Attention:
When group-DIP-switch 8 is ON, the smoke vent is re-triggered during a period of 30 minutes at intervals of 2 minutes in accordance with VdS
2581, based on the set alarm direction (see DIP-switch 6). Therefor, the drive must be safeguarded against blockage in accordance with VdS 2580
Part 4.7. . All D+H drives meet this precondition. Otherwise DIP-switch 8 must be switched on OFF.

Group plug-in card GE 628 (-L) V2

GE 628-L V2

-

drives up to max. 10A can be connected to
a group plug-in card

-

possibility of combination with further
groups

-

adjustable ventilation time limitation and
OPEN-running time limitation

-

for control of ventilation drives

DIP-switch
factory setting

Group plug-in card GE 628 (-L) V2

Only possible if DIP-switch 4 = ON (memory mode in CLOSED-direction). Ventilation time can be

set by using a potentiometer.

The drives / NSHEVs will automatically close again, after the set time has expired.

Only possible if DIP-switch 1 = ON (OPEN-running time limitation).
If DIP-switch 1 is switched to ON, the OPEN-running time limitation can be re-triggered again.

Press vent button

once briefly. > The drives / NSHEVs will close to their final position.

The drives / NSHEVs will close as long as the vent button

is pressed.

Press vent button

once briefly. > The drives / NSHEVs will open to their final position.

The drives / NSHEVs will open as long as the vent button

is pressed.

The drives/ NSHEVs will close in the case of alarm.

Only possible if DIP-switch 4 = ON.
In the case of power failure, the drives/ NSHEVs.

.

During a period of 30 minutes, the smoke vent is triggered
at intervals of 2 minutes in accordance with VdS 2581.

The group plug-in card can be triggered in OPEN-direction via Az signals.

The group plug-in card can be triggered in CLOSED-direction via Zz signals.

GE 628 V2

GE 628-L V2

DIP-switch 1 on ON

OPEN-running time limitation in ventilation operation

DIP-switch 2 on ON

Ventilation time limitation

DIP-switch 3 on ON

OPEN-retriggering

DIP-switch 4 on ON

Storage operation in CLOSED-direction

DIP-switch 4 on OFF

Tip operation in CLOSED-direction

DIP-switch 5 on ON

Storage operation in OPEN-direction

DIP-switch 5 on OFF

Tip operation in OPEN-direction

DIP-switch 6 on ON

Group CLOSE in case of alarm

- no function -

DIP-switch 7 on ON

Power failure-CLOSE

- only function, if control panel
has emergency
power supply -

DIP-switch 8 on ON

Alarm re-triggering

- no function -

DIP-switch 9 on ON

DIP-switch 10 on ON

If the vent button is actuated in OPEN-direction, the drives/ NSHEVs run for
the duration of the running time.

will close

(If for example a rain detector is connected,

the switch must be ON, otherwise no closing will take place.)

Only possible if DIP-switch 5 = ON (Storage operation in OPEN-direction).
Running time in OPEN-direction can be limited by using the potentiometer.

GE 628 V2

High-Speed function:

-

for control of smoke and heat ventilation
drives in conjunction with the line plug-in
card LE 513

-

Smoke and heat ventilation re-triggering
function

-

group-fault display

-

power failure-CLOSE function

All D+H drives with SHEV high-speed function
are supported. In daily ventilation operation, a
considerable noise reduction is achieved
through the reduced drive speed. In case of
SHEV the drives run - triggered through the
orange monitoring line - with a very high speed
to reach the OPEN position defined within 60
seconds at the most.

Summary of Contents for RZN 43-E Series

Page 1: ...nstallation commissioning repair and service The highest national and international quality standards are therefore reliably fulfilled The comprehensive network of D H service and sales partners is at...

Page 2: ...d by D H for carrying out this maintenance competently and will be automatically provided with the latest maintenance instructions Following tests must be carried out during maintenance External exami...

Page 3: ...heat ventilation system under alarm conditions will occur if the inner temperature exceeds 72 C caused by the radiant heat from a fire in the immediate vicinity of the installation location VE 530 Se...

Page 4: ...er power lines In case of a cable with green yellow this must Cable and terminal boxes have to be labeled ground wire not be used Slot E1 E2 AM 44 Z Alarm cutoff module TR 42 Cutoff relay module WFR 4...

Page 5: ...function can be deactivated via the servicetool Attention Reset of the service timer can be carried out by a specialist company only who has been authorized by the appliance manufacturer close red gre...

Page 6: ...switched OFF ON for Smoke Detector Reset at the control panel This line is released by a line connected in series Every previous plug in slot after the releasing line must be occupied Both the lines...

Page 7: ...rst to penultimate smoke vent button each Malfunc tion 1 shunt connection by customer Line plug in card LE 513 continuation Parallel connection of RT 45 on LE 513 Terminal resistor for line monitoring...

Page 8: ...During a period of 30 minutes the smoke vent is triggered at intervals of 2 minutes in accordance with VdS 2581 The group plug in card can be triggered in OPEN direction viaAz signals The group plug i...

Page 9: ...llel 3 wires for each drive line simple cable length m x total current total consumption 1 2 3 4 5 6 7 8 9 10 A 3x 1 5 mm 120 60 40 30 24 20 17 15 13 12 m 3x 2 5 mm 200 100 65 50 40 33 28 25 22 20 m 5...

Page 10: ...s overridden in the case of an alarm from the Smoke and heat vent system The function Master CLOSE e g in the case of rain or a timer has a higher priority than the servo function and can be activated...

Page 11: ...g Mot a Mot b drive with SGI or ZA SG SG I black black orange 2x47kW branch box by customer terminal module EM 47 K LT MOT Mot a Mot b HS SG I SG I SGI 0 10 V 0 10 V SG 0 10 V 0 20 mA 4 20 mA BMS Mot...

Page 12: ...1 ZMP2 1 2 3 4 5 6 7 8 9 10 11 WE 516 rain wind wind 1 2 4 3 5 7 6 8 9 R W WRG 82 S 1 1 S 1 2 P3 P4 rain wind N AZ ZZ1 T ITR 79 1 6 2 7 4 3 5 230VAC 5 1 3 RTR 230 open close potential free wind rain i...

Page 13: ...w lock plug in card AE 525 A Function of DIP switches S1 1 on ON failure alarm S1 2 no function DIP switch factory setting DIP switch factory setting Function of DIP switches S1 1 on ON failure alarm...

Page 14: ...1 Bridge diagnostic pin against middle pin on line plug in card Check fuse connections cables t clamps smoke detectors and external control 2 Bridge diagnostic pin against middle pin on line plug in c...

Page 15: ...rol panel with reset button 2 Press concealed button in smoke vent button smoke vent closes 3 Red display LED in button and on line plug in unit goes out 1 Trigger external control if available 2 Smok...

Page 16: ...org Sasse Str 28 32 22949Ammersbek Tel 40 605 65 Fax 40 605 65 254 Germany 49 239 49 E Mail info dh partner com www dh partner com 2010 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Ri...

Reviews: