

Reviews: