D+H RZN 43-E Series Instructions For Use Manual Download Page 2

min

15

2

45

30

sec

20

2

60

40

OK

AUTO

M

2/16

RZN 43xx-E

99.821.70 3.5/01/12

Weather automatic switched on

Technical Data

Type of control panel

RZN 4308-E

RZN 4316-E

RZN 4332-E

RZN 4364-E

Protection class

I

Ingress protection

IP54

Class of rating
- Monitoring

Continous duty

- Alarm / ventilation

short-time duty

Output voltage

24VDC / residual ripple

48%

Safe output
- running current of drives
- rated current of drives

Housing

sheet steel

colour of housing

RAL 7035; light grey

Rated voltage

230 VAC, 50Hz

230 VAC, 50Hz

230 VAC, 50Hz

230 VAC, 50Hz

Rated power

240 VA

500 VA

1000 VA

2000 VA

Stand-by operating

ca. 10,4 W

ca. 11 W

ca. 16,2 W

ca. 26 W

Interfering emission

DIN EN 55011; DIN EN 50081-2

Resistance to jamming

DIN EN 61000-4 -2, -3, -4

Temperature range

-5 bis +40 °C

6,4 A

12,8 A

25,6 A

51,2 A

8 A

16 A

32 A

64 A

Housing dimensions

...-E6

500 x 500 x 210

...-E6

500 x 500 x 210

...-E6

600 x 600 x 210

...-E12 800 x 1000 x 300

...-E9

600 x 600 x 210

...-E9

600 x 600 x 210

...-E9

600 x 600 x 210

...-E15 800 x 1000 x 300

...-E14

600 x 600 x 210

...-E14

600 x 600 x 210

...-E14

600 x 800 x 250

...-E20 800 x 1000 x 300

Automatic temperature control

Signal "rain"

Signal "wind-force switchpoint"

Guarantee

You will get

guarantee for all D+H products from date of verified

handing over of the system up to maximal 3 years after date of delivery,
when mounting and starting has been carried out by a D+H authorized

.

D+H guarantee is expired, with connection of D+H components with
external systems or with mixing of

D+H products with parts of other

manufacturers.

2 years

distributor

Maintenance

Once a year by a specialist company authorised by the equipment
manufacturer.

-

Renew test badge.

-

Update logbook.

The respective current D+H maintenance instructions should be followed.
A D+H authorised company has been specially trained by D+H for carrying
out this maintenance competently and will be automatically provided with
the latest maintenance instructions.
Following tests must be carried out during maintenance:
-

External examination and inspection of system components

-

Measuring of insulation resistances

-

Checking of all relevant power supply units.

-

Functional testing of connected system components.

-

Logging the competent execution of maintenance and identification
thereof in accordance with directions.

Important Regulations

Regulations for Hazard detection systems VDE 0833, Guidelines for
electrical systems VdS 2221, VDE 0100, DIN 18232 for smoke and heat
ventilation systems, regulations from the local fire-authorities and from
energy supply company, for mains supply connection must be observed.

Pictograph Explanation

Smoke and heat vent alarm

Control panel O.K.

Fuse drive

Power supply

Vent button function “OPEN”

Vent/ smoke vent function “CLOSE”

Fault

Battery fault

Charging voltage controller

Check pins ground fault

Regulator for wind-force switchpoint

Regulator for signal storage time

Ground fault

Smoke detector / fuse

Smoke-vent button / fuse

Window-lock group / fuse

Stroke-instantaneous value in per cent

Hysteresis

Regulator for Ventilation time

Regulator for OPEN running time

Automatic weather control activated

24 V - Emergency Supply

Emergency power supply for 72 hours.
Use only VdS approved accumulators.

:

2 x accumulator type 3 (12V, 7,0Ah ± 15%)

:

2 x accumulator type 4 (12V, 12Ah ± 15%)

:

2 x accumulator type 5 (12V, 18Ah ± 15%)

:

2 x accumulator type 6 (12V, 26Ah ± 15%)

RZN 4308-E
RZN 4316-E
RZN 4332-E
RZN 4364-E

Content

Maintenance/ Guarantee/ Pictograph / Technical Data / Emergency Supply . . . 2
Motherboard / General Plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Optional Functional Extension / Wiring plan / 230V Connection . . . . . . . . . . 4
Supply plug-in card VE 520 / VE 530 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Line plug-in card LE 513 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Group plug-in card GE 628 (-L) V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Servo plug-in card SE 622 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-11
Weather plug-in card WE 516. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Window-lock plug-in cardAE 525-AandAE 526-DG. . . . . . . . . . . . . . . . . . . 13
Trouble shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Examination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Summary of Contents for RZN 43-E Series

Page 1: ...nstallation commissioning repair and service The highest national and international quality standards are therefore reliably fulfilled The comprehensive network of D H service and sales partners is at...

Page 2: ...d by D H for carrying out this maintenance competently and will be automatically provided with the latest maintenance instructions Following tests must be carried out during maintenance External exami...

Page 3: ...heat ventilation system under alarm conditions will occur if the inner temperature exceeds 72 C caused by the radiant heat from a fire in the immediate vicinity of the installation location VE 530 Se...

Page 4: ...er power lines In case of a cable with green yellow this must Cable and terminal boxes have to be labeled ground wire not be used Slot E1 E2 AM 44 Z Alarm cutoff module TR 42 Cutoff relay module WFR 4...

Page 5: ...function can be deactivated via the servicetool Attention Reset of the service timer can be carried out by a specialist company only who has been authorized by the appliance manufacturer close red gre...

Page 6: ...switched OFF ON for Smoke Detector Reset at the control panel This line is released by a line connected in series Every previous plug in slot after the releasing line must be occupied Both the lines...

Page 7: ...rst to penultimate smoke vent button each Malfunc tion 1 shunt connection by customer Line plug in card LE 513 continuation Parallel connection of RT 45 on LE 513 Terminal resistor for line monitoring...

Page 8: ...During a period of 30 minutes the smoke vent is triggered at intervals of 2 minutes in accordance with VdS 2581 The group plug in card can be triggered in OPEN direction viaAz signals The group plug i...

Page 9: ...llel 3 wires for each drive line simple cable length m x total current total consumption 1 2 3 4 5 6 7 8 9 10 A 3x 1 5 mm 120 60 40 30 24 20 17 15 13 12 m 3x 2 5 mm 200 100 65 50 40 33 28 25 22 20 m 5...

Page 10: ...s overridden in the case of an alarm from the Smoke and heat vent system The function Master CLOSE e g in the case of rain or a timer has a higher priority than the servo function and can be activated...

Page 11: ...g Mot a Mot b drive with SGI or ZA SG SG I black black orange 2x47kW branch box by customer terminal module EM 47 K LT MOT Mot a Mot b HS SG I SG I SGI 0 10 V 0 10 V SG 0 10 V 0 20 mA 4 20 mA BMS Mot...

Page 12: ...1 ZMP2 1 2 3 4 5 6 7 8 9 10 11 WE 516 rain wind wind 1 2 4 3 5 7 6 8 9 R W WRG 82 S 1 1 S 1 2 P3 P4 rain wind N AZ ZZ1 T ITR 79 1 6 2 7 4 3 5 230VAC 5 1 3 RTR 230 open close potential free wind rain i...

Page 13: ...w lock plug in card AE 525 A Function of DIP switches S1 1 on ON failure alarm S1 2 no function DIP switch factory setting DIP switch factory setting Function of DIP switches S1 1 on ON failure alarm...

Page 14: ...1 Bridge diagnostic pin against middle pin on line plug in card Check fuse connections cables t clamps smoke detectors and external control 2 Bridge diagnostic pin against middle pin on line plug in c...

Page 15: ...rol panel with reset button 2 Press concealed button in smoke vent button smoke vent closes 3 Red display LED in button and on line plug in unit goes out 1 Trigger external control if available 2 Smok...

Page 16: ...org Sasse Str 28 32 22949Ammersbek Tel 40 605 65 Fax 40 605 65 254 Germany 49 239 49 E Mail info dh partner com www dh partner com 2010 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Ri...

Reviews: