RZN 43xx-E
99.821.70 3.5/01/12
Weather automatic switched on
Technical Data
Type of control panel
RZN 4308-E
RZN 4316-E
RZN 4332-E
RZN 4364-E
Protection class
I
Ingress protection
IP54
Class of rating
- Monitoring
Continous duty
- Alarm / ventilation
short-time duty
Output voltage
24VDC / residual ripple
48%
Safe output
- running current of drives
- rated current of drives
Housing
sheet steel
colour of housing
RAL 7035; light grey
Rated voltage
230 VAC, 50Hz
230 VAC, 50Hz
230 VAC, 50Hz
230 VAC, 50Hz
Rated power
240 VA
500 VA
1000 VA
2000 VA
Stand-by operating
ca. 10,4 W
ca. 11 W
ca. 16,2 W
ca. 26 W
Interfering emission
DIN EN 55011; DIN EN 50081-2
Resistance to jamming
DIN EN 61000-4 -2, -3, -4
Temperature range
-5 bis +40 °C
6,4 A
12,8 A
25,6 A
51,2 A
8 A
16 A
32 A
64 A
Housing dimensions
...-E6
500 x 500 x 210
...-E6
500 x 500 x 210
...-E6
600 x 600 x 210
...-E12 800 x 1000 x 300
...-E9
600 x 600 x 210
...-E9
600 x 600 x 210
...-E9
600 x 600 x 210
...-E15 800 x 1000 x 300
...-E14
600 x 600 x 210
...-E14
600 x 600 x 210
...-E14
600 x 800 x 250
...-E20 800 x 1000 x 300
≈
Automatic temperature control
Signal "rain"
Signal "wind-force switchpoint"
Guarantee
You will get
guarantee for all D+H products from date of verified
handing over of the system up to maximal 3 years after date of delivery,
when mounting and starting has been carried out by a D+H authorized
.
D+H guarantee is expired, with connection of D+H components with
external systems or with mixing of
D+H products with parts of other
manufacturers.
2 years
distributor
Maintenance
Once a year by a specialist company authorised by the equipment
manufacturer.
-
Renew test badge.
-
Update logbook.
The respective current D+H maintenance instructions should be followed.
A D+H authorised company has been specially trained by D+H for carrying
out this maintenance competently and will be automatically provided with
the latest maintenance instructions.
Following tests must be carried out during maintenance:
-
External examination and inspection of system components
-
Measuring of insulation resistances
-
Checking of all relevant power supply units.
-
Functional testing of connected system components.
-
Logging the competent execution of maintenance and identification
thereof in accordance with directions.
Important Regulations
Regulations for Hazard detection systems VDE 0833, Guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
ventilation systems, regulations from the local fire-authorities and from
energy supply company, for mains supply connection must be observed.
Pictograph Explanation
Smoke and heat vent alarm
Control panel O.K.
Fuse drive
Power supply
Vent button function “OPEN”
Vent/ smoke vent function “CLOSE”
Fault
Battery fault
Charging voltage controller
Check pins ground fault
Regulator for wind-force switchpoint
Regulator for signal storage time
Ground fault
Smoke detector / fuse
Smoke-vent button / fuse
Window-lock group / fuse
Stroke-instantaneous value in per cent
Hysteresis
Regulator for Ventilation time
Regulator for OPEN running time
Automatic weather control activated
24 V - Emergency Supply
Emergency power supply for 72 hours.
Use only VdS approved accumulators.
:
2 x accumulator type 3 (12V, 7,0Ah ± 15%)
:
2 x accumulator type 4 (12V, 12Ah ± 15%)
:
2 x accumulator type 5 (12V, 18Ah ± 15%)
:
2 x accumulator type 6 (12V, 26Ah ± 15%)
RZN 4308-E
RZN 4316-E
RZN 4332-E
RZN 4364-E
Content
Maintenance/ Guarantee/ Pictograph / Technical Data / Emergency Supply . . . 2
Motherboard / General Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Optional Functional Extension / Wiring plan / 230V Connection . . . . . . . . . . 4
Supply plug-in card VE 520 / VE 530 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Line plug-in card LE 513 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Group plug-in card GE 628 (-L) V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Servo plug-in card SE 622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Weather plug-in card WE 516. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Window-lock plug-in cardAE 525-AandAE 526-DG. . . . . . . . . . . . . . . . . . . 13
Trouble shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Examination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15