Parameter
Name
Description
Setting Range
C6-03 Carrier Frequency
Proportional Gain
Default: Determined
by C6-00
Min.: 0
Max.: 99
C7-00 Proportional Gain
Applications by setting this gain, if the load is
heavy increase the value, and vice versa to
reduce this value
Default:50%
Min.: 1%
Max.: 100%
Group L, Frequency Command
L1: Frequency Command
L1-00
<4>
Frequency
Command 1
To use speed commands for each multi-step
speed, set E1-□□ to 5, 6, 7 and 8 (multi-step
speed command 1, 2, 3, 4). Sets E1-□□ to 9 for
Jog frequency command.
The upper limit is determined by d1-02 and
L2-00.
In PM Closed-Loop Vector Control, o1-00 will
be automatically set to 1 with the unit set to %.
When L2-00 (Frequency Upper Limit) is
adjusted, the exceeded frequency in L1-00 to
L1-15 will be automatically set to the upper
limit determined in L2-00.
Default:5.00Hz
Min.: 0.00Hz
Max.: Determined by
d1-02, L2-00
L1-01
<4>
Frequency
Command 2
Default: 8.00 Hz
Min.: 0.00 Hz
Max.: Determined by
d1-02, L2-00
L1-02
<4>
Frequency
Command 3
Default: 10.00Hz
Min.: 0.00 Hz
Max.: Determined by
d1-02, L2-00
L1-03
<4>
Frequency
Command 4
Default: 12.00Hz
Min.: 0.00Hz
Max.: Determined by
d1-02, L2-00
L1-04
<4>
Frequency
Command 5
Default: 15.00Hz
Min.: 0.00Hz
Max.: Determined by
d1-02, L2-00
L1-05
<4>
Frequency
Command 6
Default: 20.00Hz
Min.: 0.00Hz
Max.: Determined by
d1-02, L2-00
L1-06
<4>
Frequency
Command 7
Default: 25.00Hz
Min.: 0.00Hz
Max.: Determined by
d1-02, L2-00
L1-07
<4>
Frequency
Command 8
Default: 30.00Hz
Min.: 0.00Hz