Visual inspection:
Only one master-drive allowed.
The adress is sticked on the drive.
In a group there is a master 2 and a
slave 1 drive.
Attention: only applies by factory set. as soon as
the drives were reprogramized with SCS
he factory set adressing does not apply any
longer.
Wiring:
Is the group wired correctly?
Therefore look connection diagrams.
Null balance:
It should be null balanced.
Software SCS or the special magnet
MAG 502 is required.
Call D+H Service:
Drives must be configured.
Software SCS is required.
Trouble shooting
Main closing edge
Beside closing edge
Beside
closing edge
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
6/16
7/16
English
English
99.823.97 2.8/10/21
99.823.97 2.8/10/21
Technical data
Type
KA 34-K-BSY+ Set
KA 54-K-BSY+ Set
Supply
230 V AC, +10 % / -15 %, 50 Hz
Power consumption
45 W / 75 VA
75 W / 115 VA
Nominal force
2 x 300 N
2 x 500 N
Nominal locking force
Max. 2600 N (VdS 2580: 2000 N; without bracket)
Service life
>20 000 double strokes
Duty cycle
30 % (With cycle time 10 minutes)
Housing
Aluminium, powder-coated in ~RAL 9006
Ingress protection
IP 32
(With covering stoppers delivered with bracket sets)
Temperature range
-15 ... +75 °C (VdS 2580: -5 ... +75 °C)
Fire stability
30 min / 300°C
Emission sound pressure level
LpA ≤ 70 dB(A)
Nominal stroke length *
See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings);
Locking relief activated
* Programmable with software SCS
Running speed and forces
All approx. 20 %
switch-off reserve (temporary)
Locking force adjustment
If factory-set locking pressure of approx. 150 N is not
sufficient to close the window, it can be infinitely
increased up to approx. 250 N.
Put in covering stopper after adjustment.
approx. 150 N
approx. 250 N
Ø 6 mm
Locking force adjustment
KA
34-K-BSY+:
300
N, 11,8
mm/s
KA
54-K-BSY+:
500
N, 11,8
mm/s
KA
34-K-BSY+:
300
N, 12,2
mm/s
(with
tensile
force
(1/2
nominal
load)
16,1
mm/s)
KA
54-K-BSY+:
500
N, 13,3
mm/s
(with
tensile
force
(1/2
nominal
load)
17,2
mm/s)
Closure Ranges
77
mm
5 mm/s
150
...
250
N
23
mm
KA34/54-K-BSY+ Set
KA34/54-K-BSY+ Set
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder
Maik Schmees
Member of the Board
Authorized signatory, Technical Director
12.01.2016
Maintenance and cleaning
Inspection and maintenance has to be carried out
according to D+H maintenance notes. Only original
D+H spare parts may be used. Repair is to be carried
out exclusively by D+H.
Wipe away debris or contamination with a dry, soft
cloth.
Do not use cleaning agents or solvents.
Guarantee
You will get 2 years guarantee for all D+H products
from date of verified handing over of the system up to
maximal 3 years after date of delivery, when
mounting and starting has been carried out by an
authorized D+H-distributor.
D+H guarantee is expired, with connection of D+H
components with external systems or with mixing of
D+H products with parts of other manufacturers.
A synchron-group KA-K-BSY+ can be count up to 2
drives, which communicate by a bus. Each drive has
it’s own adress. This adress is configurable with SCS.
The last drive of a synchron-group is the master,
which controls the other drives, the slaves. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive, all drives will
shut down from the master-drive.
Functional description