99.825.21 1.3/08/13
9/28
English
CDP-TW-BSY+
Type
CDP -TW 1600 -BSY+
CDP -TW 2000 -BSY+
CDP -TW 3000 -BSY+
Power supply
24 V DC, ±15 %
24 V DC, ±15 %
24 V DC, ±15 %
Nominal current
6,0 A
6,6 A
8,0 A
Nominal force
2 x 800 N
2 x 1000 N
2 x 1500 N
Nominal locking force
2 x 1500 N
Lifetime ***
>10 000 double strokes
Reliability
Re = 400
Duty cycle
30 % (with cycle time 10 minutes)
Housing
Aluminium, PC/ABS (end covers)
Ingress protection
IP 32
Temperature range
-5 ... +75 °C
Fire stability
30 min / 300 °C
Nominal stroke length *;**
See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings),
locking relief activated (0,3 mm)
*
Programmable with software SCS
**
1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580
Technical data
OPEN
Forces
CR
III
CR
II
CR
I
2 x 800 N
2 x 800 N
2 x 800 N
2 x 500 N
CDP-TW 1600
CLOSE
2 x 1500 N
2 x 1000 N
2 x 1000 N
2 x 500 N
CDP-TW 3000
2 x 1000 N
2 x 1000 N
2 x 1000 N
2 x 500 N
CDP-TW 2000
Running speed and forces
Normal operation =
SHEV- fast running =
All forces
+ approx. 20 % switch-off reserve (temporary)
Closure
Ranges
Main closing edge
Beside
closing
edge
Beside
closing
edge
In the "CLOSE" direction the drive has an active protection
for the main closing edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for 10 seconds, then
"CLOSE" again. If after three attempts closing is not possible,
the drive remains in this position.
In addition, the drive is equipped with passive protection. The
closing speed in closing range 2 and 1 is reduced to 5 mm/s.
There are still substantial forces that
pose a risk to life and limb.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
Closing edge protection