99.825.46 1.1/09/14
6/24
English
CDP-K-BSY+
99.825.46 1.1/09/14
7/24
English
CDP-K-BSY+
Performance features
- Microprocessor controlled synchro electronics
BSY + for a precise synchronous run of up to
4 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Protection system for the main closing edge
- Locking relief after closing
- Especially quiet motor running in ventilation mode
- Symmetrical chain outlet
- Connection via pin-and-socket connector
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Intended use
- Chain drive for electric opening and closing of heavy
windows and flaps in the facade and roof area
- Operating voltage 230 V AC
- Useable for smoke ventilation, D+H Euro-SHEV
according to DIN EN 12101-2 as well as
daily natural ventilation
- Only for inside mounting
Technical data
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230V!
- Connection has to be carried out only by an
authorized electrical specialist
- Danger of violent pressure in handaccessible area
- Keep away People from the operating area of the
drive
- Keep away children from the control
- Observe pressure load diagram of the chain!
- Use only in dry rooms
- Only for inside mounting.
Use rain detector with danger of rain
(e.g. at domelights or roof windows)
- Just use unchanged original D+H parts
- Observe mounting instructions of bracket set!
Observe enclosed red safety slip!
Safety notes
Drive unit with 2,5 m silicone cable. Dependent on
the type of window, different bracket sets are
available separately.
Extent of supply
OPEN
Forces
CR
III
CR
II
CR
I
C
L
O
S
E
Running speed and forces
Normal operation =
SHEV- fast running =
All forces
+ approx. 20 % switch-off reserve (temporary)
Closure Ranges
Type
CDP 800-K-BSY+
CDP 1000-K-BSY+
CDP 1500-K-BSY+
Power supply
230 V AC, ±10 %, 50 Hz
230 V AC, ±10 %, 50 Hz
230 V AC, ±10 %, 50 Hz
Power consumption
50 W / 71 VA
60 W / 80 VA
80 W / 107 VA
Nominal force
800 N
1000 N
1500 N
Nominal locking force
1500 N
Lifetime ***
>10 000 double strokes
Reliability
Re = 400
Duty cycle
30 % (with cycle time 10 minutes)
Housing
Aluminium, PC/ABS (end covers)
Ingress protection
IP 32
Temperature range
-5 ... +75 °C
Fire stability
30 min / 300 °C
Nominal stroke length *;**
See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings),
locking relief activated (0,3 mm)
*
Programmable with software SCS
** 1000 mm max. according to VdS 2580
*** (500 mm) according to VdS 2580
Main closing edge
Beside closing edge
Beside closing edge
Closing edge protection
In the "CLOSE" direction the drive has an active protection
for the main closing edge. If there is an overload in the closing
range 3 and 2, the drive runs "OPEN" for 10 seconds, then
"CLOSE" again. If after three attempts closing is not possible,
the drive remains in this position.
In addition, the drive is equipped with passive protection. The
closing speed in closing range 2 and 1 is reduced to 5 mm/s.
There are still substantial forces that
pose a risk to life and limb.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
250
500
750
1000
1250
1500
1750
2000
1500
1000
500
0
max. Load (N)
Stroke / (mm)
Observe maximum pressure load of the chain!
Maximum pressure load of the chain is not
automatically identical with maximum pressure force
of the drive!
Pressure load diagram
Visual inspection:
Only one master-drive allowed.
The master has the last address, corresponding
to the total number of drives.
The adress is sticked on the drive.
Slaves are numbered downwards.
Example: In a group, composed of 3 drives,
there is a master 3, a slave 2 and a slave 1drive.
Attention: only applies by factory set.
As soon as the drives were reprogrammed with
SCS the addressing might vary from
factory set addressing.
Wiring:
Is the group wired correctly?
Therefore look connection diagrams.
Null balance:
It should be null balanced. (Page 8)
Software SCS or the special magnet
MAG 502 is required.
Call D+H Service:
Drives must be configured.
Software SCS is required.
Trouble shooting
A synchron-group (CDP-K-BSY+) can be count up to
8 drives, which communicate by a bus. Each drive
has it’s own adress. This adress is configurable with
software SCS.
The last drive of a synchron-group is the master,
which controls the other drives, the slaves. Different
forces between the drives of a group will balanced
with intelligent force- and position control. In case of
malfunction respective cutoff of a drive or a position
difference > 30 mm, all drives will shut down from the
master-drive.
Functional description
800 N
800 N
800 N
500 N
CDP 800
1500 N
1000 N
1000 N
500 N
CDP 1500
1000 N
1000 N
1000 N
500 N
CDP 1000