CPS1000AVR
Guaranteed Uninterruptible Power System
5
4.
Setup Button:
Click the setup button to open the Setup Window.
5.
Model:
This shows the model of the CyberPower UPS that is being used.
6.
Version:
This shows the hardware version.
7.
Status Bar:
The area display messages about the status of the software.
8.
Schedule Button:
Click this button to access the Schedule Window.
POWERPANEL PLUS™ MAIN WINDOW DESCRIPTION
1. Input
Voltage:
This reading shows the
current input voltage of the utility power.
The input normally appears in green, but
will turn red if the input voltage is lower
than 85v or higher than 150v.
2. Battery
Level:
This indicator displays
the current charge on the battery. The
indicator will display a red color when a
power failure occurs.
3. Frequency:
This indicator displays the
frequency of the utility power.
4. Scheduled
On:
PowerPanel Plus™
can be scheduled to turn your computer
system on. It can only be set when a
Scheduled Off
is also set.
Scheduled On
settings that are set to occur within seven days will be displayed.
When the UPS is in standby, after the
Scheduled Off
, the using battery and check battery indicators will flash
in rotation.
5. Final
Countdown:
When PowerPanel Plus™ detects that the utility voltage is below 85 volts or above 150
volts, the
Final Countdown
will begin. When the countdown reaches zero, PowerPanel Plus™ will save and
close any open applications, and then shut down the operating system in an intelligent and orderly manner.
6.
Approximate Backup Time:
This indicator shows the
approximate
amount of backup time that is available,
based upon the battery capacity and the load on the system. This indicator can appear in red, yellow, or
green, depending upon the number of minutes available.
7. Scheduled
Off:
PowerPanel Plus™ can be set to automatically shutdown the computer system at a user
specified time.
Scheduled Off
settings that are set to occur within seven days will be displayed.
8. Temperature:
This indicator displays the internal operating temperature of the unit. If the temperature
exceeds 158°F (70°C), the indicator will change from green to red.
9. Load
Level:
This indicator shows the % of capacity of the battery outlets that is currently being used. If the
load level exceeds 90%, the indicator will change to a red color.
10. Output
Voltage:
This indicator shows the output voltage of the UPS.
POWERPANEL PLUS™ SETUP WINDOW
1. Play
Sound:
With this option enabled,
the software will play audible voice
messages through your computer
speakers. A sound card and speakers
are required
2.
Time Between Power Failure and
Shutdown:
This is the user
controllable delay between when the
power fails and the software starts the
shutdown process. If unchecked, the
unit will run on battery until the low
battery signal is received (2 minutes of
backup time remaining) and then start the shutdown process.
3.
Time Between Power Failure and Initial Warning:
This setting determines the delay between when the
power fails and the first audible alarm.
4. Delay
Between
Warning
Messages:
User adjustable setting for the delay between the audible alarms that
occur during a power failure.
5. UPS
Self-Test:
Allows the user to test the UPS without having to unplug the unit from the wall. When Run
is clicked, the will switch to battery power and the unit will beep.
6. About:
This button will display information about the software, as well as contact information.
7. Advance:
This button opens the
Advanced Setup Window
.