Installing the CTM-200
18
© 2021 Cypress Solutions
Complete Manual: CTM-200 R2 (Revision 1.4)
Recommended wire gauge for use with the connector is 16AWG. Note that the OUT GND connection is
connected to the CTM-200’s supply ground.
Power (Common Ground)
Switched Load
5.4.2
Input Connection
The 8 inputs may be configured in the CTM-200 for monitoring a digital DC voltage state or an analog DC
voltage. Six of the inputs are single ended and two are differential.
For digital state monitoring the minimum input voltage is 0 volts while the maximum is 36 volts.
The threshold detection voltage is 2.5 volts with 1 volt of hysteresis. Note that the IN GND connection is
referenced to the CTM-200’s supply ground.
Analog input values will be sampled and can be reported at a maximum frequency of 10Hz.