Cypress Envirosystems
Doc # 152-10201-01 Rev 2.0
BBS User Manual
Page 11
5.3.1
WSTM Readings Page
Users can specify which WSTM columns they would like to see in
READINGS
page by selecting columns from
the
SITE SETTINGS
WSTM Tab. The column selections will be saved as a browser cookie to the local computer
so users from different computers may select different columns to view.
Figure 11. Available WSTM fields (found in the Site Settings page)
In addition to the status fields detailed in Table 1 above, WSTMs will report the following in the condition
column based on the alarm profile set in the
CONFIGURATION
page.
Blowing
The trap is blowing steam. The row is highlighted in red.
Leaking
The trap is starting to blow steam. The row is highlighted in orange.
Flooded
The trap is building up condensate on the inlet. The row is highlighted in red.
Out of Service
There is no steam going to the trap. It is not being used in the system. The row is
highlighted in blue.
Offline
The WSTM is not reporting data to the BBS. The row is highlighted in yellow.
No Data
The WSTM has never reported any data to the BBS. The row is highlighted in yellow.
Good
This is the default status of the Node. The row is not highlighted.
Table 2. WSTM Condition Field
5.4
Configuring Nodes
You can add, delete, and edit node configurations by going to the
CONFIGURATION
page. This page is
password restricted, so that only the system administrator can access it. If multiple devices have been
setup to communicate with the BBS, each device will have a separate configuration page
5.4.1
Access Node Configurations
To access the Node Configuration screen:
1.
Click
CONFIGURATION
in the Main Menu.
A dialog box, shown in Figure 12, appears asking for a user name and password.