Cypress Envirosystems
Doc # 152-10201-01 Rev 2.0
BBS User Manual
Page 19
Node Math function
Select this for the Steam Trap node. Enter Node1 and Node2 that will
be used to calculate the reading for new node. E.g. Node3 = Node1-
Node2
Precision
Precision is used to set the number of decimal places to display on the
readings page. If no precision is used, decimal places will be displayed
depending on how large or small the reading value is at the time.
Update Rate
Update rate as it has been configured on the field device (duration of
time between samples). This is used to determine if the field device is
inactive (no wireless data). Changing this value does not change the
update rate on the field device.
Enable Alarm
This field must be checked for the SMS alarm to be activated for the
node. If a limit is exceeded, and the SMS Alarm box is checked for the
node, an SMS Text message and/or email will be sent to all SMS Alarm
recipients.
Alarm Excursion #
This is the number of consecutive times the node data limit has is
exceeded before an SMS and/or Email notification is sent. (Only works
when SMS Alarm is checked)
Min Alarm Threshold
This is a specified lowest allowable value. If the node reading drops
below this number, an alarm condition is created.
Max Alarm Threshold
This is a specified highest allowable value. If the node reading rises
above this number, an alarm condition is created.
WTR Configuration
Select this radio button if configuring a WTR type node. Use this for
WFM and WSTM nodes as well
WTR Configuration – Log
Scale
Select this check box if the reading needs to be calculated in Log scale
WTR Device Type
Select WFM as the device.
WTR Sensor Type
Select this to specify the right sensor type. For the first node ID, select
OPT1-2, for the second Node ID select OPT1-2, for the third Node ID
select Thermocouple Type-K and for the fourth Node ID the sensor
type is ignored since this is a binary On/Off device.
Sensor Responsivity -
Volts or mA1, Volts or
mA2, Value1, Value2
Select this to calculate slope and intercept values in y= mx+B
Enter these readings for calculating the slope and intercept. This will
be used later to calculate the Min and Max values and engineering
reading. These can be either noted down from the data sheet or the
actual reading from the device. E.g. For WTR type 0-10 V, Volts1 = 0,
Volts2 =10.35, Value1 = 0.0001, Value2 = 1000