I.L. 29-8858
Note: The battery can be replaced at any time, even
while the circuit breaker is in service, without affect
ing the operation of the circuit breaker or its protec
tion function.
A
CAUTION
CARE SHOULD BE EXERCISED WHEN REPLACING
A BATTERY TO INSURE THAT THE CORRECT
POLARITIES ARE OBSERVED. POLARITY MARK
INGS ARE SHOWN ON THE RATING PLUG WHEN
THE HINGED COVER IS OPEN AS INDICATED IN
FIG. G.
The replacement battery should be the same type or
equivalent. Acceptable 3.0 volt lithium batteries may be
Rating
Plug
Identification
Fig. 6
"Battery
Check"
Pushbutton
Typical Rating Plug
Values for
Short.
S1 and S2
instantaneous M1 and M 2
Settings
Battery
"OK" if
LED
Lights "GREEN" wnen
"Battery Check" Button ls Pushed
Trip
Unit
Connector
(Fits
into Keyed Cavity
Page 1 3
obtained from the following companies under their type
designation indicated:
Company
Model
Varta Batteries, Inc.
1 50 Clarbrook Road
Elmsford, N.Y. 1 0523
Duracell
South Broadway
Tarrytown, N.Y. 1 0591
(91 4) 591 -7000
Sanyo Electric Inc.
Battery Division
200 Riser Road
Little Ferry, N.J. 07643
Potantv
Marks
CR 1 /3N
DL 1 /3N
CR 1 /3N
Battery Remcwa l Tab
Satterv
in Top Right
Corner
of Trip Unit.
See Fig. 1 )
Fig. 7
Auxiliary Power Module
Effective May 1 997