6.4 Gas Supply
GAS FLOW RATES:
NATURAL
GAS
1.6m3/Hour
LPG/PROPANE
0.6m3/Hour
This is a high power [14KW] appliance and needs a very strong and constant
gas supply. Before installing this appliance the gas pipe work needs to be
reviewed to ensure the gas pressure at the appliance, when on full, remains at
20mBar at all times.
If the appliance is run with a gas supply which is not suitable it will render the
appliance unreliable and possibly dangerous.
Once the fire is connected, the gas must be tested
“at the test point within the
fireplace enclosure”
as per the commissioning sequence:
1.
Other appliances in the house off.
a.
Standing Pressure – Off
b.
Inlet Pressure – On Pilot
c.
Inlet Pressure – On Full
2.
Other appliances in the house on.
a.
Standing Pressure – Off
b.
Inlet Pressure – On Pilot
c.
Inlet Pressure – On Full
3.
The pressure must remain at +/- 1mBar of the value stated on the
dataplate.
SEE IMAGE ON PAGE 11