WPT Installation Manual  

Document No. 910-00005-01, Rev 17 

 

 

Page 13 of 19 

 

Operation 

The  various  indicators  and  characters  that  are  displayed  on  the  LCD  display  are 
shown in the Figure 16. 

 

Figure 16. LCD Display 

 

The front panel of the LCD display is used to perform the following functions: 

 

Adjusting the setpoint temperature 

 

Turning on/off the occupancy override 

 

Measuring the branch line pressure  

3.1 

Adjusting the Setpoint Temperature 

The setpoint temperature may be shifted up or down using the 

 or 

 buttons.  To 

change the setpoint temperature: 

  Press the 

 or 

 button once to view the current setpoint along with the setpoint 

indicator. 

  Press the 

 or 

 button to change the setpoint value. 

  Once the desired value is reached, press the OVR button to accept the change.  

Leaving the display on the desired value for 5 seconds will also result in a setpoint 
change. 

The LCD display will revert to the current temperature. 

3.2 

Turning ON/OFF the Occupancy Override 

NOTE: This feature  only  works  if  the WPT  is  in  “Unoccupied”  mode  as  commanded 
by the scheduler. 

To change the occupancy state from “Unoccupied” to “Override”: 

  Press the OVR button to activate the occupancy override.  The LCD display 

flashes the override duration in hours. 

  Press the 

 or 

 button to change the override duration to desired value.  

  Once the desired value is reached, press the OVR button to accept the change.  

Leaving the display on the desired value for 5 seconds will also result in a duration 
change. 

Summary of Contents for WPT-800 Series

Page 1: ...he legacy pneumatic HVAC systems 1 1 Components The WPT 800 Series kit includes the following components WPT Universal Wall Bracket Mounting screws 6 x 1 self tapping x2 Wall Anchors CR123 batteries x...

Page 2: ...y not have a lot of slack be careful that the tubes do not retract into the wall In a 2 pipe system note the positions of branch and main tubes ESD Handling Precautions Warning The WPT contains ESD se...

Page 3: ...g can result if the end of the lever is allowed to move left or right by more than 1 16 Figure 2 WPT Lever 2 1 2 Installing the WPT The WPT is installed in the existing thermostat location using the U...

Page 4: ...e large center opening is aligned with the air tube s The Universal Wall Bracket is shown in Figure 4 Figure 4 Universal Wall Bracket 4 Pull the air tubes through the central opening of the Universal...

Page 5: ...tubes marked B and M on the rear of the WPT as shown in Figure 6 Connect the pneumatic tube to the M port in case of single pipe WPT Figure 6 Connecting Main and Branch Tubes to M and B Ports 7 Attac...

Page 6: ...omptly in accordance with local regulations place in plastic bag and recycle if possible Do not insert batteries with the and polarities reversed Do not short circuit Be sure to wrap each battery when...

Page 7: ...WPT Installation Manual Document No 910 00005 01 Rev 17 Page 7 of 19 Figure 8 WPT Menu Structure...

Page 8: ...dy is displayed on the LCD During this period the WPT is attempting to discover its nearest RWALs and HUSB This process should not be disturbed Wait for the dy to disappear from the LCD before perform...

Page 9: ...n F value 5 Press OVR to confirm D1 6 Repeat steps 4 and 5 to configure D2 D3 and D4 of the node ID NOTE While the node ID is being configured the corresponding bar of the battery indicator flashes Fi...

Page 10: ...gle between Standalone RF Mode On and Off In this menu when the battery icon is empty RF is off and the device is in standalone mode When the battery icon is full RF is on and the device requires a Wi...

Page 11: ...adjustment above the top surface of the Friction Clip or not less than one thread below the bottom surface of the Control Lever as depicted in Figure 15 NOTE Each battery segment on the LCD represents...

Page 12: ...A confirmation screen will appear and flash the stored control pressure for 3 seconds Repeat the calibration procedure if this value does not match the desired control pressure NOTE The WPT will autom...

Page 13: ...icator Press the or button to change the setpoint value Once the desired value is reached press the OVR button to accept the change Leaving the display on the desired value for 5 seconds will also res...

Page 14: ...Control Pressure Follow these steps to verify the control pressure Press the button and OVR button together for two seconds NOTE The display shows dt Press OVR four times The LCD displays the branch p...

Page 15: ...5 times to see the primary path C icon is displayed indicating that the ID is being displayed either a repeater ID or the HUB ID Press the OVR button again to see the wireless signal strength from th...

Page 16: ...a few seconds LC Indicates that the buttons are locked This indication disappears automatically after a few seconds E0 Discovery error Not able to connect to nearest repeater or HUSB Retry discovery b...

Page 17: ...10 If the pressure in the WPT is not the same as the main pressure try swapping the WPT with another unit For 1 pipe WPTs 1 Remove the WPT from the Universal Wall Bracket 2 Verify that the branch line...

Page 18: ...T does not have any field replaceable or repairable parts Contact the original distributor of the unit for repair or warranty service NOTE Care should be taken to keep the unit dust free during instal...

Page 19: ...Pa Airflow Usage 0 011 scfm 5 2 mL s Sensitivity Factory Adjusted to 2 0 2 5 PSI F Operating Frequency Band 2 4 GHz ISM Band Battery Life More than 2 years with four setpoint changes per day Operating...