5
Technical Specification
Action
Direct / Reverse Acting
Number of pipes
Single / Dual pipe
Setpoint Temperature Range
55ºF to 85ºF (13°C to 29 °C)
Air connections
Barb fittings, 3/32 in (2.5 mm) ID tube
Maximum Operating Pipe Pressure
25 psi (170 kPa)
Airflow Usage
0.011 scfm (5.2 mL/s)
Sensitivity
Factory Adjusted to 2.0 – 2.5 PSI/F
Operating Frequency Band
2.4 GHz ISM Band
Battery Life
More than 2 years
(
with four setpoint changes per day
)
Operating Conditions
32 to 122ºF (0 to 50ºC)
95%RH Max, Noncondensing
Storage Conditions
-40 to 122ºF (-40 to 50ºC)
95%RH Max, Noncondensing
Dimensions
Length: 5.6 in (141 mm )
Width: 4.1 in (104 mm )
Depth: 2.1 in (53 mm )