background image

GE 650 Set

99.824.62 1.1/06/12

7/16

English

S1.1 = ON

S1.1 = OFF

S1.2 = ON

S1.2 = OFF

S1.3 = ON

S1.4 = ON

S1.5 = ON

Only if S1.1 = OFF!

S1.6 = ON

S1.7 = ON

S1.8 = ON

S1.9 = ON

S1.10 = ON

S1.10 = OFF

The drives will be closing only so long

as the ventilating button is pressed.

Pushing the ventilation button once

^

CLOSES the drives.

The drives will be opening only so long

as the ventilating button is pressed.

Pushing the ventilation button once

OPENS the drives.

The group plug-in can be moved into the CLOSED position with Zz signals.

The group plug-in can be moved into the OPEN position with Az signals.

Power failure-CLOSED. In the event of a mains failure, the drive closes.

Ventilation time limitation

OPEN-running time limitation

Using a potentiometer, running time in OPEN direction can be limited.

If the vent button is actuated in OPEN direction, the drives will run OPEN

as long as the running time is set. Adjustment range from 2 to 60 seconds.

OPEN-retriggering. The OPEN-running time limitation can be retriggered

RWA-Nachtaktung eingeschaltet. The smoke vent is triggered for a duration of 20 minutes

in intervals of 2 minutes according to VdS 2581

High sensitivity. All faults (see Page 3) are displayed immediately.

Faults are only displayed after 90s. Brief transmission errors are ignored.

Using a potentiometer, ventilation time can be set.

Drives will automatically close again, after the adjusted time has expired.

Adjustment range from 2 to 45 minutes.

Only if S1.1 = OFF!

min

15

2

45

30

sec

20

2

60

40

S2.1 = ON

S2.2 = ON

SHEV fast mode (HS) of drives in the event of an alarm.

ATTENTION! This function must only be used in conjunction with corresponding D+H high

speed drives.

If D+H drives without high speed or third-party drives are connected, activation can

destroy the drive!

Group CLOSED in case of alarm. The drives/NSHEV's will be closing in case of alarm.

Delivery conditions

1 2

3 4

5 6

7 8

9 10

ON

1 2

ON

S1

S2

DIP switch setting

Cable lenghts and cross sections

-

ax. cable length 500 m

-

in. cable cross section 1.5 mm²

- Amaximum voltage drop of 6.5% (3%

with third-party drives) on the cables is

permitted.

- Max. 45 drives can be connected to a

group

The following two formulas must always be

used to calculate cable cross sections. The

higher value must be used.

M

M

2300

63

105

168

2000

72

121

193

1700

85

142

227

1400

104

173

276

1100

132

220

351

800

167

278

444

500

167

278

444

200

167

278

444

m

m

m

Total power

consumption in VA

5 x 1,5 mm²

5 x 2,5 mm²

5 x 4,0 mm²

Basic cable length (m) x Number all Drives

3220

Cross section (mm²) =

Einfache Leitungslänge (m)

111

Cross section (mm²) =

Formula 1:

Formula 2:

Summary of Contents for EM 650

Page 1: ...anleitung Seite 2 en fr es Original instructions Page 5 Notice originale Page 8 Manual original P gina 11 GE 650 99 824 62 1 1 06 12 X1 2 3 4 5 6 7 8 max T 10A Group Modul GM 650 1 IN 230V N X2 OUT E...

Page 2: ...ntwortung dass das unter Technische Daten beschriebene Produkt mit den folgenden Richtlinien bereinstimmt 2004 108 EG 2006 95 EG Technische Unterlagen bei D H Mechatronic AG D 22949 Ammersbek Thomas K...

Page 3: ...be spannungsfrei schaltet Der Konfigurationsmodus l sst sich durch einen Taster in der Frontblende aktivieren Diese Betriebsart wird durch die Ausgabe einer St rung angezeigt Zum aktivieren des Konfig...

Page 4: ...ltet Gem VdS 2581 wird der Rauchabzug 30 Minuten lang angesteuert Intervallzeit 2 Minuten Hohe Empfindlichkeit Alle St rungen siehe Seite 3 werden sofort angezeigt St rungen werden erst nach 90s angez...

Page 5: ...VAC cables in the same cable duct Safety notes Maintenance and cleaning Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used R...

Page 6: ...onfiguration mode can be activated by pushing a button on the front panel This mode is indicated when the fault is output Push the configuration mode button for 2 seconds to activate the configuration...

Page 7: ...immediately Faults are only displayed after 90s Brief transmission errors are ignored Using a potentiometer ventilation time can be set Drives will automatically close again after the adjusted time ha...

Page 8: ...c bles que des conducteurs 230 VAC Consignes de s curit Les appareils lectriques accessoires et emballa ges sont liminer en vue de leur r cup ration conforme l environnement Ne jetez pas d appareils...

Page 9: ...onnect es sans que le GE 650 mette apr s env 3 min les motorisations hors tension Le mode de configuration s active l aide d un bouton qui se trouve dans le cache frontal Ce mode de fonctionnement s a...

Page 10: ...rcours en ouverture peut tre r pet e Red clenchement en mode d senfumage sur ON Selon r glem Vds 2581le d senfumage doit tre command pendant 30 minutes avec un intervall de 2 minutes possible Uniqueme...

Page 11: ...ur Emplear nicamente piezas originales D H no modificadas Nunca se deber n tender l neas de 24 VDC junto con l neas de 230 VAC en la misma canaleta para cables Notas de seguridad Declaramos bajo nuest...

Page 12: ...desconecte los accionamientos de la corriente transcurridos aprox 3 min El modo de configuraci n puede activarse mediante un pulsador situado en el panel frontal Este modo de servicio se indica median...

Page 13: ...i n CERRADO mediante se ales Zz La unidad enchufable en grupo puede activarse en direcci n ABIERTO mediante se ales Az En caso de falla en la alimentaci n el ctrica el accionamiento se desplaza en dir...

Page 14: ...n OPEN or CLOSE Anschluss Connection 1 2 3 4 5 6 7 8 IN 230V N OUT E L N GM 650 Flachbandkabel Ribbon cable 1 2 3 4 5 6 7 8 9 N E L EM 650 L L N PE letzter D H Antrieb last D H Drive erster bis vorlet...

Page 15: ...650 C ble plat Cable de cinta plana 1 2 3 4 5 6 7 8 9 N E L EM 650 L L N PE dernier D H Motorisation accionamiento D H ltimo du premier l avant dernier D H Motorisation accionamiento D H primero hast...

Page 16: ...05 65 Fax 40 605 65 254 Germany 49 239 49 E Mail info dh partner com www dh partner com 2011 D H Mechatronic AG Ammersbek Technische nderungen vorbehalten Rights to technical modifications reserved So...

Reviews: