Parameter
Name
Description
Setting Range
1
∶
Time of Run
Keeps track of time when the output voltage is
active.
o4-02
Cooling Fan
Operation Time
Setting
Sets the initial value to start keeping track of
cumulative fan operation time. View the
cumulative fan operation time in U3-01.
Default: 0 h
Min.: 0 h
Max.: 6000 h
o4-06 U2 Reset Setting
Resets the data for U2-□□ (Fault Information)
as these data will not be reset by A1-03 (Reset).
0
∶
Disabled
1
∶
Enabled
Default: 0
Range: 0, 1
o4-07 kWh Monitor
Initialization
0:U3-08 and U3-09 monitor data is not reset
when the controller is initialized.
1:U3-08 and U3-09 monitor data is reset when
the controller is initialized.
Default: 0
Range: 0, 1
Group t, Auto-Tuning
t1: IM Auto-Tuning
t1-00 #1/2 Selection
1
∶
#1
Set details in d1-00 to d1-11, d2-00 to d2-10.
2
∶
#2
Set details in d1-12 to d1-22, d2-11 to d2-22.
Default
∶
1
Range: 1, 2
t1-01 Auto-Tuning
Method Selection
0
∶
Rotational Auto-Tuning
1
∶
Stationary Auto-Tuning
2
∶
Stationary Auto-Tuning for Line-to-Line
Resistance
Default
∶
0
Range: 0, 1, 2
t1-02 Output Power
Sets the Load Rated output power in kW units.
Note: 1HP (Horse Power) = 0.746kW
Default
∶
<2>
Min.: 0.00 kW
Max.: 650.00 kW
t1-03 Load Rated
Voltage
Sets the Load Rated voltage according to the
nameplate.
Default
∶
200.0 V
Min.: 0.0 V
Max.: 255.0 V <3>
t1-04 Load Rated Current Sets the Load Rated current according to the
nameplate.
Default
∶
<2>
Min.: 10% of
controller rated
current
Max.:200% of
controller rated
current
t1-05 Base Frequency
Sets the base frequency according to the
nameplate.
Default
∶
50.0 Hz
Min.: 0.0 Hz