GE 650 Set
99.824.62 1.1/06/12
7/16
English
S1.1 = ON
S1.1 = OFF
S1.2 = ON
S1.2 = OFF
S1.3 = ON
S1.4 = ON
S1.5 = ON
Only if S1.1 = OFF!
S1.6 = ON
S1.7 = ON
S1.8 = ON
S1.9 = ON
S1.10 = ON
S1.10 = OFF
The drives will be closing only so long
as the ventilating button is pressed.
Pushing the ventilation button once
^
CLOSES the drives.
The drives will be opening only so long
as the ventilating button is pressed.
Pushing the ventilation button once
OPENS the drives.
The group plug-in can be moved into the CLOSED position with Zz signals.
The group plug-in can be moved into the OPEN position with Az signals.
Power failure-CLOSED. In the event of a mains failure, the drive closes.
Ventilation time limitation
OPEN-running time limitation
Using a potentiometer, running time in OPEN direction can be limited.
If the vent button is actuated in OPEN direction, the drives will run OPEN
as long as the running time is set. Adjustment range from 2 to 60 seconds.
OPEN-retriggering. The OPEN-running time limitation can be retriggered
RWA-Nachtaktung eingeschaltet. The smoke vent is triggered for a duration of 20 minutes
in intervals of 2 minutes according to VdS 2581
High sensitivity. All faults (see Page 3) are displayed immediately.
Faults are only displayed after 90s. Brief transmission errors are ignored.
Using a potentiometer, ventilation time can be set.
Drives will automatically close again, after the adjusted time has expired.
Adjustment range from 2 to 45 minutes.
Only if S1.1 = OFF!
min
15
2
45
30
sec
20
2
60
40
S2.1 = ON
S2.2 = ON
SHEV fast mode (HS) of drives in the event of an alarm.
ATTENTION! This function must only be used in conjunction with corresponding D+H high
speed drives.
If D+H drives without high speed or third-party drives are connected, activation can
destroy the drive!
Group CLOSED in case of alarm. The drives/NSHEV's will be closing in case of alarm.
Delivery conditions
1 2
3 4
5 6
7 8
9 10
ON
1 2
ON
S1
S2
DIP switch setting
Cable lenghts and cross sections
-
ax. cable length 500 m
-
in. cable cross section 1.5 mm²
- Amaximum voltage drop of 6.5% (3%
with third-party drives) on the cables is
permitted.
- Max. 45 drives can be connected to a
group
The following two formulas must always be
used to calculate cable cross sections. The
higher value must be used.
M
M
2300
63
105
168
2000
72
121
193
1700
85
142
227
1400
104
173
276
1100
132
220
351
800
167
278
444
500
167
278
444
200
167
278
444
m
m
m
Total power
consumption in VA
5 x 1,5 mm²
5 x 2,5 mm²
5 x 4,0 mm²
Basic cable length (m) x Number all Drives
3220
Cross section (mm²) =
Einfache Leitungslänge (m)
111
Cross section (mm²) =
Formula 1:
Formula 2: