I.L. 29-8858
r-, 1"""1
I
1
1
I
1
""
Setting lnsL
I L
m
x ln
:
®
(S)
I_
-
-
Available Settings
2. 2.5,
3, 4,
5, 6, M , , M,
In Multiples of
Rating
Plug
Amperes !In)
M1 and M2 Values are Specified on Rating Plu
g
Fig. 4.5 Instantaneous Current Settings
Note: For Testing Purposes Only: When using an
external single phase current source to test low level
ground fault current settings, it is advisable to use
the Auxiliary Power Module (APM) (See Fig. 7). Espe
cially when the single phase current is low, without
the APM it may appear as if the trip unit does not
respond until the current is well above the set value,
leading the tester to believe there is an error in the
trip unit when there is none. The reason this occurs
is that the single phase test current is not a good
simulation of the normal three phase circuit. If three
phase current had been flowing, the trip unit would
actually have performed correctly. Use the APM for
correct trip unit performance whenever single phase
tests are made.
Available Settings
�
Gnd-Fault
Setting
A, B.
C,
D.
m
X
in
E. F. H. K
e
Specific Values
Given on
CirCUit
Breaker Time-Current
Curve
and in Table
1
Fig. 4.6 Ground Fault Current Settings
Effective May 1 997
Page 9
TABLE
1
- GROUND FAU LT CUR RENT SETTINGS
GROUND FAULT CURRENT SETTINGS
(AMPERES)<D
A
B
c
D
E
F
H
K
1 00
25
30
35
40
50
60
75
1 00
200
50
60
70
80
100
120
1 50
200
@
250
63
75
BB
100
125
150
1 BB
250
300
75
90
1 05
120
1 50
180
225
300
fi)
400
w
1 00
1 20
140
160
200
240
300
400
a:
600
150
1 BO
2 1 0
w
240
300
360
450
600
a_
630
15B
1 B9
221
252
3 1 5
37B
473
630
::E
�
BOO
200
240
2BO
320
400
480
600
BOO
(!)
1 000
250
300
350
400
500
600
750
1 000
::J
..J
1 200
300
360
420
480
600
720
900
1 200
a_
(!)
1250
312
375
43B
500
625
750
938
1200
z
�
1 600
400
4BO
560
640
BOO
960
1 200
1 200
a:
2000
500
600
700
BOO
1000
1 200
1 200
1 200
Cl
2400
600
720
640
960
1 200
1200
1200
1 200
w
..J
1 200
..J
2500
625
750
B75
1 000
1 200
1 200
1200
;:!:
3000/31 50
750
900
1 050
1 200
1 200
1 200
1 200
1 200
Ul
�
3200
BOO
960
1 1 20
1 200
1 200
1 200
1200
1 200
4000
1 000
1200
1 200
1 200
1 200
1 200
1200
1200
5000
1200
1200
1 200
1200
1200
1 200
1 200
1 200
<D Tolerances on settings are
±1
0%
of values shown.
m
Refer
to
Type DS, type SPB or Series C A-Frame supplemental instruction
leaflets given in Section
9
for list of available rating plugs for each type circuit
breaker.
4.9 Ground Fault Time Delay Setting
As illustrated in Fig. 4.7, there are two different G round
Fault curve shapes, i.e. , fixed time (flat) or 12t response.
The shape selected depends on the type of selective
coordination chosen. The 12t response will provide a
longer time delay in the low-end of the ground fault cur
rent range than will the flat response.
Five flat (.1 , .2, .3, .4, .5 sec.) and three 12t (.1 *, .3*, .5*
sec.) response time delay settings are available. The 12t
response settings are identified by the suffix asterisk (*)
that appears in the setting viewing window. The 12t
response is applicable to currents less than 0.625 times
the ampere rating of the installed rating plug
(In).
For cur-
rents greater than 0.625 x
In
the 12t response reverts to
the flat response.
www
. ElectricalPartManuals
. com