D+H RZN 43-E Series Instructions For Use Manual Download Page 10

622

1

2

3

4

5

6

7

8

ON

10/16

RZN 43xx-E

99.821.70 3.5/01/12

The servo plug-in unit SE 622 is used as interface
module between Building Management System
(BMS) or Central air conditioning plant (ZLT) and
D+H Smoke extraction and vent system RZN
43xx-E. The unit is to convert an analogue preset
value from the BMS into a drive stroke between 0-
100% in conjunction with D+H drive with option
"-SGI". Opening width can be steplessly
controlled, depending on the BMS input value.
For the function of the SE 622,

are

additionally required to the drive with position
indicator for actual value feedback.

Cable connection BMS - servo plug-in unit:
- provide 2 wires Ø 0,8 mm per servo plug-in

unit.

- one group plug-in unit is required per servo

plug-in unit.

- all connected drives must have the same

stroke.

- Safe closing of all drives when the setpoint

value from the BMS < 5 %.

two wires

Servo plug-in card SE 622

Technical Data:

System requirements : RZN 43xx-E /

GVL 83xx-E
in conjunction with
D+H drive with
option "-SGI"
or ZA...-SG

Input (BMS)

: selectable 0 -10V

or

0 - 20 mA

or

4 - 20 mA

Input impedance

: voltage = 50 k

current = 50

Hysteresis

: adjustable 2-10%

Output

:- 0 or 24VDC, only in

conjunction with
GE 628 (-L) V2

- 0-10 V current position
- max. 5 SE 622 per

control panel

Ω

Ω

Functional description

Factory settings

(0 - 10 V)

SG

SGI

ON

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Function:

Power failure-synchronisation

Triggering is effected as analogue setpoint value
via a 2-wire circuit. Either current-controlled with
values 0 - 20 mA, 4 - 20 mA or voltage-controlled
with values 0 - 10V. This corresponds to an
opening width of 0 - 100%. BMS input is
electrically isolated from the D+H-system
voltage.
The servo plug-in unit compares the setpoint
value from BMS with the actual value of the drive
and operates the drive to the desired position,
using the group plug-in unit. The servo function
can be switched off at the plug-in unit or by
remote control. Then the drive group can be
manually opened or closed by built-in vent
buttons or external vent buttons LT. The actual
value can be checked on a digital display on the
plug-in unit. The feedback to the BMS is provided
as analogue signal with values 0 - 10 V.
The servo function is overridden in the case of an
alarm from the Smoke and heat vent system. The
function “Master CLOSE“, e.g. in the case of rain
or a timer, has a higher priority than the servo
function and can be activated by DIP-switch (5).
The drives are automatically closed in the case of
wire break or short circuit on the setpoint value
wire.

After a power failure with the DIP switch No. 6
switched to ON, the drive will go to its position
CLOSED in order to be able to open again up to
the given value (e.g. 50% from the BMS) in the

Attention!
Encode only, if unit is not plugged-in.

OPEN direction, after the power failure has been
resolved.

The drive is controlled

automatically, so there is a potential source of
danger of pinch or shear points in the area of the
drive. With the factory-setting “OFF“, the drive
must run to position „CLOSED“ after a power
failure, via a vent button with visual contact to the
drive. For this, the automatic operation of the
servo plug-in unit SE 622 must be switched OFF
beforehand.

are

equipped with a digital pulse generator. The
servo plug-in unit must know the total pulse
number of the drive so that the setpoint value
from the BMS can be equally distributed over the
opening width. For this purpose, there is an
operating mode “Measure opening width“.
The clamps 8 + 9 (-N + Auto I/O) must be bridged
on the plug-in slot of the servo plug-in unit for the
activation of this operating mode.

Please note:

D+H Drives with the option "-SGI"

This operating mode is activated with reset button
(S4). The button (S4) must be activated for at
least for 7 seconds.

Auto

I/O

-N

SE 622

RZN 43xx-E / GVL 83xx-E

10

11

3

4

5

7

6

8

9

0

min. 7 sec.

Please note:

The drives of type ZA...-SG

Attention!

In this mode, the drive will run over

the entire stroke length in the OPEN and in the
CLOSE direction. A stop is not possible at this
time.
The measured stroke will be saved in the SE 622.

are equipped with

an analogue position indicator. The servo
plug-in unit compares the set value of BMS
with the actual value of the drive, and directs
the drive to the desired position using the
group plug-in unit.

The SE 622 is not compatible with the

SE 621! (Observe connection diagram!)

Encoding SE 622

S2

S6

S4

Master CLOSE funct.

ZA...-SG

Drive with "-SGI"

Input 4-20 mA

Input 0-20 mA

Input 0-10 V

1

OFF

ON

ON

ON

ON

ON

2

ON

OFF

OFF

OFF

3

4

5

6

7

8

Power failure sync.

OFF

OFF

ON

S2

S6

SGI

SG

no

function

Summary of Contents for RZN 43-E Series

Page 1: ...nstallation commissioning repair and service The highest national and international quality standards are therefore reliably fulfilled The comprehensive network of D H service and sales partners is at...

Page 2: ...d by D H for carrying out this maintenance competently and will be automatically provided with the latest maintenance instructions Following tests must be carried out during maintenance External exami...

Page 3: ...heat ventilation system under alarm conditions will occur if the inner temperature exceeds 72 C caused by the radiant heat from a fire in the immediate vicinity of the installation location VE 530 Se...

Page 4: ...er power lines In case of a cable with green yellow this must Cable and terminal boxes have to be labeled ground wire not be used Slot E1 E2 AM 44 Z Alarm cutoff module TR 42 Cutoff relay module WFR 4...

Page 5: ...function can be deactivated via the servicetool Attention Reset of the service timer can be carried out by a specialist company only who has been authorized by the appliance manufacturer close red gre...

Page 6: ...switched OFF ON for Smoke Detector Reset at the control panel This line is released by a line connected in series Every previous plug in slot after the releasing line must be occupied Both the lines...

Page 7: ...rst to penultimate smoke vent button each Malfunc tion 1 shunt connection by customer Line plug in card LE 513 continuation Parallel connection of RT 45 on LE 513 Terminal resistor for line monitoring...

Page 8: ...During a period of 30 minutes the smoke vent is triggered at intervals of 2 minutes in accordance with VdS 2581 The group plug in card can be triggered in OPEN direction viaAz signals The group plug i...

Page 9: ...llel 3 wires for each drive line simple cable length m x total current total consumption 1 2 3 4 5 6 7 8 9 10 A 3x 1 5 mm 120 60 40 30 24 20 17 15 13 12 m 3x 2 5 mm 200 100 65 50 40 33 28 25 22 20 m 5...

Page 10: ...s overridden in the case of an alarm from the Smoke and heat vent system The function Master CLOSE e g in the case of rain or a timer has a higher priority than the servo function and can be activated...

Page 11: ...g Mot a Mot b drive with SGI or ZA SG SG I black black orange 2x47kW branch box by customer terminal module EM 47 K LT MOT Mot a Mot b HS SG I SG I SGI 0 10 V 0 10 V SG 0 10 V 0 20 mA 4 20 mA BMS Mot...

Page 12: ...1 ZMP2 1 2 3 4 5 6 7 8 9 10 11 WE 516 rain wind wind 1 2 4 3 5 7 6 8 9 R W WRG 82 S 1 1 S 1 2 P3 P4 rain wind N AZ ZZ1 T ITR 79 1 6 2 7 4 3 5 230VAC 5 1 3 RTR 230 open close potential free wind rain i...

Page 13: ...w lock plug in card AE 525 A Function of DIP switches S1 1 on ON failure alarm S1 2 no function DIP switch factory setting DIP switch factory setting Function of DIP switches S1 1 on ON failure alarm...

Page 14: ...1 Bridge diagnostic pin against middle pin on line plug in card Check fuse connections cables t clamps smoke detectors and external control 2 Bridge diagnostic pin against middle pin on line plug in c...

Page 15: ...rol panel with reset button 2 Press concealed button in smoke vent button smoke vent closes 3 Red display LED in button and on line plug in unit goes out 1 Trigger external control if available 2 Smok...

Page 16: ...org Sasse Str 28 32 22949Ammersbek Tel 40 605 65 Fax 40 605 65 254 Germany 49 239 49 E Mail info dh partner com www dh partner com 2010 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Ri...

Reviews: