WPT Installation Manual 

Document No. 910-00005-01, Rev 17 

 

 

Page 2 of 19 

 

 

Configuring the WPT 

 

Calibrating the WPT 

2.1 

Mounting the WPT 

2.1.1 

Remove the Existing Thermostat 

1.  Remove the external cover of the existing thermostat, if any.  

2.  Locate  and  remove  the  mounting  screws  and  carefully  remove  the  unit  from  the 

wall along with the attached pneumatic tubes.  

3.  Detach the old thermostat unit from the air tubes carefully.  The air tubes may not 

have a lot of slack – be careful that the tubes do not retract into the wall.  In a 2-
pipe system, note the positions of branch and main tubes.  

 

ESD Handling Precautions 

Warning! 

 

 

The WPT contains ESD sensitive circuit cards and components. 

 

Great care must be exercised while handling the WPT with the cover open. 

 

Do not touch any of the circuit boards with fingers or any part of the body. 

 

Touching  the  circuit  boards  may  cause  the  unit  to  fail  due  to  electrostatic 
discharge. 

 

Hold and handle the unit as shown in Figure 1, using the external bottom plastic 
cover as the support. 

 

 

 
Figure 1. Handling the WPT 

Do Not Touch 

Electrical 

Contacts 

Summary of Contents for WPT-800 Series

Page 1: ...he legacy pneumatic HVAC systems 1 1 Components The WPT 800 Series kit includes the following components WPT Universal Wall Bracket Mounting screws 6 x 1 self tapping x2 Wall Anchors CR123 batteries x...

Page 2: ...y not have a lot of slack be careful that the tubes do not retract into the wall In a 2 pipe system note the positions of branch and main tubes ESD Handling Precautions Warning The WPT contains ESD se...

Page 3: ...g can result if the end of the lever is allowed to move left or right by more than 1 16 Figure 2 WPT Lever 2 1 2 Installing the WPT The WPT is installed in the existing thermostat location using the U...

Page 4: ...e large center opening is aligned with the air tube s The Universal Wall Bracket is shown in Figure 4 Figure 4 Universal Wall Bracket 4 Pull the air tubes through the central opening of the Universal...

Page 5: ...tubes marked B and M on the rear of the WPT as shown in Figure 6 Connect the pneumatic tube to the M port in case of single pipe WPT Figure 6 Connecting Main and Branch Tubes to M and B Ports 7 Attac...

Page 6: ...omptly in accordance with local regulations place in plastic bag and recycle if possible Do not insert batteries with the and polarities reversed Do not short circuit Be sure to wrap each battery when...

Page 7: ...WPT Installation Manual Document No 910 00005 01 Rev 17 Page 7 of 19 Figure 8 WPT Menu Structure...

Page 8: ...dy is displayed on the LCD During this period the WPT is attempting to discover its nearest RWALs and HUSB This process should not be disturbed Wait for the dy to disappear from the LCD before perform...

Page 9: ...n F value 5 Press OVR to confirm D1 6 Repeat steps 4 and 5 to configure D2 D3 and D4 of the node ID NOTE While the node ID is being configured the corresponding bar of the battery indicator flashes Fi...

Page 10: ...gle between Standalone RF Mode On and Off In this menu when the battery icon is empty RF is off and the device is in standalone mode When the battery icon is full RF is on and the device requires a Wi...

Page 11: ...adjustment above the top surface of the Friction Clip or not less than one thread below the bottom surface of the Control Lever as depicted in Figure 15 NOTE Each battery segment on the LCD represents...

Page 12: ...A confirmation screen will appear and flash the stored control pressure for 3 seconds Repeat the calibration procedure if this value does not match the desired control pressure NOTE The WPT will autom...

Page 13: ...icator Press the or button to change the setpoint value Once the desired value is reached press the OVR button to accept the change Leaving the display on the desired value for 5 seconds will also res...

Page 14: ...Control Pressure Follow these steps to verify the control pressure Press the button and OVR button together for two seconds NOTE The display shows dt Press OVR four times The LCD displays the branch p...

Page 15: ...5 times to see the primary path C icon is displayed indicating that the ID is being displayed either a repeater ID or the HUB ID Press the OVR button again to see the wireless signal strength from th...

Page 16: ...a few seconds LC Indicates that the buttons are locked This indication disappears automatically after a few seconds E0 Discovery error Not able to connect to nearest repeater or HUSB Retry discovery b...

Page 17: ...10 If the pressure in the WPT is not the same as the main pressure try swapping the WPT with another unit For 1 pipe WPTs 1 Remove the WPT from the Universal Wall Bracket 2 Verify that the branch line...

Page 18: ...T does not have any field replaceable or repairable parts Contact the original distributor of the unit for repair or warranty service NOTE Care should be taken to keep the unit dust free during instal...

Page 19: ...Pa Airflow Usage 0 011 scfm 5 2 mL s Sensitivity Factory Adjusted to 2 0 2 5 PSI F Operating Frequency Band 2 4 GHz ISM Band Battery Life More than 2 years with four setpoint changes per day Operating...

Reviews: